Upon completing the diagnostic, a tested condenser motor and compressor by recommended amp draw and found the both of them are currently operating properly, I checked the refrigerant charge and showed proper numbers. My sub cool was 9 and superheat was 16. While testing the Run Cap. I found that it’s out of the range and recommended to customer to replace it which I got OK and complete the job. Recommendation Note: Clean Evaporator coil on the time of Tune-Up