HVAC technician, cooling, air conditioner repair. cond, 1/6 Hp, 1075/1, Rev, 208/230-1-60. Upon arrival customer stated that their main floor HVAC system wasn’t cooling. Upon inspection I found that the condensing fan motor was bad. Replaced the motor and started unit back up. Needs new capacitor. "cap,run Single,80mfd,370v,round" after replacing the condensing fan motor, the compressor wasn’t coming on. Found out that the capacitor was bad. Replaced capacitor, started unit up, found that the contacts was weak. 1 Pole, 30a, 24v. After replacing the condensing fan motor, the capacitor, I found that the contacts were weak. Replaced the contactor, started up unit and it’s working properly now. Pressures after unit ran for 10 mins, 75-230psi.
HVAC technician, cooling, air conditioner maintenance. Clean and tuned condensers York’s.
HVAC technician, heating and cooling, Commercial package roof top. York. Ordering new draft inducer motor.
HVAC technician, heating and cooling, RTU unit, Commercial York package unit
HVAC technician, heating and cooling, Packaged rooftop repair. York. Found draft inducer assembly bad.
Plumber, plumbing, tankless water heater repair. Performed service for tankless water heater
hvac technician, cooling, heating, air conditioner repair, furnace repair, Rtu repair. York. Found insulation blocking air flow
hvac technician, heating, cooling, furnace repair, air conditioner repair, Rooftop repair. York Rtu. Found insulation blocking air flow.
Furnace repair. Comformaker furnace. Replaced ignitor on furnace.
Furnace repair. Comformaker furnace. Found two out of three chambers cracked on heat exchanger.
water heater maintenance, Diagnosis of leaking A.O. Smith water heater
performed plumbing repair, Replaced master bath shower valve
Performed plumbing installation of a Garbage disposal.