Maintenance on Lennox gas furnace
West system: 1230: I found clog at exhaust transition piece. I unclogged transition drain outlet. Blew out all drain tubing and trapped. Tested operation. Installed customers new filter.
September 1, 2017: pumped down condensing unit on roof. Removed and replaced thermostatic expansion valve, using torch and brazing alloy. Attached sensing bulb outside of case. Evacuated low side to deep vacuum. Tested operation. ambient: 77.liquid line: 85 .suction line: 46 .metering device: TXV . Suction pressure: 119(40).head pressure: 280(92) . Return air: 72 .supply air: 55 .wet bulb: 61 .
Clean & check on 3 a/c systems
Serviced amana gas furnace and replaced drain hose
Furnace maintenance on Lennox system
Need to order motor from manufacturer. 900rpm. Pt. 1011404 BLW0BB - Blower motor - 3/4 or 1 hp - $708.00
Ac and heating maintenance on Amana system