On arrival system running and cooling with no issues. Customer stated that they had flipped breakers to system a couple times and each time the system resumed running. System has a contactor less board. Found no current codes, compressor capicator was reading 39 out of 45 and compressor saver kit was 0 mfd. Replaced both and advised customer to call us and not flip breakers if problem persists so we can see code causing issue. System cooling as I left.