2014 2.5t closet gas upflow. Leaks detected in evaporator coil. Circuit board not passing proper voltage through Y to outdoor contactor. Low voltage severed on condenser unit - repaired. Jumpered at the tstat and the circuit board and Y was not functioning properly. History of power outages. Forcing the compressor on, my inrush amperage exceeds the manufacturers specifications indicating internal damage. Dual run capacitor just at tolerance. No ground wire in gas furnace high voltage Circuit. Wetswitch has been taken out of circuit in the past. Blower is dirty. Due to the age, performance and parts availability I explained to Homeowner the major issues found and the saftey thereof. We discussed many repair options, but due to the aforementioned decided to speak to a CA 4/25/25 @10 to see about finding a more comfortable and affordable option of replacement. Homeowners just took on the care of their father which has ailments, so they are stressed. I offered that if an agreement w