1900 Railroad Ave
Mt Vernon, WA , WA 98273
360-219-9468

Job Locations
for anacortes, wa


Map of Anacortes WA
Aaron E.

Aaron E.


Job Checkin

*MAIL PHYSICAL COPY* Arrived on site per customer request to inspect their boiler for the upcoming winter months. Presented pricing for HVAC membership and price for furnace service without membership. Customer declined membership but agreed to furnace service price. Customer complained of a slight smell of gas. Used electronic gas sniffer to check for leaks and detected a gas leak in the flex connections. Presented pricing for replacement of gas flex, which customer accepted. Removed old gas flex connections from shut off up to gas valve. From gas valve, installed black iron fittings to accommodate drip leg and flex connections. Connected new gas flex and tested for leaks. No leaks were identified. Incoming gas pressure was 14.35 W.C. Gave unit a call for heat. Unit kicked right on. Noticed a rattling sound coming from inducer motor. Took amp reading for inducer and got a reading of 1.4 A. Due to poor reception was unable to present pricing for replacement motor at this time. Will