Arrived onsite and customer wanted us to go over hydronic system. Customer currently has a tankless water heater that is doing space heating and DHW informed customer of the dangers of doing so and that health complications can arise from having an open loop heating system. Tankless water heater seams to be able to only meet the demand of the system for DHW but cannot handle both. When turning on zones tankless will not always fire up due to what is believed to be caused by a low limit fire that will limit the minimum fire capacity on unit All zone pump modules and pumps appear to be functioning, but control strategies have no been set up properly and are likely unable to perform due to current unit installed, piping configuration, lack of hydronic knowledge. Before work had started I informed customer of issues with system and highly recommended we replace system with correct system for application. Customer stated he wanted unit looked at and fixed if it needed it. Told cust