520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Local Reviews
for collegeville, pa


Job Locations
for collegeville, pa

Shawn R.

Shawn R. Job Checkin

35 ft by 16 ft 7in total run if needed to replace all the pipe. 6ft 2in from 90°elbow to union


Barry P.

Barry P. Job Checkin

Replaced Blower wheel of Daikin MiniSplit (basement unit) Tested operation. System is operating well at the time of this service.


Barry P.

Barry P. Job Checkin

Plan me,bership Heat Tune Up Made call for heat from thermostat. Checked filter and drain. Measured temperature rise. Measured static pressure. Checked condition of both coils. Checked all wiring, control boards, electric motors and components. Checked refrigerant pressures and data. Checked electric heat operation/amp draw. Tested defrost from outdoor control. Recommended ECM surge protector for blower motors. Homeowner asked for email estimate. Heat pump system is operating well at the time of this maintenance.


Luis T.

Luis T. Job Checkin

Installation of whole house humidifier 600M, installed hunky on return, made all necessary water, electrical and ductwork connections, after installation test humidifier and set to winter 35 %, check humidifier drain ok. Showed customer how to operate humidifier.


Joe K.

Joe K. Job Checkin

Completed precision Heating tune up / inspection. Replaced flame sensor, cleaned burners and checked heat exchanger. Pulled amp draw on all major components, performed combustion and static pressure test. System running good at this point. Also completed 6 month inspection on new Mini Split System.


Luis T.

Luis T. Job Checkin

Performed ac tune up on trane ac unit, check electrical low and high voltage connections ok flushed drain ok replaced filter, check outdoor unit refrigerant pressures capacitor and contactor ok cycle unit, also look at the dining area light/electrical outlet, found breaker tripped, breaker for dining area is located at different electrical panel not the main panel, went over indoor air quality with customer, air purifier and whole house humidifier emailed proposal for recommendations


Chris B.

Chris B. Job Checkin

Performed Quality Assurance on Ductless System. Inspected units and tested drain lines on each indoor unit. Installed a Water Alarm next to the Condensation Pump in the Basement. Reviewed installation with homeowners and completed checklist form in system. This Install passed the QA Inspection.


Paul W.

Paul W. Job Checkin

Installed new Daikin mini split system. Leveled pad and installed disconnect and wired in. Ran new lineset and flared into out door unit and indoor heads. Pressure tested and evacuated. Installed new condensate pump for basement unit and ran vinyl to discharge. Ran wire to panel and installed breaker. Tested system. System working well at time of install.


Brian B.

Brian B. Job Checkin

Performed heating maintenance, checked air filter ok. Tested electric back up heaters. Checked voltage, amperage and electrical connections, measured capacitor values. Started heat pump, calculated btu output. Tested defrost cycle. Checked operation and temperature rise across coil.


Brian B.

Brian B. Job Checkin

Performed cooling maintenance, replaced standard air filter. Cleaned condensate drain and trap. Inspected cooling coil. Checked voltage, amperage and electrical connections, measured capacitor values. Started heat pump, measured refrigerant charge. Checked operation and temperature drop across coil.


Luis T.

Luis T. Job Checkin

Preformed precision heat tune up on heat pump and air handler. Replaced a 20x25x1 air filter checked heat and back up electric everything checked out ok. Checked pressures on heat pump cap and electrical connections. Compressor amps and line voltage everything checked out ok. Unit is running to factory standards. customer renewed plan


Luis T.

Luis T. Job Checkin

Had previously been onsite due to the AC not operating. Found the Compressor had failed and started leaking from the Winding Terminals. This caused the Compressor to be damaged electrically and cause failure. Removal of the old Compressor and installation of a new Compressor with Wiring Harness. Due to system being opened to atmosphere, the Filter Drier will need to be replaced as well. Braze Compressor and Filter Drier into the Outdoor Unit with Nitrogen sweeping the system. Pressure test system to ensure it is holding pressure. Perform Triple Evacuation on System. Charge system with 410-A Refrigerant. When the Compressor failed this caused damage to the Wiring at the Outdoor Disconnect/Breaker. Install a new Non-Fused Disconnect with Whip to the Outdoor Unit. Test operation of system. Please note that the Outdoor Unit could not be fully tested and additional repairs may be needed if further damage or component failure occurred that could not be tested at time of previous service.


Chris B.

Chris B. Job Checkin

Service call that the AC was not operating. Upon arrival, spoke with Owner and Tenant about issue. System was turned off at the Thermostat. Turned System to Cooling to test. Found the Blower Motor was running but the Outdoor Unit was not turning on. Tested Voltage at the Outdoor Unit, which was not receiving any Voltage. Inspected the Breaker/Disconnect which was tripped. Reset and turned back on. The Breaker tripped immediately. Also found burnt wires at the Outdoor Disconnect/Breaker. Disassembled the Outdoor Unit to Access the Compressor. The Compressor Terminals and Windings were completely melted and blown apart. Hooked gauges up to the system and found system to be out of Refrigerant. Pressure tested system with 300 PSI of Nitrogen. Found leak at the Compressor itself. Need to replace the Compressor and the Wiring Harness for the Compressor. Also would replace the Outdoor Disconnect due to the Damaged wiring which could have damaged the Breaker. Will contact York and follow up


Chris B.

Chris B. Job Checkin

Performed Six Month Inspection of Amana Heat Pump System that was installed on 7/10/2018. Replaced the 20x25x1 Air Filter. Reviewed Dip Switch Settings on Air Handler. Adjusted Profile setting to Profile D on system. Inspected Wiring on Unit and put back in operation. Tested System in Auxilary Heat Mode and then in Heat Pump Mode. Took Supply and Return Air Temperature Measurements. System is operating to standards.


Joseph D.

Joseph D. Job Checkin

Replaced the existing heat pump with a new Amana heat pump. Outdoor is on a new pad on 6 inch bump up legs. New whip and disconnect was installed. Ran a new copper lineset to the indoor. New Amana air handler was installed in the basement of the home. Re used the existing box and filter rack. Made a transition and tied it back into the supply duct. Ran a new drain to the sump pump pit. Installed EZ trap and wired it to the indoor unit. Indoor also had a 10KW electric heat kit installed. The system was tested in heat and cool and the system is running to factory standards.