520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Local Reviews
for media, pa


Job Locations
for media, pa

Barry P.

Barry P. Job Checkin

1st floor system thermostat was blank at arrival. Found dirty 16x25x1 Filter and blown 3A fuse. Found loose 24V conductor causing short. Reconnected 24V connections at Contactor coil. Verified coil was not shorted to ground and tested system operation. Low voltage short did not recur Both systems are operating well at the time of this service.


Barry P.

Barry P. Job Checkin

Plan member AC tune up; 4 ton communicating Amana system: Filter ok. Checked drain and EZ trap. Measured temperature split. Measured static pressure. Inspected both indoor and outdoor coil: Good Checked wiring, controls, electric motors and components. Checked refrigerant pressures and diagnostics p. Recommended ECM surge protector. Emailed estimate. AC system operating well at the time of this maintenance.


Barry P.

Barry P. Job Checkin

Found lose low volt conductors at out door equipment. Rewired and tested system operations/performance. Checked refrigerant pressures/diagnostics. Checked temperature split. System is operating well at the time of this service.


Kurt M.

Kurt M. Job Checkin

Performed precision a/c tune up on (2) York split a/c systems. All(8) 16x25x1 air filters are clean. Checked all electrical conections and components. Flushed both drains with water. Checked temperature split at both indoor units. Both belts for blower motors are ok. Checked refrigerant pressures and temperatures at indoor and outdoor units. Both a/c systems are working fine at time of service.


Kurt M.

Kurt M. Job Checkin

Performed precision a/c tune up on amana a/c system. Replaced Aprilaire 413 air filter. Checked all electrical conections and components. Checked temperature split at indoor unit. Blew out condensate drain. Checked refrigerant pressures and temperatures at indoor and outdoor units. A/c system is working fine at time of inspection.


Barry P.

Barry P. Job Checkin

AC Tune Up for 2 Ton R22 AC system with Piston. Steam boiler is still energized at boiler and will increase room temperature even during a call for cooling as there is no steam valve. Drain and filter ok. Capacitors ok. Controls and wiring ok, Found high superheat and low temperature split. Also found pitted contactor. Strongly Recommend replacing system due to age and expense of repairing R22 systems with refrigerant leaks. I also provided estimate to replace contactor and charge system to design levels with the reminder that that is a temporary fix that will have to be performed on an annual or semi annual basis. The recommended work can only be performed after steam boiler is shut down and we can accurately charge system. AC system will underperform unless equipment is replaced or recommended estimate is approved/completed.


Barry P.

Barry P. Job Checkin

HVAC is controlled by building automation system. Checked condition of coils. Cleaned debris from Odyssey unit. Checked all filters. Cleared, inspected, tested drains at both air handlers. Found weak 7.5uF capacitor at smaller outdoor unit. Discussed replacing this with Mike DeFrank who approved. Replaced capacitors. Systems are operating well at the time of this maintenance.


Barry P.

Barry P. Job Checkin

AC Tune Up for Sanyo R410A MiniSplit system that serves kitchen office. Checked washable filters. Measured temperature split. Checked refrigerant pressures/data. MiniSplit is operating well at the time of this maintenance.


Barry P.

Barry P. Job Checkin

AC Tune Up 2.5 Ton AC tune up 20x20x1 Filter ok at this time. Checked drain, Checked temperature split. Checked static pressure. Checked all controls, wiring, electric motors and components. Checked refrigerant pressures/data. AC System is operating well at the time of this maintenance .


Barry P.

Barry P. Job Checkin

Cooling tune up for Sanyo MiniSplit that serves Snack Bar at Rowan Hall. Checked filters. Checked operation of remote. Checked coils. Checked refrigerant pressure/superheat. MiniSplit is operating well at the time of this maintenance.


Barry P.

Barry P. Job Checkin

AC TuneUp for 2.5 Ton Amana AC system. (Chlorine’s Closet System) Made call for cooling from thermostat. Checked filter and drain. Checked all wiring, controls, electric motors and components. Measured compressor amps. Measured static pressure and temperature split. Checked refrigerant pressures/data. Air conditioner is operating well at the time of this maintenance.


Barry P.

Barry P. Job Checkin

AC Tune Up for 5 ton Trane split System. Measured temperature split. Checked all wiring, controls, electric motors and components. Checked drain and trap. Checked refrigerant pressures. Air Conditioner is operating well at the time of this maintenance.


Barry P.

Barry P. Job Checkin

3 Cooling maintenances All filters ok at this time. Made call for cooling from each thermostat. Checked all wiring, controls, electric motors and components. Measured static pressure and temperature rise of each system. Checked drains and traps. Indoor coil and outdoor coil of each system clean/in good condition. Checked refrigerant pressures/data. All AC systems ok at this time.


Luis T.

Luis T. Job Checkin

Replaced all new flue pipe for tech center basement gas furnace, adapted 6 in down to four in, use metal strap to add support to flue pipe, performed combustion test after repairs cycle gas furnace ok, would recommend having chimney inspected to make sure is clean and cleared. Office to bill for repairs


Kurt M.

Kurt M. Job Checkin

This Estimate is to replace the weak Actuator control found on the Steam line that is controlling the fan operation. 3/8/22. Replaced steam actuator control. Wired in actuator control the way it was wired before, did not operate correctly, had to change wiring and switch the equipment type switch on thermostat from gas and oil to heat pump for the fan to energize on a call for heating. Tested heating and cooling , system is working correctly at time of service.