520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Local Reviews
for media, pa


Job Locations
for media, pa

Barry P.

Barry P. Job Checkin

Disconnect and remove existing Inducer Motor and Assembly. Install a new Inducer Motor and Inducer Motor Blower Wheel Assembly. Complete all electrical connections and put system into operation. Perform Combustion Testing on system. Cycle unit to ensure proper operation. 11/26/21 Replaced Inducer motor. Tested system operation. Replaced filter. Cycled furnace from thermostat 3 times. Combustion/draft test: Good. Processed payment; collected balance. System is operating well at the time of this service.


Barry P.

Barry P. Job Checkin

No heat 88KBTU natural gas furnace (80%). Found seized inducer, no error code. Made call for heat. Manually freed seized inducer. Cleaned flame sensor. Checked all electrical. Filter should be replaced. I did not have a 20x20x1 filter on truck. Furnace runs for short lengths (2-3 minutes) before inducer seizes. Combustion/draft test: Good. Homeowner became plan member. URGENT need to determine price and availability of inducer and give price for replacement. Informed homeowner that due to age of system HVAC supply house may not have part on their shelf and earliest date for repair could be next week.


Kurt M.

Kurt M. Job Checkin

Cycled on thermostat for a call for heat. Blower came on right away. Ran air handler for about 10 minutes. Hot water coil was starting to get hot. Took away call at thermostat and fan shut off correctly. There is a very old zone valve that is falling apart and an old aquastat. If the aquastat is sticking it could be potentially keeping the fan on once the coil is hot. Explained this to the guy that runs the store upstairs. He is going to turn the thermostat to off on the weekends and see how this works if it then over heats the store or not. At this point we are not going to go any further with repairs.


Luis T.

Luis T. Job Checkin

Day one- removed attic fan to put return in same area. Installed new air handler pan on 2x6s. Installed indoor unit on pump up feet. Installed new supply plenum and return box. Installed new 8in collars with dampers. Installed 3 MVs one in each bedroom. Ran flex’s to each MV. Installed new outdoor unit on leveled stone. Still need to run lineset, insulate duct, thermostat wire and frame new return. High and low voltage, drainage, braze,pressure test, evacuate. Connect flex’s to each collar. Need big ladder or lift. Day 2- 32 ft extension ladder was too small, had to get boom lift. Installed new slim duct, power wire, condensate and refrigerant lines. Connected flex lines in attic. Completely finished with slim duct and boom lift. Final day- competed all duct connections, competed all refrigerant connections installed new thermostat and return grill. Sealed all connections installed new ez trap and wet switch. Tested system in cooling. Tested condensate drain. Will need to have mi


Kurt M.

Kurt M. Job Checkin

Replaced gas valve and performed combustion test, also checked for gas leaks , no leaks found. Found older mercury thermostat is ver in accurate and should be replaced.


Kurt M.

Kurt M. Job Checkin

Found fuse was removed from air handler. Found white wire for heating tied to common causing a short. Repaired wiring and cleaned up. Found bad zone valve, (entire zone valve body). Water constantly passes threw valve but mike is ok with this . Found thermostat not enegizing g terminal. Installed new Honeywell t-4 thermostat and tested for heating mode.


Barry P.

Barry P. Job Checkin

Replaced cod OEM spark ignitor. Tested operation. Furnace is operating well at the time of this service.


Barry P.

Barry P. Job Checkin

Replaced pilot assembly. Added ground between manifold frame and ignition control. Double checked connections at control. Cycled heat 10 time observing flame. Checked flame sense (rectification circuit) Blower wheel bearings sound poor. Combustion test:Good As I was leaving. Furnace shut off. The remaining attempts for trial for ignition gas valve would not open. I checked for 24V from control. Option are to replace gas valve or replace furnace altogether. Replaced 14x24x1 Filter for Back Office Unit. Contacted Mike to let him know hat furnace is not working/ needs a gas valve.


Barry P.

Barry P. Job Checkin

Flame cuts out randomly. Checked flues. Checked gas pressure. Checked pressure switch. Cleaned intermittent pilot assembly. Gas valve closes because of flame sense failure. Cleaned pilot tubing. Replaced filter Need to return to replace intermittent pilot assembly.


Barry P.

Barry P. Job Checkin

Found trial for ignition stopping at spark ignition for upstairs (classroom) furnace. Took ignitor out and back at terminal (control board). Trial for ignition completed. Checked flame rectification circuit. Cleaned ignitor. Checked filter. Measured temperature rise. Cycled furnace at thermostat several times. Provided email estimate to replace spark ignitor. Office to bill.


Chris B.

Chris B. Job Checkin

Performed Quality Assurance on Daikin Ductless install. Tested drain lines and checked wiring at each indoor unit. Ran each unit in cooling mode and measured air temperatures for supply and returns. Completed checklist form in system. Reviewed installation with homeowner. This Install passed the QA Inspection: 2 Yellows. Comments from QA: Use a bigger wall bracket and make sure lineset/wiring are not rubbing on nails in the ceiling bays. Customer is very happy with the install and with the installers!


David B.

David B. Job Checkin

Installed 4 new ductless wall mounted units. Installed one 18k wall unit in dining room area. Lineset ran through garage, deck, crawl space and basement to get to other side of house. Installed one 7k wall unit inside office and ran lineset through closet into basement. Installed second 7k wall unit inside office and ran lineset through closet into basement. Installed one 12k wall unit in basement exterior wall. Installed new outdoor unit on bracket. Installed new disconnect and surge protector for unit. Tested each units condensate. Tested all heads in heating and cooling. All penetrations sealed and work area cleaned.


Barry P.

Barry P. Job Checkin

Zero volts at indoor head in reception area. Reset outdoor disconnect. Found one Disconnect in tunnels manually shut off. Turned disconnect back on. Tested operation of all indoor units. Mini splits are working well at the time of this service.


Luis T.

Luis T. Job Checkin

Indoor unit pitched backwards from condensate drains. Adjusted uni strut to level unit. Added rubber pads for easier door access. Tested drain pan with 1 gallon of water. Tested Condensate drain. System draining properly now that it is pitched correctly. Insulated supply plenum and unit. Allowed unit to run for 30-40 mins to test drain. System working properly and no leaks present.


Kurt M.

Kurt M. Job Checkin

When I arrived talked to mike and the tennet, unit was full of dirt but had not been leaking any water. Thoroughly brushed out fan with a small brush(each individual fin). Wiped out entire unit and cycled on. No noise from the wheel. System is working fine at time of service.