2930 61st Street
Menomonie, WI 54751
715-283-4422

Our Top Cities


Local Reviews
for shakopee, mn


Job Locations
for shakopee, mn

Craig M.

Craig M. Job Checkin

Diagnosed 20+ year old natural gas furnace with intermittent operation and insufficient heating. Inspection revealed inducer motor running hot with excessive amp draw due to cracked/damaged wheel assembly. Removed and inspected inducer assembly, confirming significant impeller damage with contamination present in housing. Recommended replacement of inducer assembly or complete furnace replacement based on equipment age and condition.

Diagnosed 20+ year old natural gas furnace with intermittent operation and insufficient heating. Inspection revealed inducer motor running hot with excessive amp draw due to cracked/damaged wheel assembly. Removed and inspected inducer assembly, confirming significant impeller damage with contamination present in housing. Recommended replacement of inducer assembly or complete furnace replacement based on equipment age and condition. Diagnosed 20+ year old natural gas furnace with intermittent operation and insufficient heating. Inspection revealed inducer motor running hot with excessive amp draw due to cracked/damaged wheel assembly. Removed and inspected inducer assembly, confirming significant impeller damage with contamination present in housing. Recommended replacement of inducer assembly or complete furnace replacement based on equipment age and condition.

Craig M.

Craig M. Job Checkin

Diagnosed no heat condition on 4-year-old furnace system. Visual inspection and testing confirmed faulty gas valve. Successfully replaced defective valve assembly and verified proper heating operation after repair. System now functioning normally.

Diagnosed no heat condition on 4-year-old furnace system. Visual inspection and testing confirmed faulty gas valve. Successfully replaced defective valve assembly and verified proper heating operation after repair. System now functioning normally.

Chase O.

Chase O. Job Checkin

Conducted preliminary site assessment for plumbing installation project. Identified areas requiring completion include two toilet installations pending floor completion and installation of shower trim kit. Parts compatibility issues encountered with shower components; awaiting delivery of appropriate trim kit expected by week's end. Job requires return visit to complete all installations once flooring work is finished and necessary parts are received.

Conducted preliminary site assessment for plumbing installation project. Identified areas requiring completion include two toilet installations pending floor completion and installation of shower trim kit. Parts compatibility issues encountered with shower components; awaiting delivery of appropriate trim kit expected by week's end. Job requires return visit to complete all installations once flooring work is finished and necessary parts are received. Conducted preliminary site assessment for plumbing installation project. Identified areas requiring completion include two toilet installations pending floor completion and installation of shower trim kit. Parts compatibility issues encountered with shower components; awaiting delivery of appropriate trim kit expected by week's end. Job requires return visit to complete all installations once flooring work is finished and necessary parts are received.

Koshoua V.

Koshoua V. Job Checkin

Diagnosed inactive humidifier installed 4 months prior with furnace. Found water supply valve closed during original installation. Opened valve halfway, confirmed proper water flow during both heating cycle operation and idle periods. Verified system functionality with no leaks present. Provided homeowner with thermostat information for proper monitoring and operation.

Diagnosed inactive humidifier installed 4 months prior with furnace. Found water supply valve closed during original installation. Opened valve halfway, confirmed proper water flow during both heating cycle operation and idle periods. Verified system functionality with no leaks present. Provided homeowner with thermostat information for proper monitoring and operation. Diagnosed inactive humidifier installed 4 months prior with furnace. Found water supply valve closed during original installation. Opened valve halfway, confirmed proper water flow during both heating cycle operation and idle periods. Verified system functionality with no leaks present. Provided homeowner with thermostat information for proper monitoring and operation.

Roger M.

Roger M. Job Checkin

Performed comprehensive maintenance on furnace and boiler systems of undetermined age. Identified and replaced dirty filter during tune-up process. Documented equipment specifications with detailed photos of make, model, and serial numbers for service records.

Performed comprehensive maintenance on furnace and boiler systems of undetermined age. Identified and replaced dirty filter during tune-up process. Documented equipment specifications with detailed photos of make, model, and serial numbers for service records. Performed comprehensive maintenance on furnace and boiler systems of undetermined age. Identified and replaced dirty filter during tune-up process. Documented equipment specifications with detailed photos of make, model, and serial numbers for service records.

Chase O.

Chase O. Job Checkin

Completed chase installation to connect water supply line for vanity. Documented unfinished area with exposed concrete flooring and plumbing runs. Shower installation pending compatible parts. Two toilets remain to be installed pending completion of flooring work.

Completed chase installation to connect water supply line for vanity. Documented unfinished area with exposed concrete flooring and plumbing runs. Shower installation pending compatible parts. Two toilets remain to be installed pending completion of flooring work. Completed chase installation to connect water supply line for vanity. Documented unfinished area with exposed concrete flooring and plumbing runs. Shower installation pending compatible parts. Two toilets remain to be installed pending completion of flooring work.

Jared R.

Jared R. Job Checkin

Performed comprehensive geothermal system maintenance including complete tune-up of both main level and upper level furnaces. Conducted thorough inspection of all components including heat exchangers (noting rust/degradation in primary exchanger), burners, safety switches, gas pressures, and combustion air systems. Verified proper operation of the geothermal heat pump, checked refrigerant levels, inspected wiring connections, and confirmed all systems functioning within normal parameters.

Performed comprehensive geothermal system maintenance including complete tune-up of both main level and upper level furnaces. Conducted thorough inspection of all components including heat exchangers (noting rust/degradation in primary exchanger), burners, safety switches, gas pressures, and combustion air systems. Verified proper operation of the geothermal heat pump, checked refrigerant levels, inspected wiring connections, and confirmed all systems functioning within normal parameters. Performed comprehensive geothermal system maintenance including complete tune-up of both main level and upper level furnaces. Conducted thorough inspection of all components including heat exchangers (noting rust/degradation in primary exchanger), burners, safety switches, gas pressures, and combustion air systems. Verified proper operation of the geothermal heat pump, checked refrigerant levels, inspected wiring connections, and confirmed all systems functioning within normal parameters.

Chase O.

Chase O. Job Checkin

Completed 4-hour service call to install customer-supplied toilet and bathroom vanity faucet. Successfully installed new black matte finish widespread faucet on oval white sink. This was a return visit to complete previously started work.

Completed 4-hour service call to install customer-supplied toilet and bathroom vanity faucet. Successfully installed new black matte finish widespread faucet on oval white sink. This was a return visit to complete previously started work. Completed 4-hour service call to install customer-supplied toilet and bathroom vanity faucet. Successfully installed new black matte finish widespread faucet on oval white sink. This was a return visit to complete previously started work.

Robert J.

Robert J. Job Checkin

Responded to customer's kitchen sink leak where the shut off valve was leaking and faucet was corroded. Installed customer-supplied faucet (providing a missing locking nut) and replaced the cold-side shut off valve. Final inspection confirmed no active leaks in the system.

Responded to customer's kitchen sink leak where the shut off valve was leaking and faucet was corroded. Installed customer-supplied faucet (providing a missing locking nut) and replaced the cold-side shut off valve. Final inspection confirmed no active leaks in the system. Responded to customer's kitchen sink leak where the shut off valve was leaking and faucet was corroded. Installed customer-supplied faucet (providing a missing locking nut) and replaced the cold-side shut off valve. Final inspection confirmed no active leaks in the system.

Koshoua V.

Koshoua V. Job Checkin

Performed annual furnace tune-up on 6-year-old system. Replaced extremely dirty air filter contaminated with smoke residue and soot-like deposits. Discovered rust buildup on heat exchanger and burners with water streaking. Adjusted excessively high gas pressure which successfully lowered carbon monoxide readings to acceptable levels. Cleaned flame sensor rod and verified proper heating operation.

Performed annual furnace tune-up on 6-year-old system. Replaced extremely dirty air filter contaminated with smoke residue and soot-like deposits. Discovered rust buildup on heat exchanger and burners with water streaking. Adjusted excessively high gas pressure which successfully lowered carbon monoxide readings to acceptable levels. Cleaned flame sensor rod and verified proper heating operation. Performed annual furnace tune-up on 6-year-old system. Replaced extremely dirty air filter contaminated with smoke residue and soot-like deposits. Discovered rust buildup on heat exchanger and burners with water streaking. Adjusted excessively high gas pressure which successfully lowered carbon monoxide readings to acceptable levels. Cleaned flame sensor rod and verified proper heating operation.

Roger M.

Roger M. Job Checkin

Diagnosed AC system exhibiting no cooling and found refrigerant leak at condenser coil with infrared leak detector, verified by visible water dripping into furnace. Replaced defective condenser coil to restore proper system operation and cooling capacity.

Diagnosed AC system exhibiting no cooling and found refrigerant leak at condenser coil with infrared leak detector, verified by visible water dripping into furnace. Replaced defective condenser coil to restore proper system operation and cooling capacity. Diagnosed AC system exhibiting no cooling and found refrigerant leak at condenser coil with infrared leak detector, verified by visible water dripping into furnace. Replaced defective condenser coil to restore proper system operation and cooling capacity.

Roger M.

Roger M. Job Checkin

Responded to no-cooling complaint for a 25-year-old HVAC system showing 7° temperature differential from setpoint. Diagnostic testing revealed failed disconnect fuses. Replaced fuses, restoring proper system operation and cooling functionality.

Responded to no-cooling complaint for a 25-year-old HVAC system showing 7° temperature differential from setpoint. Diagnostic testing revealed failed disconnect fuses. Replaced fuses, restoring proper system operation and cooling functionality. Responded to no-cooling complaint for a 25-year-old HVAC system showing 7° temperature differential from setpoint. Diagnostic testing revealed failed disconnect fuses. Replaced fuses, restoring proper system operation and cooling functionality.

Koshoua V.

Koshoua V. Job Checkin

Performed furnace tune-up on FRP unit of unknown age. Detected critical safety issues including a cracked heat exchanger, extremely dirty blower motor, and dangerously elevated carbon monoxide levels exceeding 100 ppm. Showed homeowner the cracked heat exchanger and carbon monoxide readings. Set up a sales appointment to discuss replacement options.

Performed furnace tune-up on FRP unit of unknown age. Detected critical safety issues including a cracked heat exchanger, extremely dirty blower motor, and dangerously elevated carbon monoxide levels exceeding 100 ppm. Showed homeowner the cracked heat exchanger and carbon monoxide readings. Set up a sales appointment to discuss replacement options. Performed furnace tune-up on FRP unit of unknown age. Detected critical safety issues including a cracked heat exchanger, extremely dirty blower motor, and dangerously elevated carbon monoxide levels exceeding 100 ppm. Showed homeowner the cracked heat exchanger and carbon monoxide readings. Set up a sales appointment to discuss replacement options.

Chase O.

Chase O. Job Checkin

Completed preliminary installation work in bathroom undergoing renovation, including assessment of plumbing connections for customer-supplied fixtures (two toilets, three faucets, and two shower trim kits). Evaluated kitchen area for refrigerator water line hookup with all necessary connection points identified and prepared for final fixture installation.

Completed preliminary installation work in bathroom undergoing renovation, including assessment of plumbing connections for customer-supplied fixtures (two toilets, three faucets, and two shower trim kits). Evaluated kitchen area for refrigerator water line hookup with all necessary connection points identified and prepared for final fixture installation. Completed preliminary installation work in bathroom undergoing renovation, including assessment of plumbing connections for customer-supplied fixtures (two toilets, three faucets, and two shower trim kits). Evaluated kitchen area for refrigerator water line hookup with all necessary connection points identified and prepared for final fixture installation.

Charles P.

Charles P. Job Checkin

Diagnosed and repaired pinhole leak in 1/2" copper supply line to toilet that was causing water damage to bathroom floor and adjacent closet. Customer had water service shut off upon arrival. Completed necessary repairs, restoring water service and eliminating the leak.

Diagnosed and repaired pinhole leak in 1/2" copper supply line to toilet that was causing water damage to bathroom floor and adjacent closet. Customer had water service shut off upon arrival. Completed necessary repairs, restoring water service and eliminating the leak. Diagnosed and repaired pinhole leak in 1/2" copper supply line to toilet that was causing water damage to bathroom floor and adjacent closet. Customer had water service shut off upon arrival. Completed necessary repairs, restoring water service and eliminating the leak.