03JUL2024 Jason Brown Arrived for previous customer no cool. Spoke with homeowner about the systems performance. It’s not keeping up, it used to but now it’s not. It’s seems to be working now but the other day it got up in the 80s. Inspected equipment found blower and coil good, ac relatively clean. Washed condenser coils, removed blower motor and verified wheel and balance. Cycled cooling and checked pressures. AC Calls for 13 degrees of subcooling. Currently reading 4. With homeowner permission I weighed in 1lb of 410a to achieve a 14 degree cooling. Temp split increased 2 degrees to 17 degrees. System is cooling to its best abilities at this time.