22MAY2024 Jason Brown Arrived for repeat customer leak search. Spoke with Barbara about the scope of work. Captured r22 in compressor and pressurized system to 400 psi nitrogen. Performed leak search on equipment with no hits. Monitored pressure and had a .01 psi drop about every 30 seconds. Inspected lineset. Lineset runs underground. Peeled back armaflex from around concrete penetration and performed leak search there. Immediately hit. Triple checked area to confirm leak. Discussed replacement options with Barbara. We are still deciding between Carrier and American Standard. With either system we are replacing the disconnect whip and lineset. The installation will come with a new easy to use thermostat. We will shift the heat pump over to accommodate the electrical meter. System is not working at this time. Please let us know if you need an additional portable AC, or anything in the mean time. Thank you!