2330 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Job Locations
for atlantic beach, nc


Map of Atlantic Beach NC
Romario  T.

Romario T.


Job Checkin

Wiring was correct, no improper wiring was found. Line voltage was being sent to the fan motor. Tech initially believed the fan motor had failed. Traced the wiring ll the way to the fan motor and found a burnt plug connection at the compressor compartment which is a quick disconnect for the fan motor. Water may have slipped inside the connection since it is located on a area where water can get in. Tech spliced the wires to the condenser fan motor, tested cooling afterwards and system came back on without challenges. Condenser fan motor is rated for 1.1 amps and it was pulling 9amps. System is Back operating. Service warranty per Jerry.