2308 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Job Locations
for dunn, nc


Map of Dunn NC
David  S.

David S.


Job Checkin

— Performed CMA Inspection on 82 Rooftop Exhaust Fans. Checked operation, greased bearings as able, inspected condition of belts & fan blades. Inspection reports provided with pictures. Smaller Rooftop Exhaust Fans are not on Service Contract, per office. — Exhaust Fan A03: Motor belts missing. Recommend installing 2-A48 belts. Provided estimate. System should be tagged out pending belt replacement. Provided estimate to install (2) A48 belts. Remote grease fitting hose ruptured prior. Recommend replacement of hose. — Exhaust Fan A04: Observed excessive noise from bearing, even after lubricating. Recommend replacement of axle bearings. System should be tagged out to prevent early failure of motor. — Exhaust Fan A07: Remote grease fitting hose ruptured prior. Recommend replacement of hose. Minor noise still present. — Exhaust Fan A09: Observed excessive noise from bearing, even after lubricating. Recommend replacement of axle bearings. System should be tagged out to p