Percy M.

Percy M. Job Checkin

TECH DIAGNOSED SPLIT SYSTEM #5 WHICH IS A NEW SYSTEM, THE POWER HAD WENT OUT. AFTER DIAGNOSTICS TECH FOUND THERMOSTAT WIRE NOT CONNECTED PROPERLY, AND THERE WAS A FUSE BLOWN INSIDE OF AIR HANDLER. TECH TOOK WIRES OIT OF THERMOSTAT AND PUT THEM BACK IN PROPERLY, ALSO TECH CHANGED FUSE IN AIR HANDLER. SPLIT SYSTEM #5 IS BACK RUNNING PROPERLY.


Percy M.

Percy M. Job Checkin

PERFORMED CMA INSPECTION ON 3 GAS PACKAGE SYSTEMS, 6 EXHAUST FANS AND 2 MAKE UP AIR SYSTEMS. ALL SYSTEMS HAVE A PROPER DELTA T AND ARE PERFORMING PROPERLY AT THIS TIME. COMPLETED FILTER CHANGE OF 8-20x20x1 FILTERS,8-16x25x2 FILTERS, 20-20x20x2 FILTERS AND 4-20x25x2 FILTERS. PICTURES AND PERFORMANCE REPORT ARE ATTACHED TO THIS INVOICE.


Romario  T.

Romario T. Job Checkin

Found the recently replaced thermostat programmed incorrectly. Thermostat was set for heat pump instead of gas and hot-gas dehumidification mode disabled. Tech corrected the settings and assured both circuits operated prior to departure as well as the hot-gas dehumidification. Temperature dropped throughout visit. No charge per office due to recent CMA visit.


Percy M.

Percy M. Job Checkin

TECH PERFORMED CMA INSPECTION ON 3 GAS PACKAGE SYSTEMS, 6 EXHAUST FANS, AND 2 MAKE UP AIR SYSTEMS. UPON ARRIVAL MANAGER OF STORE STATED THAT THERMOSTAT FOR KITCHEN AREA WAS NOT WORKING PROPERLY, TECH DIAGNOSED THERMOSTAT AND FOUND BUTTONS TO CHANGE SETTINGS AND TEMPERATURE WAS NOT WORKING ON THERMOSTAT. TECH REPLACED THERMOSTAT WITH APPROVAL FROM MRS. HUBBARD, TECH COMPLETED FILTER CHANGE OF 8-20x20x1 FILTERS, 24-20x20x2 FILTERS AND 12-16x20x2 FILTERS. ALL SYSTEMS ARE PERFORMING PROPERLY AT THIS TIME. PERFORMANCE REPORT AND PICTURES ARE ATTACHED TO THIS INVOICE.


Demarcus  M.

Demarcus M. Job Checkin

UNIT #3- MEMORY CARE/ACTIVITY- 4 TON TRANE SPLIT HEAT PUMP


Demarcus  M.

Demarcus M. Job Checkin

UNIT #5-KITCHEN- 5 TON CARRIER AIR HANDLER ONLY


Demarcus  M.

Demarcus M. Job Checkin

UNIT #9- 4 TON CARRIER AIR HANDLER ONLY


Jesse J.

Jesse J. Job Checkin

Tech preformed CMA FULL SERVICE on 9 Split Systems, 1 Air Make-up Unit, and 2 Exhaust Fans. *Split System #9 is still down from previous diagnosis of failed compressor, compressor shorted to ground. This was diagnosed on 10/5/23. Tech recommends replacing System. *Split System #3 is still down from previous diagnosis on 8/17/23 of failed blower motor, motor is locked up. Compressor also failed megohm test. Due to age and these challenges, tech recommends replacing system over repair. *Exhaust Fan #1 ( dishwasher) is still down with locked up motor, diagnosed on 4/14/23. Tech recommends replacing Exhaust Fan. *Split System #7 is operating at this time but has multiple challenges. Compressor tested in caution area of megohm test. Run capacitor is at lowest tolerance in operating range. Compressor plug has gotten extremely hot at some point and become disfigured. Blower motor is operating at higher amps than FLA listed, indicating motor is beginning to fail electrically. And evaporator c


Joshua C.

Joshua C. Job Checkin

Completed a filter change on 3 TRANE gas package units, 2 Make up Air hoods, washed filters, kitchen filters.


Joshua C.

Joshua C. Job Checkin

Completed a filter change on 3 TRANE gas package units, washed filters on 2 Make up Air hoods, kitchen filters.


Joshua  C.

Joshua C. Job Checkin

Tech performed CMA full service on 3 gas package units, 1 make up air unit with condensing towers, 1 make up air without, and 6 exhaust fans. Upon inspection tech found the gas pressure feeding each package unit low. Tech adjusted the gas pressure and confirmed system is operational. All systems are running properly at this time. Tech has attached system performance reports and pictures to this invoice.


Joshua  C.

Joshua C. Job Checkin

Tech performed CMA full service on 3 Gas Package Units, 2 Air Make Up Units, and 6 Exhaust fans. Upon inspection tech found the gas pressure to all package units low. Tech was able to adjust units 1 and 3 to proper pressure but due to corrosion fusing the gas valve adjustment screw closed was unable to adjust unit 2. All systems are running properly at this time. Tech has attached system performance reports and pictures to this invoice.


David  S.

David S. Job Checkin

Tech found wire not connected to ignition board Reconnected and tightened connections Heat and AC working correctly Told managers smell is oil burn off and smell disappeared while on site Thermostat is functioning properly at this time


Jesse J.

Jesse J. Job Checkin

Tech preformed CMA FULL SERVICE on 1 Package HP. Unit is operating at this time, but compressor has failed megohm test, showing signs of internal failure beginning. Fan motor is also over listed FLA. Condenser Coil also shows signs of deterioration. No leaks present at this time. Due to multiple challenges and age of system tech does recommend replacing unit. Tech has attached system performance report to invoice along with pictures.


Jesse J.

Jesse J. Job Checkin

Tech preformed CMA INSPECTION on 9 Split Systems, 1 makeup air unit, and 2 exhaust fan. Tech also completed approved repairs recommended from month of Aprils service. Tech replaced fan motor and dual run capacitor on Split System #4. System is up and operating at this time. Tech replaced fan motor and run capacitor on Split System #9. After completing repairs tech found unit kept tripping breaker, after further diagnosis tech found compressor shorted to ground. System #9 is not operational. Recommend replacing system. Tech replaced belt on exhaust fan #2. Tech also found Split System #3 powered of at disconnect due to previous diagnostic in August. Estimate for repairs/ replacement has been sent. Tech found Air Handler #5 in poor physical condition. Unit cabinet is completely rusted and breaking in several places. Condenser #5 is less than 2 years old, tech recommends replacing Air Handler. All other systems are operating properly at this time. Tech has attached system performance repo