Performed furnace certification for sale of home drt
Customer stated condenser fan motor stopped spinning Checked capacitor -capacitor checked out within spec checked motor amp draw -found motor drawing higher than normal amperage motor did not spin freely it appears that condenser fan motor bearings are failing recommend either replacing fan motor or air conditioner
Found furnace to be off on pressure switch fault. Found drain trap in furnace to be restricted causing water to back up into furnace causing pressure switch fault. Cleared drain trap and ran furnace. Furnace was working well. Performed combustion analysis on furnace, furnace passed in all fields. Recommend getting furnace checked out next fall to make sure furnace is running safely before heating season. Recommend changing air filter monthly.