Commercial HVAC repair of a Carrier rooftop unit not cooling. Discovered a failed compressor. Commercial HVAC install of a new compressor, filter drier and contactor. Tested and confirmed proper operation.
Commercial refrigeration repair of Machine not producing ice. Discovered a failed ice thickness sensor. Commercial refrigeration install of a new ice thickness sensor.
Commercial refrigeration repair of a Randell 2 door salad top reach in cooler making noise. Found that the fan blade and shroud were broken. Commercial refrigeration install of a new fan blade and shroud.
Commercial HVAC repair of a York roof top unit making a loud noise. Found the blower wheel became detached from the wheel hub. Commercial HVAC install of a new blower assembly.
Commercial HVAC repair of a York roof top unit making a loud noise. Found blower wheel breaking off of the shaft. Commercial HVAC install of a new blower assembly.
Commercial HVAC repair for a Lennox roof top unit not blowing air. Found blower wheel came off the shaft. Commercial HVAC install for a new blower assembly.
Commercial Refrigeration for a Silver King Reach in cooler that is not keeping its temperature. Found one of the stake on connectors for main power to be disconnected and the cord was plugged into a outlet that was very far away. Recommended commercial hvac repair to plug the stake on connector back into the unit and move the plug to a closer outlet.
Commercial HVAC repair for a Bard Packaged RTU. Commercial HVAC installation for a new Honeywell Thermostat.
Commercial HVAC repair for a Rheem Packaged RTU that is not providing heat. Commercial HVAC installation for a new thermostat
Commercial HVAC Service call for a Carrier Air Handler
Refrigeration call. Found 3 beep Freeze Timer alarm. Inspected and Cleaned float switch & water inlet valve. Reset & observed sequence of operations. Discovered water pump motor not pumping, voltage at connections + over amping - propeller seized. Capacitor tested good. Inspected water deflector which had no missing fins. Water inlet valve had material past screen, not good. I.M. parts haven't been cleaned in a while. Unit is due for a thorough cleaning and sanitizing which can't be done today. This should be scheduled with office. Last time this was done was last year. Water filter is changed regularly. Went to Hoshizaki supply house and picked up pump motor & valve - replaced. Motor amped good. Brushed condenser coil. Cleaned air filter. Observed & timed unit make batch of ice. Unit is currently operational. Call is complete.