Upon arrival for service call on 1996 Lennox furnace, found system not getting 24 volts between R and C this is due to system having overheated due to blower motor not coming on. I found blower never got 120 from the board. Board is bad and will need replaced customer would like to go ahead with repair. I was able to get customer temporary heating by jumping the fan to l1.