Diagnosed R 22 system low on refrigerant. Added 5lbs of r22. System is now critically charged.
Installed new control board, fan motor, and matching capacitor.
Second floor system not cooling in Newbury. Checked indoor thermostat. Set to cool. Indoor fan started. Checked indoor unit and system was running well. Indoor blower clean. Filter recently replaced. Checked outdoor system no operation. Checked electrical, found bad capacitor. Replaced capacitor. Started system. Compressor and condenser fan amperage within normal range. Refrigerant pressures good. 81/236. 16 degrees super heat. Outdoor coil is dirty and needs good cleaning.