No cool, Found system with very low refrigerant levels Client aware system leaking refrigerant wants temporary fix **No warranty on refrigerant ** Recharge and balance refrigerant Low 73 psig Super-heat 8'F High 210 psig Sub Cool 12'F Ck/change filter Measure temperature difference :19'F Outdoor temp 87'F Client Aware system needs further attention for permanent fix/repair also made aware system can freeze and leak water causing property damage **leak found in coil by previous tech and also sys. has weak condenser fan motor Mr aware could fail again** Suggested upgrading equipment