No cool, found system overheated due to dirty condenser coil and low refrigerant levels also system has water in emergency drain pan In Attic **Mr didn't want water removed going to have home Warranty company repair aware could cause system failure and/or property damage** Wanted us just to get system cooling for Tenants Approved repairs by phone Started club waived service fee Perform 1 system AC tune up. -Filter:ok -Flush drain line: Flush with h20 and treated *water in pan* -Clean and tighten electrical connections and wires: -Check electrical components: -High voltage wiring Romex -Blower motor: 4.5 amps -Blower cap: 7.5uF @7.1 under load ok -Condenser fan motor: .6 amps -Compressor: 133 amps (16.2 before cleaning) -Dual capacitor: 45/3uF @39.6/2.8 Failed -Contactor: 236 Volts across -Breaker: disconnect box -Recarged refrigerant levels: Low: 73 psig High: 263 psig super heat: 5'F Sub cool: 28'F -Replace valve caps (Missing upon arrival) -Clean