3617 Clearview Parkway
Atlanta, GA 30340
770-454-1800

Job Locations
for avondale estates, ga


Map of Avondale Estates GA
Jason H.

Jason H.


Job Checkin

No cool, found system overheated due to dirty condenser coil and low refrigerant levels also system has water in emergency drain pan In Attic **Mr didn't want water removed going to have home Warranty company repair aware could cause system failure and/or property damage** Wanted us just to get system cooling for Tenants Approved repairs by phone Started club waived service fee Perform 1 system AC tune up. -Filter:ok -Flush drain line: Flush with h20 and treated *water in pan* -Clean and tighten electrical connections and wires: -Check electrical components: -High voltage wiring Romex -Blower motor: 4.5 amps -Blower cap: 7.5uF @7.1 under load ok -Condenser fan motor: .6 amps -Compressor: 133 amps (16.2 before cleaning) -Dual capacitor: 45/3uF @39.6/2.8 Failed -Contactor: 236 Volts across -Breaker: disconnect box -Recarged refrigerant levels: Low: 73 psig High: 263 psig super heat: 5'F Sub cool: 28'F -Replace valve caps (Missing upon arrival) -Clean