No cool, Upstairs system, Found condenser fan motor overheated due to shorted run capacitor system is 13 years old suggested upgrading Installed new capacitor 35/5 Motor struggling to start Tested Motor running @1.3 amps (1.0 amp max could fail) Found low refrigerant super heat at 42 low signs of leak Recharge and balance refrigerant levels Low 70 psig Superheat 10'F High 212 psig Sub Cool 5'F Cleint aware system leaking refrigerant wants temporary fix **No warranty on refrigerant ** Measure temperature difference 18'F Outdoor temp 86'F Client Aware system needs further attention for permanent fix/repair also made aware system can freeze and leak water causing property damage Suggested upgrading equipment