Several Circuits in the house turning on and off, no tripping breakers. Smelled electrical burn coming from Main Disconnect outside. - Bolts attaching Main Breaker to bus bar were both arcing. Bolt on A Phase was red and smoking. - Neither bolt was even hand tight. Replaced outside main disconnect with new 200amp main with 8 spaces. All is well again.