On call, No cool, Found motor and compressor overheated due to shorted dual capacitor also condenser very dirty needs maintenance. -Installed new capacitor -Filter: ship 4 pack 14"25"1" Merv 8 STH -Clean and tighten electrical connections and wires: -Condenser fan motor: .6 amps -Compressor: 6.4 amps -Dual capacitor: 35/5 uF -Contactor: 237 Volts across -Monitor refrigerant levels: Low: 148 Psig High: 271 Psig super heat: 18'F Sub cool: 9'F -Clean out condenser coil -Measure temperature difference:19'F -Outdoor ambient temperature: 83'F raining -Cycle system, operating at this time *Equipment normal wear and tear *Need to have maintained to manufacture requirements to keep warranty current* ** Need to return and finish maintenance prepaid **