Job Checkin

No cool, Started smiley club on 3 systems. Found compressor overheating due to failed dual run capacitor also has dirty condenser coil and also leaking refrigerant check evaporator coil as courtesy (no charge) -Installed new capacitor 35/5 2 year part Warranty 90 days labor -Clean and tighten electrical connections and wires: -Check electrical components -High voltage wiring Romex not up to current codes -Condenser fan motor: .49 amps -Compressor: 5.2 amps -Dual capacitor: 35/5 uF new -Contactor: 241Volts across -Breaker: disconnect outdoor amp Client aware system leaking refrigerant wants temporary fix **No warranty on refrigerant ** -Evaporator coil very rusty and freezing showed Mrs aware of condition Recharge and balance refrigerant TXV sys Before Low 20 Psig Super-heat 83'F High 138 Psig Sub Cool 0'F After Low 71 Psig Super-heat 35'F High 184 Psig Sub Cool 8'F Ck filter ok Mrs changed Installed new brass cap Measure temperature difference 19'F Indo