returned to install compressor double checked compressor windings- not open cycled a/c cond fan motor operating at half speed(ecm) compressor is not the issue compressor going into thermal overload due to fan motor operation replaced condenser fan motor under warranty cycled a/c multiple times with no issues system operating at 130/327 superheat 16 subcool 15 ambient 92 system operational at this time