Water leak Start club 2 system Found system freezing up due to low refrigerant levels and PVC Drain pipe in attic broken Recharge and balance refrigerant levels in both systems Mr aware system leaking refrigerant wants temporary fix **No warranty on refrigerant ** Repair drain line Flush and treated with time release Mr change filters ok Measure temperature difference Indoor temp 83' Outdoor temp 71' Upstairs Low 72 psi High 223 psi Temp diff 22' F Downstairs Low 68 psi High 207 psi Temp diff 21' F Got running can't have installed till 7/13/16 going out of town Cleint Aware system needs further attention to repair Suggested upgrading equipment 18 years old Told will get $500 repair credit if upgrades system within 14 days