Repaired Trane Intellipak SXHFC commercial chiller. Diagnosed faulty electronic expansion valve (EEV). Removed old Sporlan SEI-30 valve, installed new SEI-30 with updated software. Recalibrated valve using Trane Tracer software. Checked refrigerant charge, adjusted superheat. Chiller now maintaining proper leaving water temperature.