Thank you Smiths, your rep was courteous and professional. He worked around my crazy schedule.
He was great. He found the problem very quickly and very professionally fixed it just as quickly. Very happy with this service! Thank you
Very nice - very thorough and knowledgeable in his job - be glad to have him again
I was called to perform cooling maintenance on the HVAC system to ensure it operates efficiently during the hot months. I started by cleaning the condenser coils, checking the refrigerant levels, and inspecting the blower motor for any signs of wear. I also tested the thermostat for accuracy and replaced the air filter to improve airflow. After completing the maintenance, I ran the system through a full cooling cycle, and everything is now running smoothly, ready to keep the home cool and comfortable.
Diagnosed failed dual-run capacitor on 3-ton Ruud heat pump causing compressor hard-start issues and intermittent condenser fan operation. Capacitor tested at 32μF/5μF (rated 45μF/7.5μF). Also found contactor with severely pitted contacts causing voltage drop. Replaced both components and installed surge protector to prevent future electrical issues. Measured superheat at 13°F and subcooling at 10°F after repair—both within spec. Also performed amperage test on compressor (RLA 19.2A vs nameplate 19.8A) indicating healthy compressor despite capacitor failure. System now operating efficiently.
Cooling service maintenance and filter change on 4 units
HVAC service and filter change on three units