PROBLEM 37 PT INSPECTION TRANE DIAGNOSIS ALL MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME UNIT IS COOLING WITH A 20 PLUS DEGREE TEMPERATURE SPLIT ACROSS THE COIL 10 MFD RUN CAPACITOR IS WEAK THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTOR /RECOMMEND REPLACING THE CAP REPLACED 10 MFD RUN CAPACITOR UNDER WARRANTY TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COIL FLUSHED DRAIN