Job Checkin

PERFORMED PMP INPECTION ON 2 SPLIT GAS AC UNITS CHECKED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURERS RANGE VERFIED TEMP SPLITS ACROSS COILS CLEANED OUTDOOR COILS TIGHTENED ELECTRICAL CONNECTIONS TESTED INRUSH AMPS OF COMPRESSORS INSPECTED CONDITION OF UNITS UNITS RUNNING IN COOLING AT TIME OF INSPECTION. SOUTH UNIT COMPRESSOR PULLING HIGH IN RUSH AMPS AND MAKING MINOR NOISE ON START-UP. START ASSIST CAPACITOR WAS INSTALLED AT TIME OF INSPECTION AND BROUGHT IN RUSH AMPS DOWN TO 22 FROM 79. WEATHER MASTERS RECOMMENDS FOLLOW UP INSPECTION IN FALL FOR HEATING SIDE OF SYSTEM.