I like that Keith let's me know when parts are wearing out before they break down. It gives me the opportunity to be proactive and take care of the problem when it fits my budget but before I have a problem.
Bi-annual maintenance time and as always Keith was on time, courteous and efficient. Money well spent!
Doing quarterly filter changes on the units
PERFORM PMP INSPECTION. TESTED EACH SYSTEM IN COOLING. VERIFIED SEQUENCE OF OPPERATION. - TIGHTEN ELECTRICAL CONNECTIONS. - HOSED OFF THE OUTDOOR COILS. - TESTED FREON LEVELS. - TESTED RUN CAPACITORS. - FLUSHED THE CONDENSATE LINES. - VERFIED TEMPATURE SPLITS. - INSPECTED DUCT CONNECTIONS AT AIR HANDLERS. ALL 3 SYSTEMS ARE RUNNING NORMAL AT THIS TIME. THE NORTH LARGER A/C HAS A OUTDOOR FAN MOTOR SHOWING WEAR. RECOMMEND REPLACMENT TO PREVENT FAILURE IN THE SUMMER. RECOMMEND MARS ECM MOTOR.
PROBLEM: EVAPORATIVE COOLER NOT COOLING DIAGNOSIS: PERFORMED FULL COOLER SERVICE BY CLEANING PADS, REPLACING FLOAT VALVE, REPLACING WATER PUMP, REPLACING BELLT, OILING BEARINGS AND MOTOR, AND ADDING SCALE REDUCER UNIT COOLING AFTER SERVICE WAS PERFORMED BUT IS OLD AND HAS MANY CORRODED COMPONENTS THAT MAY BREAK IN THE FUTURE
PROBLEM: NO COOL IN CONFERENCE ROOM DIAGNOSIS: THERMOSTAT WAS CALLING FORCOOLING WHEN INSPECTED. AFTER MOVING TO THE ROOFTOP UNIIIT AND INSSSPECTING THE UNIT, IT WAS FOUND THAT THE INDOOR BLOWER MOTOR FAN BELT WAS BROKEN. REPAIR: WEATHER MASTERS REPLACED THE 4L-410 BELT. CYCLED POWER TO THE SYSTEM THAT RESET THE PRESSURE SWITCHES. VERIFIED SEQUENCE OF OPERATIONS FROM THERMOSTAT
REPLACE FILTERS 16)20X20X1 4) 16X25X2 1) 24X24X1
REMOVED AND REPLACED 32 16×16×2IN PLEATED FILTERS
PERFORMED PMP INSPECTION ON 3 HEAT PUMP SPLIT UNITS CHECKED AMP DRAWS ON MOTORS TESTED RUN CAPACITORS FOR PERFORMANCE CHECKED TEMPERATURE SPLIT TIGHTENED ELECTRICAL CONNECTIONS INSPECTED CONDITION OF COILS VERIFIED SEQUENCE OF OPERATION FOR DEFROST CYCLE UNITS ARE RUNNING NORMALLY IN HEATING AT TIME OF INSPECTION. UNIT 1 OFM SHOWING WEAR BUT PERFORMING WITHING MANUFACTURERS SPECIFICATIONS. ALL UNITS SHOWING NORMAL WEAR FROM AGE. WEATHER MASTERS RECOMMENDS FOLLOW UP INSPECTION IN SPRING FOR A/C SIDE OF SYSTEM.
PROBLEM PMP VISIT 2 UNITS DAY AND NIGHT UPSTAIRS NXH530GKA200 E163517490 DIAGNOSIS 40/5 DUAL RUN CAPACITOR HAS FAILED /MOTORS MAY HAVE TAKEN INTERNAL DAMAGE /WE WILL REPLACE CAP UNDER WARRANTY VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT IS HEATING WITH A 25 DEGREE TEMP SPLIT ACROSS THE EVAPORATOR COIL TESTED DEFROST CYCLE /NO ISSUES AT THIS TIME ALL MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME DOWNSTAIRS CCH636GKA200 E182008587 40/5 DUAL RUN CAPACITOR IS SHOWING WEAR BUT STILL WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME /MAY NEED TO REPLACE AT NEXT VISIT VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT IS HEATING WITH A 25 DEGREE TEMP SPLIT ACROSS THE EVAPORATOR COIL TESTED DEFROST CYCLE /NO ISSUES AT THIS TIME ALL MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME REPAIRS REPLACED 40/5 DUAL RUN CAPACITOR UNDER WARRANTY TIGHTENED ALL ELECTRICAL CONNECTIONS
INSTALL NEW MARS ECM UNIVERSAL CONDENSER FAN MOTOR. 2 YR WARRANTY TESTED SYSTEM IN HEATING TO VARIFY SYSTEM IS RUNNING PROPERLY. AT THIS TIME THE EQUIPMENT IS RUNNING WITH A 29 DEG TEMP SPLIT. THIS IS NORMAL FOR THE CONDTIONS THE UNIT IS CURRANTY RUNNING IN. NOTE: THIS WINTER HAS BEEN COLDER THEN THE PAST FEW YRS. THE SYSTEM IS A HEAT PUMP AND DOES NOT HEAT AS WELL WHEN THE OUTDOOR TEMP IS BELOW 40 DEG. THIS IS NORMAL FOR A HEAT PUMP ROOFTOP PACKAGE UNIT.
PERFORM INSPECTION ON 1 ROOFTOP PACKAGE HEAT PUMP SYSTEM. DIAGNOSIS: SYSTEM RUNNING FINE IN HEATING AND COOLING. VERIFIED SEQUENCE OF OPPERATION. TIGHTEN ELECTRICAL CONNECTIONS. TESTED FREON LEVELS. AMP DRAWS AND RUN CAPACITOR. UNIT IS SHOWING NORMAL WEAR DUE TO AGE. NOTE: INDOOR FILTER WAS RECENTLY CHANGED. NOTE: THE ELECTRICAL SEAL TIGHT WHIP HAS SEPERATED CAUSING EXPOSED ELECTRICAL WIRES. WEATHER MASTERS RECOMMENDS REPLACING THE ELECTRICAL WHIP. THE OUTDOOR CONDENSER COIL HAS HAIL DAMAGE AND MAY CAUSE ISSUES WITH THE SYSTEM. WEATHER MASTERS RECOMMENDS HAVING THE COIL REPLACED TO PPREVENT ISSUES WITH THE SYSTEM OVER HEATING IN THE SUMMER OR ICING UP IN THE WINTER. WEATHER MASTERS WILL QUOTE THESE REPAIRS.
WEATHER MASTERS PURPOSES TO REMOVE AND REPLACE CONDENSOR FAN MOTOR. PART UNDER WARRENTY LABOR ONLY Serial c102381496
PROVIDE ESTIMATE FOR NEW ROOFTOP PACKAGE HEAT PUMP. UNIT IS 35 YRS OLD. HIGHLY RECOMMEND REPLACING UNIT.
PERFORMED PMP INSPECTION ON ROOF TOP PACKAGE UNIT TESTED CAPACITOR FOR CORRECT PERFORMANCE VERIFIED TEMPERATURE RISE CHECKED SEQUENCE OF OPPERATIONS FOR DEFROST CYCLE CHECKED AMP DRAWS OF MOTORS TIGHTENED ELECTRICAL CONNECTIONS DIAGNOSIS UNIT IS HEATING AT THIS TIME, OUTDOOR FAN MOTOR IS SHOWING WEAR AND TESTING AT 1.24 AMPS WITH A RATING OF 1.2 MOTOR IS UNDER WARRENTY UNTIL DECEMBER 2020 ALL OTHER COMPONENTS ON UNIT RUNNING NORMALLY AT THIS TIME WHILE SHOWING NORMAL WEAR FOR AGE
PROBLEM: UNIT NOT HEATING DIAGNOSIS: THERMOSTAT INSTALLED INCORRECTLY REWIRED THERMOSTAT FOR CORRECT FUNCTION OF UNIT VERIFIED SYSTEM OPPERATING IN HEATING UNIT HEATING NORMALLY AT THIS TIME