PROBLEM 37 PT INSPECTION @2 TRANE MASTER MFD-2/2013 4TWB4061E1000BB 1306412D2F DIAGNOSIS CONDENSER FAN MOTOR IS LEAKING OIL /THIS MAY CAUSE THE MOTOR TO FAIL IN THE SUMMER WHEN THE TEMPERATURES INCREASE CHECKED DEFROST CYCLE /NO ISSUES AT THIS TIME VERIFIED SEQUENCE OF OPERATION IN HEATING MODE AND THE UNIT HEATING WITH A 30 PLUS DEGREE TEMPERATURE SPLIT ACROSS THE EVAPORATOR COIL MOTOR AMPS AND RUN CAPACITOR ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME NO RECOMMENDED REPAIRS AT THIS TIME KITCHEN UNIT TRANE MFD-2/2013 4TWB4049E1000BB 130918W62F DIAGNOSIS 5MFD RUN CAPACITOR IS WEAK /RECOMMEND REPLACING /THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTOR CHECKED DEFROST CYCLE /NO ISSUES AT THIS TIME VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT HEATING WITH A 30 PLUS DEGREE TEMPERATURE SPLIT ACROSS THE EVAPORATOR COIL NO OTHER RECOMMENDED REPAIRS AT THIS TIME TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COILS REPLACED 7.5MFD RUN CAPACITOR FOR