PERFORM FILTER CHANGE ON 7 SYSTEMS. PERFORM INSPECTIONS ON 7 UNITS. DIAGNOSIS: UNIT 20- REDLINE IS NOT USING THIS SYSTEM DUE TO NO THERMOSTAT CONNECTED. CONDENSER FAN MOTOR OVER AMPING , RECOMMEND REPLACMENT. MARS ECM UNIT 18- SYSTEM WAS NOT COOLING DUE TO BLOWN FUSES. SYSTEM IS TURNED OFF TO PREVENT COMPRESSOR FAILURE TILL SYSTEM CAN BE REPAIRED. CONDENSER FAN MOTOR OVER AMPING. SYSTEM HAD BLOWN 45 AMP FUSES. CONDENSATE DRAIN LINE CRACKED. NEEDS REPLACED. RECOMMEND REPLACING CONDENSER FAN MOTOR WITH MARS ECM. RECOMMEND NEW 60MFD COMPRESSOR CAPACITOR AND KS1 HARD START COMPRESSOR KIT. RECOMMEND NEW 15MFD CAPACITOR FOR INDOOR BLOWER MOTOR. UNIT 16- SYSTEM RUNNING FINE IN COOLING JUST RECOMMEND HAVING REPAIRS DONE CONDENSER FAN MOTOR OVER AMPING . RECOMMEND NEW CONDENSER FAN MOTOR. MARS ECM . RECOMMEND NEW 60MFD CAPACITOR FOR COMPRESSOR. RECOMMEND NEW 15MFD CAPACITOR FOR INDOOR BLOWER. UNIT 19- SPLIT SYSTEM - UNIT RUNNING AND COOLING FINE. RECOMMED 5MFD CAPACITOR FOR O