Water furnace premiere 2 Initial inspection of the full system discovered that the ecobee thermostat does not have any control or sensors or attached accessories regarding any humidity control in the home. The onboard ecobee sensor is sensing the local humidity and sending self-generated warnings to the homeowner through the thermostat display. Test run of the open loop geothermal shows the mechanicals of the package equipment and ecobee controls are running in normal condition however there is a water flow LED indicator light flashing indicating recent issues in the past. During test running of the equipment the well pump pressure dropped to the 20 psi range during operation of the geothermal with one bathroom sink on. Equipment did return to almost 70 PSI with everything off but again dropped to 30 PSI with the geothermal running. Well pump pressure should always remain between 40 and 60 PSI Running r22 refrigerant pressure was tested at 45 PSI suction in heating mode. After con