725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews

Rated 4.9 out of 5 stars based on 345 customer reviews

Excellent Service by Gregg and his colleague

Greg and his colleague did awesome job balancing and providing recommendations. He also uncovered an issue that was kind a hidden.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

We have used Weston air on several properties and the service is always professional and mechanically well done. The price is fair. What we like is that it’s very realizable,

  • Overall Experience
  • Quality
  • Price
  • Convenience

Outstanding Company!

We have been a customer of Westin Air for four years now and recently had our old HVAC system replaced by Westin Air. They are the most professional HVAC company we’ve ever had with outstanding service and technical excellent. When I had a question about a new sound from our new system when turning on the furnace, Wes the owner personally came to the house to check it out (the sound was normal to the new system). What service! If you have any HVAC needs, call Westin Air.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Chris was great

Showed up in a timely manner and explained everything very well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service!

Always there when I need them. And always ready to help out when I am in a pinch. Great guys to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Attention to detail

Chris has a great attention to detail and is always willing to help us with our Energy Star Program

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service, Quality personnel

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service Professional employees!

Very responsive and gets the job done!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Service man showed up on time. Found part to be replaced and explained the problem. Also, gave us an overall status of the unit.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great communication

Working with Chris is always easy. He is almost always available to talk and responsive to when I have something I need help with. Willing to answer any questions I have and always trying to make things right for me and the client.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Quick Response & Excellent Service!

Westin Air continues to exceed my expectations for responsiveness and quality of service! Everyone is extremely friendly, understand and accommodating to help make the situation right! I would highly recommend Westin Air to anyone who wants a reliable, friendly and HONEST HVAC company!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service and quick response!

Chris is quick to respond and is a man of his word. He is passionate about what he does and is quality driven.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Experience!

Chris was Amazing!!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

A professional in your own neighborhood

I, Seth Peters, am a 18-year veteran and Employee #1 of Westin Air. We specialize in WaterFurnace geothermal, daiken and mitsubishi many split and whole home equipment, new construction and replacement installs

  • Overall Experience
  • Quality
  • Price
  • Convenience

Takes Pride

Chris takes pride in his works and cares about things getting done properly!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations

Nate G.

Nate G. Job Checkin

Goodman single stage furnace locked out ignition attempts Reset power Gas valve not opening Verified 24V present at gas valve Put wires back and gas valve began operating normally Jostling the electronics on the gas valve causes interruption in operation Recommend replacing the gas valve to prevent further malfunction Furnace is currently operating Discussed maintenance plans, discounts and repairs Currently in contract with another company who would not respond to emergency service After canceling existing contract, will sign up for gold plan and replace gas valve. Ideally, on the return visit, perform heating maintenance and replace the gas valve at the same time.


Graham M.

Graham M. Job Checkin

Upon arrival inspected furnace and found unit locked out on NO RPM. inspected motor and had no operation with power. Quote replacement motor. Replaced motor and test ran system, unit heating as should no concerns post repairs. PO# CW11272 cedar


Brandon P.

Brandon P. Job Checkin

2002 Carrier durmace operating in good condition despite age. 16x25x1 air filter in good condition. Clean flame sensor and check ignitor. Visual inspection of burners. Test ran operation in heating mode. System operates within temperature rise specifications. Blower and inducer motors tested good. Humidifier is currently shut down due to broken drain hookup. Broken drain hookup will need replaced before humidifier can be operated to avoid leaking water onto the ground. Brian will the repair himself. Furnace is operating properly, efficiently and ready for Winter.

2002 Carrier durmace operating in good condition despite age. 16x25x1 air filter in good condition. Clean flame sensor and check ignitor. Visual inspection of burners. Test ran operation in heating mode. System operates within temperature rise specifications. Blower and inducer motors tested good. Humidifier is currently shut down due to broken drain hookup. Broken drain hookup will need replaced before humidifier can be operated to avoid leaking water onto the ground. Brian will the repair himself. Furnace is operating properly, efficiently and ready for Winter.

Nate G.

Nate G. Job Checkin

Performed heating maintenance on a Bryant 2 stage 96% efficient natural gas furnace Aprilaire 210 filter needs changed Flame sensor clean Blower clean Humidifier water panel new High fire gas pressure 3.2" Temperature rise 55⁰ Low fire gas pressure 1.3" Temperature rise 49⁰ Condensate line flowing properly


Brandon P.

Brandon P. Job Checkin

Testing operation of the unit showed that the water valve for first stage operation will not open and is causing the unit to trip on fp1 code. Wired in second stage valve to first stage to get a temporary fix to allow for unit operation. Test ran in first and second stage heating. Recommend replacement of the faulty valve for proper operation. Will prepare a quote for repairs.


Nate G.

Nate G. Job Checkin

2002 Trane single stage 80% furnace Furnace throwing open limit circuit fault Verified limit circuit is closed with Ohm meter Failed control board for open limit fault is very common on these Trane control boards Replaced control board with a white rogers universal Fault codes are now referenced to the booklet left with the furnace Please do not discard this booklet


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on two Goodman high efficiency furnaces. Both 20x25x1 air filters are new today. Clean flame sensors and check ignitors. Visual inspection of burners. Flush condensation trap and drain lines. Basement system humidifier is operational. Pad in good condition and damper opened. Test run systems in heating mode. Both are within specifications for temperature rise. Blower and inducer motors are operating properly. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. Systems are operating properly, efficiently and ready for Winter.


Nate G.

Nate G. Job Checkin

Looked at 3 Reznor unit heaters One has two small cracks in the heat exchanger, but it is operational Discussed carbon monoxide risks Other unit needs a new spark module and fan control thermostatic switch. Third unit had a bad thermocouple. Replaced thermocouple Unit is operating normally at this time.

Looked at 3 Reznor unit heaters
One has two small cracks in the heat exchanger, but it is operational 
Discussed carbon monoxide risks 
Other unit needs a new spark module and fan control thermostatic switch.
Third unit had a bad thermocouple.
Replaced thermocouple 
Unit is operating normally at this time. 

Looked at 3 Reznor unit heaters
One has two small cracks in the heat exchanger, but it is operational 
Discussed carbon monoxide risks 
Other unit needs a new spark module and fan control thermostatic switch.
Third unit had a bad thermocouple.
Replaced thermocouple 
Unit is operating normally at this time.

Graham M.

Graham M. Job Checkin

Upon arrival inspected furnace and found popped 24v fuse. Inspected thermostat wiring and had short W to B inspected thermostat wiring at base, and found improper wiring with blue wire on B and on C at furnace. Disconnect B and test run furnace. Unit is heating with no issues after reconfiguring the wiring on thermostat.


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 16x25x4 due soon Clean flame sensor Ohm test igniter: 58.3 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: ok - hum off - solenoid bad Inspect exhaust flu - pvc no concerns Set thermostat for heat Check amp draw on blower motor: 4.23 Check amp draw on inducer motor:0.89 Check delta T - 54° Furnace is in optimal running conditions


Nate G.

Nate G. Job Checkin

Performed heating maintenance on a single stage 92% efficient natural gas furnace Replaced aprilaire 210 filter Pulled and cleaned flame sensor Condensate trap clear Gas pressure would not adjust past 2.6"wc... spec for the furnace os 3.0-3.8 Inlet pressure was above minimum specification Replaced gas valve Now able to set gas pressure to 3.0"wc Temperature rise 50⁰ Combustion test results are well within nominal ranges for a healthy heat exchanger Furnace operating within factory specs at this time

Performed heating maintenance on a single stage 92% efficient natural gas furnace
Replaced aprilaire 210 filter
Pulled and cleaned flame sensor
Condensate trap clear
Gas pressure would not adjust past 2.6"wc... spec for the furnace os 3.0-3.8
Inlet pressure was above minimum specification 
Replaced gas valve
Now able to set gas pressure to 3.0"wc
Temperature rise 50⁰
Combustion test results are well within nominal ranges for a healthy heat exchanger 

Furnace operating within factory specs at this time

Graham M.

Graham M. Job Checkin

Upon arrival inspected furnace and found unit on code 3.4 pressure switch error. inducer motor was not operating. Extremely hot to the touch, replacement motor required due to seized bearings to start furnace up. Quote presented and part ordered customer approved.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on Trane furnace. 20x25x4 air filter in good condition. Clean flame sensor and check ignitor. Visual inspection of burners. Humidifier pad in good condition. Damper is open. Test run furnace in heating mode. Temperature rise is within specs. Blower and inducer motors tested good. 4" galvanized B-vent in good condition and no sign of leaks. 0PPM CO detected during testing. System is operating properly, efficiently and ready for Winter.


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 20 25x1 clean Clean flame sensor Ohm test igniter: 54.2 Blower capacitor MFD: 12.5 @ 12.62 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - 2”-3” pvc no concerns Set thermostat for heat Check amp draw on blower motor: 3.46 Check amp draw on inducer motor:0.97 Check delta T - 49° Furnace is in optimal running conditions


Nate G.

Nate G. Job Checkin

2010 Bryant single stage 93% efficient natural gas furnace. Tripped out on a 31 fault, pressure switch stuck open Found secondary heat exchanger full of water Removed condensate trap Washed trap out thoroughly in the sink 20x25x1 Filter is brand new Flame sensor appears to have been cleaned very recently (yesterday?) Set gas pressure to 3.2"wc with reference to the burner box Ran combustion test (readings are attached to this invoice) Furnace is operating within factory specifications at this time. Signed up for silver maintenance plan Approved drain line modifications for AC condensate drain: removed p-trap (point of clogging for AC condensate), replaced cut section of pipe and installed a vent Tee fitting.

2010 Bryant single stage 93% efficient natural gas furnace. 
Tripped out on a 31 fault, pressure switch stuck open
Found secondary heat exchanger full of water 
Removed condensate trap
Washed trap out thoroughly in the sink
20x25x1 Filter is brand new
Flame sensor appears to have been cleaned very recently (yesterday?)
Set gas pressure to 3.2"wc with reference to the burner box
Ran combustion test (readings are attached to this invoice)
Furnace is operating within factory specifications at this time.

Signed up for silver maintenance plan
Approved drain line modifications for AC condensate drain: removed p-trap (point of clogging for AC condensate), replaced cut section of pipe and installed a vent Tee fitting. 2010 Bryant single stage 93% efficient natural gas furnace. 
Tripped out on a 31 fault, pressure switch stuck open
Found secondary heat exchanger full of water 
Removed condensate trap
Washed trap out thoroughly in the sink
20x25x1 Filter is brand new
Flame sensor appears to have been cleaned very recently (yesterday?)
Set gas pressure to 3.2"wc with reference to the burner box
Ran combustion test (readings are attached to this invoice)
Furnace is operating within factory specifications at this time.

Signed up for silver maintenance plan
Approved drain line modifications for AC condensate drain: removed p-trap (point of clogging for AC condensate), replaced cut section of pipe and installed a vent Tee fitting.