725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews

Rated 4.9 out of 5 stars based on 345 customer reviews

Excellent Service by Gregg and his colleague

Greg and his colleague did awesome job balancing and providing recommendations. He also uncovered an issue that was kind a hidden.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

We have used Weston air on several properties and the service is always professional and mechanically well done. The price is fair. What we like is that it’s very realizable,

  • Overall Experience
  • Quality
  • Price
  • Convenience

Outstanding Company!

We have been a customer of Westin Air for four years now and recently had our old HVAC system replaced by Westin Air. They are the most professional HVAC company we’ve ever had with outstanding service and technical excellent. When I had a question about a new sound from our new system when turning on the furnace, Wes the owner personally came to the house to check it out (the sound was normal to the new system). What service! If you have any HVAC needs, call Westin Air.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Chris was great

Showed up in a timely manner and explained everything very well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service!

Always there when I need them. And always ready to help out when I am in a pinch. Great guys to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Attention to detail

Chris has a great attention to detail and is always willing to help us with our Energy Star Program

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service, Quality personnel

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service Professional employees!

Very responsive and gets the job done!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Service man showed up on time. Found part to be replaced and explained the problem. Also, gave us an overall status of the unit.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great communication

Working with Chris is always easy. He is almost always available to talk and responsive to when I have something I need help with. Willing to answer any questions I have and always trying to make things right for me and the client.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Quick Response & Excellent Service!

Westin Air continues to exceed my expectations for responsiveness and quality of service! Everyone is extremely friendly, understand and accommodating to help make the situation right! I would highly recommend Westin Air to anyone who wants a reliable, friendly and HONEST HVAC company!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service and quick response!

Chris is quick to respond and is a man of his word. He is passionate about what he does and is quality driven.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Experience!

Chris was Amazing!!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

A professional in your own neighborhood

I, Seth Peters, am a 18-year veteran and Employee #1 of Westin Air. We specialize in WaterFurnace geothermal, daiken and mitsubishi many split and whole home equipment, new construction and replacement installs

  • Overall Experience
  • Quality
  • Price
  • Convenience

Takes Pride

Chris takes pride in his works and cares about things getting done properly!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations

Nate G.

Nate G. Job Checkin

Fault codes erase themselves after 72 hours, no stored fault codes upon arrival Found inducer and condensate trap gaskets leaking water inside the furnace Removed inducer and condensate trap Flushed trap with water Replaced trap gasket Resealed inducer seals with RTV Blower is clean 20x25x1 Filter is in good shape Pulled flame sensor and cleaned Run tested furnace High fire gas pressure set to 3.2"wc, Temperature rise 46⁰ Low fire gas pressure set to 1.3"wc, temperature rise 41⁰ No water leaks present at this time Furnace is operating perfectly within factory specifications at this time

Fault codes erase themselves after 72 hours, no stored fault codes upon arrival
Found inducer and condensate trap gaskets leaking water inside the furnace
Removed inducer and condensate trap
Flushed trap with water
Replaced trap gasket
Resealed inducer seals with RTV
Blower is clean
20x25x1 Filter is in good shape 
Pulled flame sensor and cleaned 
Run tested furnace
High fire gas pressure set to 3.2"wc, Temperature rise 46⁰
Low fire gas pressure set to 1.3"wc, temperature rise 41⁰
No water leaks present at this time
Furnace is operating perfectly within factory specifications at this time Fault codes erase themselves after 72 hours, no stored fault codes upon arrival
Found inducer and condensate trap gaskets leaking water inside the furnace
Removed inducer and condensate trap
Flushed trap with water
Replaced trap gasket
Resealed inducer seals with RTV
Blower is clean
20x25x1 Filter is in good shape 
Pulled flame sensor and cleaned 
Run tested furnace
High fire gas pressure set to 3.2"wc, Temperature rise 46⁰
Low fire gas pressure set to 1.3"wc, temperature rise 41⁰
No water leaks present at this time
Furnace is operating perfectly within factory specifications at this time

Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on Tempstar high efficiency furnace running in great condition. 20x25x4 air filter in good condition. Visual inspection of burners. Flush condensation trap and drain lines. Run test unit in heating mode from thermostat. Temperature rise is within specs. Blower and inducer motors tested good. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. System is operating properly, efficiently and ready for Winter. Renew silver maintenence plan.


Nate G.

Nate G. Job Checkin

ABC board failed Need replacement under parts warranty


Brandon P.

Brandon P. Job Checkin

Replace arma-flex on refrigerant line and thumb-gum on flue vent and lineset penatrations to seal gaps.


Nate G.

Nate G. Job Checkin

System flashing code 5 on ignition control board (ignition lockout) Reset power and burners fired up reliably on the first attempt Removed flame sensor (did not need cleaned) and cleaned it anyway Burners are crossing over ignition properly Every attempt to ignite the burners was successful Checked for loose wiring during operation to spark igniter, gas valve, control board, and flame sensor Nothing interrupted operation Tried to duplicate the fault code 5 by disconnecting the pressure switch, this trips a fault code 6 Inspected heat exchanger and filters No issues found with either Cannot find true cause for ignition lockout It could be a control board issue. Upon arrival, removed W wire at the board and it did not clear the fault the way it is supposed to. Recycling power to the unit cleared the fault. If problem persists, control board replacement may be needed System operating properly at this time


Brandon P.

Brandon P. Job Checkin

Perform preventative maintenence inspection on 1999 Bryan standard efficiency furnace running in good condition despite age. 16x25x4 air filter is in new condition. Clean flame sensor and check ignitor. Visual inspection of burners. Check humidifier pad. Test run operation of furnace in heating operation. Initial startup shows an unusual noise from the inducer motor. Suspect that the jnternal bearings are starting to fail. Inducer motor should be replaced sooner than later to avoid a non operational emergency. Quote for inducer motor will be emailed over. While operational, all other aspects of the system tested withing specifications. Blower motor, temperature rise, and gas valve are all good. No issues other than the inducer motor where found or suspected and system is currently operational.

Perform preventative maintenence inspection on 1999 Bryan standard efficiency furnace running in good condition despite age. 16x25x4 air filter is in new condition. Clean flame sensor and check ignitor. Visual inspection of burners. Check humidifier pad. Test run operation of furnace in heating operation. Initial startup shows an unusual noise from the inducer motor. Suspect that the jnternal bearings are starting to fail. Inducer motor should be replaced sooner than later to avoid a non operational emergency. Quote for inducer motor will be emailed over. While operational, all other aspects of the system tested withing specifications. Blower motor, temperature rise, and gas valve are all good. No issues other than the inducer motor where found or suspected and system is currently operational.

Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2022 Carrier 80% efficient single stage natural gas furnace 16x25x1 filter is in good condition Blower is clean Burners in good shape Pulled flame sensor and cleaned Checked gas pressure and temperature rise Opened fresh air damper Motor Amp draws are in specification No gad leaks detected Flue pipe in good shape 0ppm carbon monoxide reading during furnace operation No concerns found on today's visit


Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2016 80% efficient single stage ICP natural gas furnace 16x25x4 filter is still good (there is a spare next to the furnace) Pulled and cleaned flame sensor Blower capacitor still measured 7.7mfd Blower wheel clean Burners in good shape Gas pressure 3.8"wc Temp rise 48⁰ Motor Amp draws are within specification 0ppm carbon monoxide detected Flue pipe in good shape No gas leaks detected No concerns found on today's visit


Brandon P.

Brandon P. Job Checkin

Replace blower motor and test run operation in multiple speeds to test for previous irregular speed changing. No issues noticed while test running.


Nate G.

Nate G. Job Checkin

Replace HEPA filters and UV bulbs on all systems Left a full set of additional HEPA maintenence kits Install intake condensate drain coupling on the in-law suite furnace

Replace HEPA filters and UV bulbs on all systems
Left a full set of additional HEPA maintenence kits

Install intake condensate drain coupling on the in-law suite furnace Replace HEPA filters and UV bulbs on all systems
Left a full set of additional HEPA maintenence kits

Install intake condensate drain coupling on the in-law suite furnace

Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on two Climate Master Trilogy variable capacity communicating systems running in great condition. Air filters for both units are in clean condition. Performed visual inspection on all components including vut not limited to lower compressor/electrical compartment, upper blower/auxiliary heat strip compartment, and immediate connections for ground loop and hot water generation circuit. No issues are found or suspected from visual inspection. Performed a test operation of electric auxiliary heat strips to verify proper operation. All electric heat strips are operating properly and within specs for Amp draw. Performed operwtion test of systems in geothermal heating with no issues found or suspected. Performed heat of extraction on both systems. Both syste,s are operating properly and within specifications for heat of extraction based on air temperature rise, and ground loop temperature and pressure drop. Compressors tested within range with no issues su

Preventative maintenence inspection on two Climate Master Trilogy variable capacity communicating systems running in great condition. Air filters for both units are in clean condition. Performed visual inspection on all components including vut not limited to lower compressor/electrical compartment, upper blower/auxiliary heat strip compartment, and immediate connections for ground loop and hot water generation circuit. No issues are found or suspected from visual inspection. Performed a test operation of electric auxiliary heat strips to verify proper operation. All electric heat strips are operating properly and within specs for Amp draw. Performed operwtion test of systems in geothermal heating with no issues found or suspected. Performed heat of extraction on both systems. Both syste,s are operating properly and within specifications for heat of extraction based on air temperature rise, and ground loop temperature and pressure drop. Compressors tested within range with no issues su Preventative maintenence inspection on two Climate Master Trilogy variable capacity communicating systems running in great condition. Air filters for both units are in clean condition. Performed visual inspection on all components including vut not limited to lower compressor/electrical compartment, upper blower/auxiliary heat strip compartment, and immediate connections for ground loop and hot water generation circuit. No issues are found or suspected from visual inspection. Performed a test operation of electric auxiliary heat strips to verify proper operation. All electric heat strips are operating properly and within specs for Amp draw. Performed operwtion test of systems in geothermal heating with no issues found or suspected. Performed heat of extraction on both systems. Both syste,s are operating properly and within specifications for heat of extraction based on air temperature rise, and ground loop temperature and pressure drop. Compressors tested within range with no issues su

Nate G.

Nate G. Job Checkin

Performed 2 system geo thermal heating maintenance Checked ground loop water levels Checked air filters Replaced first floor humidifier water panel Found that humidifier water solenoid is stuck open, need to replace solenoid Checked blowers Checked drain lines Checked fault codes Run tested systems Checked Arzel zone function and explained operation Set dehumidifier to 55% No water leaks found on either system Ground loop connections are good Other than the humidifier solenoid, no concerns found on today's visit


Jason D.

Jason D. Job Checkin

Replace existing b-vent termination through roof Install new 5" B-Vent pipe from joint in attic and route through roof with new cap, collar and flashing.


Replace existing b-vent termination through roof
Install new 5" B-Vent pipe from joint in attic and route through roof with new cap, collar and flashing. 
Replace existing b-vent termination through roof
Install new 5" B-Vent pipe from joint in attic and route through roof with new cap, collar and flashing.

Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on Trane standard efficiency gas furnace running in great condition. 20x25x4 air filter in decent condition. Check again in 1-2 months. Humidifier pad is new today. Clean flame sensor and check ignitor. Visual inspection of burners. Run test unit in heating mode. Temperature rise is within specs. Blower and inducer motors tested good. Galvanized B-vent is in good condition and no sign of leaks. 0PPM CO detected during testing. Test ran humidifier operation. All systems are operating properly, efficiently and ready for Winter.


Brandon P.

Brandon P. Job Checkin

Upon arrival, system is locked out on low pressure code. Unit fault history has a number of low pressure and fp1 sensor error codes indicating low refrigerant charge. Tested refrigerant pressure and found 0.7psi in the system. The system has had a major blowout. Perform leak search in attempt to find refrigerant leak on Waterfurnace 5 Series package system. Could not pinpoint leak but was able to isolate the leak to somewhere in the outer wall of the domestic hot water generator coil. Visible oil on and around the area hinted to the location. Infrared sniffer was picking it traces of refrigerant from the area but could not pinpoint with leak detector gel. Hot water generator coil, aka desuperheater coil, will need replaced. Called Waterfurnace for warranty status and availability. Part is covered under warranty, but labor and refrigerant are not. Prepared quote for replacement. System can currently be ran in emergency heating mode for heat.

Upon arrival, system is locked out on low pressure code. Unit fault history has a number of low pressure and fp1 sensor error codes indicating low refrigerant charge. Tested refrigerant pressure and found 0.7psi in the system. The system has had a major blowout. Perform leak search in attempt to find refrigerant leak on Waterfurnace 5 Series package system. Could not pinpoint leak but was able to isolate the leak to somewhere in the outer wall of the domestic hot water generator coil. Visible oil on and around the area hinted to the location. Infrared sniffer was picking it traces of refrigerant from the area but could not pinpoint with leak detector gel. Hot water generator coil, aka desuperheater coil, will need replaced. Called Waterfurnace for warranty status and availability. Part is covered under warranty, but labor and refrigerant are not. Prepared quote for replacement. System can currently be ran in emergency heating mode for heat. Upon arrival, system is locked out on low pressure code. Unit fault history has a number of low pressure and fp1 sensor error codes indicating low refrigerant charge. Tested refrigerant pressure and found 0.7psi in the system. The system has had a major blowout. Perform leak search in attempt to find refrigerant leak on Waterfurnace 5 Series package system. Could not pinpoint leak but was able to isolate the leak to somewhere in the outer wall of the domestic hot water generator coil. Visible oil on and around the area hinted to the location. Infrared sniffer was picking it traces of refrigerant from the area but could not pinpoint with leak detector gel. Hot water generator coil, aka desuperheater coil, will need replaced. Called Waterfurnace for warranty status and availability. Part is covered under warranty, but labor and refrigerant are not. Prepared quote for replacement. System can currently be ran in emergency heating mode for heat.