725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews

Rated 4.9 out of 5 stars based on 345 customer reviews

Excellent Service by Gregg and his colleague

Greg and his colleague did awesome job balancing and providing recommendations. He also uncovered an issue that was kind a hidden.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

We have used Weston air on several properties and the service is always professional and mechanically well done. The price is fair. What we like is that it’s very realizable,

  • Overall Experience
  • Quality
  • Price
  • Convenience

Outstanding Company!

We have been a customer of Westin Air for four years now and recently had our old HVAC system replaced by Westin Air. They are the most professional HVAC company we’ve ever had with outstanding service and technical excellent. When I had a question about a new sound from our new system when turning on the furnace, Wes the owner personally came to the house to check it out (the sound was normal to the new system). What service! If you have any HVAC needs, call Westin Air.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Chris was great

Showed up in a timely manner and explained everything very well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service!

Always there when I need them. And always ready to help out when I am in a pinch. Great guys to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Attention to detail

Chris has a great attention to detail and is always willing to help us with our Energy Star Program

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service, Quality personnel

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service Professional employees!

Very responsive and gets the job done!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Service man showed up on time. Found part to be replaced and explained the problem. Also, gave us an overall status of the unit.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great communication

Working with Chris is always easy. He is almost always available to talk and responsive to when I have something I need help with. Willing to answer any questions I have and always trying to make things right for me and the client.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Quick Response & Excellent Service!

Westin Air continues to exceed my expectations for responsiveness and quality of service! Everyone is extremely friendly, understand and accommodating to help make the situation right! I would highly recommend Westin Air to anyone who wants a reliable, friendly and HONEST HVAC company!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service and quick response!

Chris is quick to respond and is a man of his word. He is passionate about what he does and is quality driven.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Experience!

Chris was Amazing!!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

A professional in your own neighborhood

I, Seth Peters, am a 18-year veteran and Employee #1 of Westin Air. We specialize in WaterFurnace geothermal, daiken and mitsubishi many split and whole home equipment, new construction and replacement installs

  • Overall Experience
  • Quality
  • Price
  • Convenience

Takes Pride

Chris takes pride in his works and cares about things getting done properly!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations

Brandon P.

Brandon P. Job Checkin

Upon arrival, unit in question was set in heating mode with no operation. Other hear was operating in cooling mode to try and cool excessively hot other room. Set other unit to off and turned head unit in cold room on. System came on and fan started to blow. Supply air was slightly warmer than return air by approximately 2F. Inspection of outdoor unit showed that vapor line was getting to 130-140F which is normal. Refrigerant coming into head is not 130-140F and is approximately 70F. Suspect that there is an insulation issue in the attic above garage but the garage attic cannot be reached currently due to needing a 10ft ladder, and there being stuff in the area the ladder will need setup. Currently have the head in question in heating mode with the other head off. Multiple issues including the other head being in cooling, very low outdoor temperature causing reduced capacity and more frequent defrost cycles, and being a bonus room above the garage can all affect the heating operation.


Graham M.

Graham M. Job Checkin

Upon arrival inspected unit and found no leaks outside. Tore down indoor head and found a leak on evap coil. Photo added of leak. Coil needs replaced under manufacturer warranty but labor and refrigerant is not covered.

Upon arrival inspected unit and found no leaks outside. Tore down indoor head and found a leak on evap coil. Photo added of leak. Coil needs replaced under manufacturer warranty but labor and refrigerant is not covered.

Graham M.

Graham M. Job Checkin

Furnace maintenance inspection performed downstairs system Inspect filter:20x25x1 clean no concerns Inspect burners: Clean no concerns Ohm ignitor:53.4 Clean flame sensor Inducer amps: 0.36 Blower Motor amps: 4.12 All wiring OK Humidifier: n/a Temperature rise:62° Furnace is running in optimum condition. Furnace maintenance inspection performed upstairs system Inspect filter:20x25x1 clean Inspect burners: Clean no concerns Ohm ignitor: 49.3 Clean flame sensor Inducer amps: 0.39 Blower Motor amps: 1.92 All wiring OK Humidifier: n/a Temperature rise:54° Furnace is running in optimum condition.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on 2020 Trane standard efficiency furnace running in great condition. 20x25x1 air filter in new condition. Clean flame sensor and check ignitor. Visual inspection of burners. Test ran in heating mode from thermostat. Temperature rise is within specs. Blower and inducer motors tested good. Galvanized B-vent in good condition and no sign of leaks. 0PPM CO detected during testing. System is operating properly, efficiently, and ready for Winter.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on standard efficiency gas furnace running in great condition. 20x25x1 air filter in new condition. Clean flame sensor and check ignitor. Visual inspection of burners. Test ran in heating mode from thermostat. Temperature rise is within specs. Blower and inducer motors tested good. Galvanized B-vent in good condition and no sign of leaks. 0PPM CO detected during testing. System is operating properly, efficiently and ready for Winter.


Jason D.

Jason D. Job Checkin

SOLD: 02/05/2026 8:54:59 PM - Option 1 Install New Bryant Single (2) Stage Gas Furnace Model #: 927TA48060V17 Serial #: 60,000 BTU’s - 97% AFUE Installation: * Additional Filtration - New PVC furnace vents. Level 2 * Reconnect to existing gas line and high voltage electric * Transition to existing supply and return ductwork * Start up and commission new system * 1" Standard Filter Rack Warranty: 20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed) 10 Year Bryant manufacturers Parts Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed)


SOLD: 02/05/2026 8:54:59 PM - Option 1

Install New Bryant Single (2) Stage Gas Furnace
Model #: 927TA48060V17
Serial #:
60,000 BTU’s - 97% AFUE
 
Installation:
* Additional Filtration - New PVC furnace vents. Level 2
* Reconnect to existing gas line and high voltage electric
* Transition to existing supply and return ductwork
* Start up and commission new system
* 1" Standard Filter Rack
 
Warranty:
20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed)
10 Year Bryant manufacturers Parts Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)

SOLD: 02/05/2026 8:54:59 PM - Option 1

Install New Bryant Single (2) Stage Gas Furnace
Model #: 927TA48060V17
Serial #:
60,000 BTU’s - 97% AFUE
 
Installation:
* Additional Filtration - New PVC furnace vents. Level 2
* Reconnect to existing gas line and high voltage electric
* Transition to existing supply and return ductwork
* Start up and commission new system
* 1" Standard Filter Rack
 
Warranty:
20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed)
10 Year Bryant manufacturers Parts Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)

Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on 2016 Waterfurnace 5 Series running in great condition. Fred's concern for high electricity bill/usage does not appear to come from the geothermal unit. Took some information on thermostat settings to review with office staff and Waterfurnace. Air filters are in clean condition. Air coil is clean. Test ran operation of first stage geo heat, second stage geo heat, aswell as auxiliary heating. Tested refrigerant pressures with aid tool. Nothing of concern was found or suspected. Blower motor and ground loop flow center pumps operating properly. No issues of high energy usage were found during inspection and no issues with the system were found or suspected. System is operating properly, efficiently and ready for Winter.


Graham M.

Graham M. Job Checkin

Replace high limit and verify operation. Unit was cycling on limit flashing in and out while messing with wiring. Unit stopped showing problems but homeowner wanted to be proactive so limit was replaced.


Brandon P.

Brandon P. Job Checkin

Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary.

Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary. Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary.

Nate G.

Nate G. Job Checkin

Adjusted water flow to humidifier with water valve.


Nate G.

Nate G. Job Checkin

Install recall Water screen and orifice were clogged Removed both and set water flow at the saddle valve If problem persists, it will need an in-line water filter added and new piece of 1/4" copper with nuts and ferrules


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 16x25x1 new today owner supply Clean flame sensor Inspect burners - clean Ohm test igniter: 53.5 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 5.80 Check amp draw on inducer motor:0.63 Check delta T - 57° Furnace is in optimal running conditions Gas heating preventative maintenance performed Check filter - 24x25x1 new today owner supply Clean flame sensor Inspect burners - clean Ohm test igniter: 59.8 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 3.2 Check amp draw on inducer motor:0.2 Check delta T - 64° Furnace is in optimal running conditions


Brandon P.

Brandon P. Job Checkin

Flow center pump has failed internally in the electrical systems. Called Waterfurnace tech support to verify control board was operating properly first. Repairs habe been approved and parts will be ordered. Office staff will call back to schedule repair when parts are in hand.

Flow center pump has failed internally in the electrical systems. Called Waterfurnace tech support to verify control board was operating properly first. Repairs habe been approved and parts will be ordered. Office staff will call back to schedule repair when parts are in hand. Flow center pump has failed internally in the electrical systems. Called Waterfurnace tech support to verify control board was operating properly first. Repairs habe been approved and parts will be ordered. Office staff will call back to schedule repair when parts are in hand.

Nate G.

Nate G. Job Checkin

Replaced blower capacitor on 1993 Trane 80% propane furnace Has a 5 series geo split and a 5 series package unit Pressurized closed loop


Brandon P.

Brandon P. Job Checkin

Outdoor fan motor bearings are in initial stages of failure. Recommend replacement of fan motor before total failure. Motor has been ordered and Westin will call back to schedule once part is in hand.

Outdoor fan motor bearings are in initial stages of failure. Recommend replacement of fan motor before total failure. Motor has been ordered and Westin will call back to schedule once part is in hand.