Greg and his colleague did awesome job balancing and providing recommendations. He also uncovered an issue that was kind a hidden.
Overall Experience
Quality
Price
Convenience
We have used Weston air on several properties and the service is always professional and mechanically well done. The price is fair. What we like is that it’s very realizable,
Overall Experience
Quality
Price
Convenience
We have been a customer of Westin Air for four years now and recently had our old HVAC system replaced by Westin Air. They are the most professional HVAC company we’ve ever had with outstanding service and technical excellent. When I had a question about a new sound from our new system when turning on the furnace, Wes the owner personally came to the house to check it out (the sound was normal to the new system). What service! If you have any HVAC needs, call Westin Air.
Overall Experience
Quality
Price
Convenience
Showed up in a timely manner and explained everything very well
Overall Experience
Quality
Price
Convenience
Always there when I need them. And always ready to help out when I am in a pinch. Great guys to work with.
Overall Experience
Quality
Price
Convenience
Chris has a great attention to detail and is always willing to help us with our Energy Star Program
Overall Experience
Quality
Price
Convenience
Overall Experience
Quality
Price
Convenience
Very responsive and gets the job done!
Overall Experience
Quality
Price
Convenience
Service man showed up on time. Found part to be replaced and explained the problem. Also, gave us an overall status of the unit.
Overall Experience
Quality
Price
Convenience
Working with Chris is always easy. He is almost always available to talk and responsive to when I have something I need help with. Willing to answer any questions I have and always trying to make things right for me and the client.
Overall Experience
Quality
Price
Convenience
Westin Air continues to exceed my expectations for responsiveness and quality of service! Everyone is extremely friendly, understand and accommodating to help make the situation right! I would highly recommend Westin Air to anyone who wants a reliable, friendly and HONEST HVAC company!!
Overall Experience
Quality
Price
Convenience
Chris is quick to respond and is a man of his word. He is passionate about what he does and is quality driven.
Overall Experience
Quality
Price
Convenience
Overall Experience
Quality
Price
Convenience
I, Seth Peters, am a 18-year veteran and Employee #1 of Westin Air. We specialize in WaterFurnace geothermal, daiken and mitsubishi many split and whole home equipment, new construction and replacement installs
Overall Experience
Quality
Price
Convenience
Chris takes pride in his works and cares about things getting done properly!
Overall Experience
Quality
Price
Convenience
Performed heating maintenance 24x25x4 filter is in good shape Aprilaire humidifier #35 water panel in good shape Opened bypass damper for humidifier and set humidity to 5 No water leaks present at this time Pulled and cleaned flame sensor Condensate trap clear Blower clean Burners in good shape Detected a heavy gas leak from the furnace control valve We will return with a new gas valve ASAP Otherwise, furnace is operating normally at this time.
Gas heating preventative maintenance performed Check filter - 20x25x4 ok due by next season Clean flame sensor Inspect burners - clean no concerns Ohm test igniter: 55.5 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: clean air open Inspect exhaust flu - 4” round pipe - disconnected at water heater junction. Taped gaps up and quoting repair Set thermostat for heat Check amp draw on blower motor: 6.98 Check amp draw on inducer motor:0.35 Check delta T - 42° Furnace is in optimal running conditions 4inch furnace pipe to 5” to 3” 5” 7” Y fitting for main flu pipe.
Diagnosed failed heat sequencer Replaced with a contactor and relay This is heavier duty and more reliable than the sequencer that failed Sequencer was previously replaced in 2018
Upon arrival inspected system and found unit in EHC HHC fault condition. Inspected heat strips and found no major concerns. Test ran system and verified proper operation for both heat pump and electric heat. Electric Heating preventative maintenance performed Turn heat on at thermostat Check filter: Trane clean effects - clean Check volt and amp draw on heating elements: 240 60a strip pack Blower motor cap: n/a ECM Temp rise at — 26° heat pump alone - 56° HP & emergency heat Force defrost on outdoor unit reversing valve is operational Furnace and heat pump in optimal running conditions
Replaced blower motor under factory parts warranty
Geothermal preventative maintenance inspection Air filter - 30x32x2 clean Run test from aurora - no saved faults Loop temperatures - 40 out 47 in Delta T 29° geothermal 27° electric Unit is in good health and ready for the season
Gas heating preventative maintenance performed Check filter - 20x25x4 new today Clean flame sensor Inspect burners - clean Ohm test igniter: 52.4 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: clean - water supply gone bad no longer supplying water Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 2.88 Check amp draw on inducer motor:0.26 Check delta T - 54° Furnace is in optimal running conditions
Performed two system heating maintenance Both furnaces are Trane S9V2 two stage variable speed blower models West side (pool room) 16x25x1 filter is good, left the included one at the furnace Blew out Condensate trap Stainless burner upgrade still in good shape Pulled and cleaned flame sensor Humidifier (aprilaire 440) in good working order, #12 water panel in OK condition, no water leaks present. Set duct-mounted humidistat to 40%, opened bypass damper Run tested furnace High fire gas pressure set to 3.5"wc, temp rise 40⁰ Low fire gas pressure set to 1.9"wc, temp rise 35⁰ No concerns found East side Aprilaire 440 humidifier has been disabled at some point in thr past, customer does not want to pursue restoring operation at this time Left bypass damper closed 16x25x1 filter is good, left new one at the furnace Blew out Condensate trap Pulled and cleaned flame sensor Stainless burners in good shape Run tested furnace High fire gas pressure set to 3.5"wc, temp rise 37⁰ Low fire gas
Gas heating preventative maintenance performed Check filter - 20x25x1 new today Clean flame sensor Inspect burners - clean no concerns Ohm test igniter: 62.1 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - 2” pvc no concerns Set thermostat for heat Check amp draw on blower motor: 4.2 Check amp draw on inducer motor:0.89 Check delta T - 53° Furnace is in optimal running conditions
11/14/2025 1:41:35 PM - Option 1 Install New Daikin HVAC System Single Stage - 9 Speed ECM Furnace: Model #: DR96SN1005CN Serial #: 2504264985 100,000 BTU's - 96% AFUE Single Stage Air Conditioner: Model #: DC5SEA4210 Serial #: 2409148448 3.5 Ton - 15.2 SEER2 *Matching Indoor Coil: Model #: CAPTA4230C3 Serial #: 2411314710 Installation: * Reconnect to existing electric * Transition to existing supply and return ductwork * Start up and commission new system * Aprilaire 1210 (20x25) Media Air Cleaner * Honeywell T6 Pro Thermostat Warranty: 5 Year Daikin manufacturers Parts Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed) 5 Year Daikin manufacturers Compressor Warranty 20 Year Daikin manufacturers Heat Exchanger Warranty (Annual maintenance must be performed)
Performed heating maintenance on a 2020 downflow Tempstar 80% efficient two stage natural gas furnace 20x20x1 filter is good, left the included filter next to the furnace Pulled flame sensor and cleaned Burners in good shape Blower is clean Run tested furnace High fire gas pressure set to 3.2"wc, temperature rise 52⁰ Low fire gas pressure set to 1.7"wc Temperature rise 45⁰ Flue pipe in good shape No gas leaks detected Furnace operating within factory specs at this time No concerns found
Gas heating preventative maintenance performed Check filter - 213 popup clean good for season Clean flame sensor Inspect burners - clean no concerns Ohm test igniter: 53.6 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - 2” PVC Set thermostat for heat Check amp draw on blower motor: 3.9 Check amp draw on inducer motor:0.45 5mfd @4.71 Check delta T - 53° rise Furnace is in optimal running conditions
Performed heating maintenance on a 2011 Carrier Infinty 3 stage 97% efficient natural gas furnace Replaced humidifier water panel (aprilaire #10) 16x25x4 filter is still good Pulled flame sensor and cleaned Pulled condensate trap and flushed with water Blower wheel is clean Burners are in good shape Run tested furnace while performing combustion test and checking temperature rise High fire set to 3.7" Med fire set to 1.75" Low fire set to 0.65" No concerns found
Upon arrival inspect system and found bad igniter. Virify igniter stocked on truck, and quote igniter replacement. After installing igniter clean flame sensor and test run system verifying proper operation. No concerns post repairs
Gas heating preventative maintenance performed Check filter - 20x25x1 clean Clean flame sensor Inspect burners - no concerns Ohm test igniter: 47.3 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: due asap Inspect exhaust flu - no major concerns Set thermostat for heat Check amp draw on blower motor: 8.00 Check amp draw on inducer motor:0.24 Check delta T - 45° Furnace is in optimal running conditions