Excellent Service by Gregg and his colleague

Greg and his colleague did awesome job balancing and providing recommendations. He also uncovered an issue that was kind a hidden.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

We have used Weston air on several properties and the service is always professional and mechanically well done. The price is fair. What we like is that it’s very realizable,

  • Overall Experience
  • Quality
  • Price
  • Convenience

Outstanding Company!

We have been a customer of Westin Air for four years now and recently had our old HVAC system replaced by Westin Air. They are the most professional HVAC company we’ve ever had with outstanding service and technical excellent. When I had a question about a new sound from our new system when turning on the furnace, Wes the owner personally came to the house to check it out (the sound was normal to the new system). What service! If you have any HVAC needs, call Westin Air.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Chris was great

Showed up in a timely manner and explained everything very well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service!

Always there when I need them. And always ready to help out when I am in a pinch. Great guys to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Attention to detail

Chris has a great attention to detail and is always willing to help us with our Energy Star Program

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service, Quality personnel

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service Professional employees!

Very responsive and gets the job done!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Service man showed up on time. Found part to be replaced and explained the problem. Also, gave us an overall status of the unit.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great communication

Working with Chris is always easy. He is almost always available to talk and responsive to when I have something I need help with. Willing to answer any questions I have and always trying to make things right for me and the client.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Quick Response & Excellent Service!

Westin Air continues to exceed my expectations for responsiveness and quality of service! Everyone is extremely friendly, understand and accommodating to help make the situation right! I would highly recommend Westin Air to anyone who wants a reliable, friendly and HONEST HVAC company!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service and quick response!

Chris is quick to respond and is a man of his word. He is passionate about what he does and is quality driven.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Experience!

Chris was Amazing!!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

A professional in your own neighborhood

I, Seth Peters, am a 18-year veteran and Employee #1 of Westin Air. We specialize in WaterFurnace geothermal, daiken and mitsubishi many split and whole home equipment, new construction and replacement installs

  • Overall Experience
  • Quality
  • Price
  • Convenience

Takes Pride

Chris takes pride in his works and cares about things getting done properly!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations

Graham M.

Graham M. Job Checkin

Replace high limit and verify operation. Unit was cycling on limit flashing in and out while messing with wiring. Unit stopped showing problems but homeowner wanted to be proactive so limit was replaced.


Brandon P.

Brandon P. Job Checkin

Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary.

Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary. Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary.

Nate G.

Nate G. Job Checkin

Adjusted water flow to humidifier with water valve.


Nate G.

Nate G. Job Checkin

Install recall Water screen and orifice were clogged Removed both and set water flow at the saddle valve If problem persists, it will need an in-line water filter added and new piece of 1/4" copper with nuts and ferrules


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 16x25x1 new today owner supply Clean flame sensor Inspect burners - clean Ohm test igniter: 53.5 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 5.80 Check amp draw on inducer motor:0.63 Check delta T - 57° Furnace is in optimal running conditions Gas heating preventative maintenance performed Check filter - 24x25x1 new today owner supply Clean flame sensor Inspect burners - clean Ohm test igniter: 59.8 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 3.2 Check amp draw on inducer motor:0.2 Check delta T - 64° Furnace is in optimal running conditions


Brandon P.

Brandon P. Job Checkin

Flow center pump has failed internally in the electrical systems. Called Waterfurnace tech support to verify control board was operating properly first. Repairs habe been approved and parts will be ordered. Office staff will call back to schedule repair when parts are in hand.

Flow center pump has failed internally in the electrical systems. Called Waterfurnace tech support to verify control board was operating properly first. Repairs habe been approved and parts will be ordered. Office staff will call back to schedule repair when parts are in hand. Flow center pump has failed internally in the electrical systems. Called Waterfurnace tech support to verify control board was operating properly first. Repairs habe been approved and parts will be ordered. Office staff will call back to schedule repair when parts are in hand.

Nate G.

Nate G. Job Checkin

Replaced blower capacitor on 1993 Trane 80% propane furnace Has a 5 series geo split and a 5 series package unit Pressurized closed loop


Brandon P.

Brandon P. Job Checkin

Outdoor fan motor bearings are in initial stages of failure. Recommend replacement of fan motor before total failure. Motor has been ordered and Westin will call back to schedule once part is in hand.

Outdoor fan motor bearings are in initial stages of failure. Recommend replacement of fan motor before total failure. Motor has been ordered and Westin will call back to schedule once part is in hand.

Nate G.

Nate G. Job Checkin

20 year old Goodman heat pump system 15 kilowatt auxiliary heat pack only operating at 5kw. Two of the three heat strips have failed Incorrect filter size has been in place for an unknown amount of time Indoor air coil is plugged with dirt as a result Heat pump is performing below specification System cannot keep up with heating demands Recommend full system replacement

20 year old Goodman heat pump system 
15 kilowatt auxiliary heat pack only operating at 5kw.  Two of the three heat strips have failed
Incorrect filter size has been in place for an unknown amount of time
Indoor air coil is plugged with dirt as a result
Heat pump is performing below specification
System cannot keep up with heating demands

Recommend full system replacement 20 year old Goodman heat pump system 
15 kilowatt auxiliary heat pack only operating at 5kw.  Two of the three heat strips have failed
Incorrect filter size has been in place for an unknown amount of time
Indoor air coil is plugged with dirt as a result
Heat pump is performing below specification
System cannot keep up with heating demands

Recommend full system replacement

Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 20x25x4 Clean flame sensor Inspect burners - rusty - pull and install stainless Pressure 1.7 down to 1.5 3.6 down to 3.2 Ohm test igniter: 50.6 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 10.0 Check amp draw on inducer motor:0.46 Check delta T - 56° Furnace is in optimal running conditions


Nate G.

Nate G. Job Checkin

Replaced blower motor, capacitor, and belly band Installed 16x25x1 filter (was laying next to the furnace) inside the furnace cabinet. There's a slot for it next to the blower motor Furnace needs replaced


Nate G.

Nate G. Job Checkin

Replaced inducer assembly Signed up for gold maintenance Parts are NOT under warranty

Replaced inducer assembly 

Signed up for gold maintenance

Parts are NOT under warranty

Nate G.

Nate G. Job Checkin

Brittle wire broke off Replaced bad connection System heating normally at this time. Ran both heating systems to verify 0ppm carbon monoxide present at this time.


Nate G.

Nate G. Job Checkin

Heat exchanger failed Propane wants quotes for full system and furnace only Furnace and AC Furnace and heat pump Bryant and Daikin options for full system replacements Include price option for bypass humidifier Floor to supply trunk 62" high 21" wide 50' line set 50' exhaust 8x24 return drop Siemens breaker panel 30A currently for outdoor unit

Heat exchanger failed
Propane
wants quotes for full system and furnace only
Furnace and AC
Furnace and heat pump 
Bryant and Daikin options for full system replacements
Include price option for bypass humidifier


Floor to supply trunk 62" high
21" wide
50' line set 
50' exhaust 
8x24 return drop
Siemens breaker panel 30A currently for outdoor unit Heat exchanger failed
Propane
wants quotes for full system and furnace only
Furnace and AC
Furnace and heat pump 
Bryant and Daikin options for full system replacements
Include price option for bypass humidifier


Floor to supply trunk 62" high
21" wide
50' line set 
50' exhaust 
8x24 return drop
Siemens breaker panel 30A currently for outdoor unit

Brandon P.

Brandon P. Job Checkin

Instsll warranty Fp1 sensor is reading incorrectly and causing system to trip on fp1 sensor. On site, sensor read 18f while fieldpiece probe read 28f. Will need to get new sensor and return to replace. Called waterfurnace and left voice-mail. Replaced faulty fp1 sensor and test ran system. Verified corrdct reading with temperature probe. System is operational with no errors.