Chris has a great attention to detail and is always willing to help us with our Energy Star Program
Very responsive and gets the job done!
Working with Chris is always easy. He is almost always available to talk and responsive to when I have something I need help with. Willing to answer any questions I have and always trying to make things right for me and the client.
Chris is quick to respond and is a man of his word. He is passionate about what he does and is quality driven.
I, Seth Peters, am a 18-year veteran and Employee #1 of Westin Air. We specialize in WaterFurnace geothermal, daiken and mitsubishi many split and whole home equipment, new construction and replacement installs
Chris takes pride in his works and cares about things getting done properly!
Always on top of his game and knows everything that’s is happening in all his communities.
Great service and great price!
Great company. Always feel like they are looking out for me, from the time I call and make my bi-yearly appointments to the time the maintenance is complete and they walk out the door....top performance, top customer service. Thank you.
Seth provided excellent service as well as a descriptive report of all work done. He also provided some good tips to keep that we could do to keep things in proper working order. Thanks.
Very positive experience. Seth answered all questions and concerns we had.
THE MAN YOU SENT WAS VERY NICE AND DID A GREAT JOB. I FEEL VERY GOOD THAT I WILL NOT HAVEANY PROBLEMS THISWINTER.
Upon arrival inspected unit and found unit backed up with water. Reconfigured drain to allowed better drainage and cleared blockage on line then test ran furnace. No concerns at this time unit running as should.
Remove and replace humidifier water canisters on 18 systems Remove and replace 210 air filter on 27 systems Remove and replace x2 20x25x1 for fresh air intakes Remove and replace 20x25x4 glassfloss filter for dessert Aire / test Clean flame sensors on pool house furnaces. Clean flame sensors car barn furnaces. Test run heat on each system verifying operation Clean minisplit washable filters for guard shack and main house garage
Install new condenser coil covered under manufacturers parts warranty.
2019 Goodman high efficiency furnace running in great condition. 20x25x1 air filter in good condition. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Run test unit in heating mode. Temperature rise is 53F with supply temp of 122F. Blower motor and inducer motor running within spec. 3" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. Furnace is operating properly, efficiently and ready for Winter.
2015 Trane XV95 running in great condition. 16x25x1 air filter in good condition. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Humidifier pad in good condition and damper opened. Test run furnace in heating mode. Temperature rise of 54F with supply temp of 123F. 2" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. Tested humidifier operation. All systems are operating properly, efficiently and ready for Winter.
Gas heating preventative maintenance performed Check filter - 20x25x1 new today Clean flame sensor Ohm test igniter: 59.7 Inspect wiring for loose connections and/or hot spots - none found Check drain trap - fix loose clamp on drain Inspect exhaust flu - 3” pvc no concerns Set thermostat for heat Check amp draw on blower motor: 2.85 Check amp draw on inducer motor:0.35 Check delta T - 55° Furnace is in optimal running conditions
Two system heating maintenance Basement system York 2 stage 96% efficient furnace Pulled and cleaned flame sensor Condensate trap is integral to the collector box Aprilaire 600 humidifier operating normally. No water leaks at this time Water panel is in good condition Cleaned Trane CleanEffects electronic air cleaner with shopvac and brush High fire gas pressure was 4"wc, spec is 3.5. Dialed it back to 3.5" Temp rise 50⁰ Low fire was 2"wc, spec is 1.5" Dialed back to 1.5 Temp rise 40⁰ Attic system York 2 stage 96% Cleaned trane electronic air cleaner Disabled humidifier from operating. There is no auxiliary drain pan underneath it Cleaned flame sensor Wired thermostat for two stage heat operation. Gas pressure 3.5" high fire temp rise 43⁰ Low fire 1.5" Temp rise 41⁰
Install new evaporator coil under manufacturers parts warranty and file claim for defective part.
Assessed condensate drain that was leaking on the attic AC system Cut out and replaced bad section. Poured water to test. Found drain line clogged. Followed drain to the basement where it goes into the sump pump pit Used wet/dry vacuum multiple times to suck out the clogs Put lots of condensate drain treatment in the trap and pour lots of water down the drain to verify the drain is flowing well now.
Gas heating preventative maintenance performed east Check filter - 210 new today Clean flame sensor Ohm test igniter: 68ohms Inspect wiring for loose connections and/or hot spots - none found Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 3.4 Check amp draw on inducer motor:1.0 Check delta T - 45° Furnace is in optimal running conditions Gas heating preventative maintenance performed west Check filter - 210 new today Clean flame sensor Ohm test igniter: 70ohms Inspect wiring for loose connections and/or hot spots - none found Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 4.8 Check amp draw on inducer motor:0.9 Check delta T - 55° Furnace is in optimal running conditions Electric Heating preventative maintenance performed Turn heat on at thermostat Blower motor ECM - no concerns Temp rise at 49° for emergency heat Furnace and heat pump in optimal running conditions
2014? Heat Controller GeoMax2 geothermal unit operating in good condition. Visual inspection of blower and compesssor compartments. No issues suspected. Test ran system in electric strip heat to verify proper operation of heating strips. All strips are operating properly with a ~20A draw at 240v. Electric strip heat temperature rise of 29F. Test ran geothermal heating operation. Geothermal heating running with a 22F temperature rise. Tested operation of geo and strip heat with a temperature rise of 41F. All parameters and equipment measured within spec. Did not check refrigerant as there is no issue suspected. System is operating properly, efficiently and ready for Winter. Theresa asked about whole home humidifier install. Pictures were taken of system and a quote will be made for humidifier install.
Bryant Q#798041 Upon arrival discovered unit was operating but not seeming to properly cool. Unit had water in drain pan. Refrigerant pressures adequate, coil not severely dirty, only concern found was with water in furnace pan. Inspected and found coil icing up. Bryant has replacements in stock. Quote will be worked up tomorrow morning and sent over
Two system water furnace 7 series heating equipment tune-up, maintenance, cleaning, filter inspection, ground loop antifreeze test run, safety inspection and performance evaluation Inspect and set up humidifiers, run test all electric auxiliary resistance heat, 20KW on 5 ton lower level, 15 KW on 3 ton upper level front door system. Lower level equipment is currently experiencing multiple software/hardware issues that would definitely benefit from immediate attention but does not appear to be affecting the operation of any modes at this time The lower level 5 ton equipment has repeatedly dropped the symphony Aurora web link Wi-Fi connection and communications and did not function at all between the May cooling inspection and October heating inspection After performing all services today and reestablishing power and communication to the web link both systems required a power cycle to reestablish symphony operations. The lower level equipment is also experiencing a unknown problem a
Replacement warranty - door switch improperly depressed
Install WaterFurnace 5 Series Geothermal system. 2 Stage compressor, Variable Speed ECM blower Model #W5AV036 Serial# 250802299 Efficiency: Up to 5.0 COP / 30.0 EER Features Included: *Aurora Advanced Controls *Hot Water Generation, connect to existing system *15 KW Backup heat *2" Merv 11 air filter *GeoLink loop flow center *Vision Pro 8000 WiFi thermostat Installation: *Reconnect to existing loop and top off antifreeze as needed. *Reconnect to existing high voltage electrical circuit *Transition to existing supply and return duct Warranty: (Annual maintenance must be performed) WaterFurnace 10 Year Parts WaterFurnace 5 Year Labor Flow Center and Accessories 5 Year Parts and Labor Warranty does not cover existing loop field. *** 30% Federal Tax Credit Eligible *** 2% Cash/Check Discount Available **High Voltage Electric to be Done by Others** **Westin Air Not Responsible for Defects with Existing Equipment and/or Loop Field**