725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews
for delaware, oh

Rated 4.9 out of 5 stars based on 27 customer reviews

Attention to detail

Chris has a great attention to detail and is always willing to help us with our Energy Star Program

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service, Quality personnel

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service Professional employees!

Very responsive and gets the job done!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great communication

Working with Chris is always easy. He is almost always available to talk and responsive to when I have something I need help with. Willing to answer any questions I have and always trying to make things right for me and the client.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service and quick response!

Chris is quick to respond and is a man of his word. He is passionate about what he does and is quality driven.

  • Overall Experience
  • Quality
  • Price
  • Convenience

A professional in your own neighborhood

I, Seth Peters, am a 18-year veteran and Employee #1 of Westin Air. We specialize in WaterFurnace geothermal, daiken and mitsubishi many split and whole home equipment, new construction and replacement installs

  • Overall Experience
  • Quality
  • Price
  • Convenience

Takes Pride

Chris takes pride in his works and cares about things getting done properly!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service

Always on top of his game and knows everything that’s is happening in all his communities.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service, arrived on time and the price was great

Great service and great price!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service, as always

Great company. Always feel like they are looking out for me, from the time I call and make my bi-yearly appointments to the time the maintenance is complete and they walk out the door....top performance, top customer service. Thank you.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Had service performed

Hi quality and knowledgeable

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Technician is competent and keeps to schedules.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Courteous and knowledgeable technician

Seth provided excellent service as well as a descriptive report of all work done. He also provided some good tips to keep that we could do to keep things in proper working order. Thanks.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Always great, professional service

Very positive experience. Seth answered all questions and concerns we had.

  • Overall Experience
  • Quality
  • Price
  • Convenience

very happy with the service

THE MAN YOU SENT WAS VERY NICE AND DID A GREAT JOB. I FEEL VERY GOOD THAT I WILL NOT HAVEANY PROBLEMS THISWINTER.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for delaware, oh

Brandon P.

Brandon P. Job Checkin

Replace damaged internal water line and test run operation. No other issues found or suspected.


Jason D.

Jason D. Job Checkin

SOLD: 02/11/2026 9:11:07 AM - Option 1 Install New Bryant Two Stage Gas Furnace Model #: 927TA48060V17 Serial #: 60,000 BTU’s - 97% AFUE Installation: * Reconnect to existing gas line and high voltage electric * Transition to existing supply and return ductwork * Start up and commission new system * Honeywell T6 Pro Thermostat Warranty: 20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed) 10 Year Bryant manufacturers Parts Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed)


Nate G.

Nate G. Job Checkin

Fault codes erase themselves after 72 hours, no stored fault codes upon arrival Found inducer and condensate trap gaskets leaking water inside the furnace Removed inducer and condensate trap Flushed trap with water Replaced trap gasket Resealed inducer seals with RTV Blower is clean 20x25x1 Filter is in good shape Pulled flame sensor and cleaned Run tested furnace High fire gas pressure set to 3.2"wc, Temperature rise 46⁰ Low fire gas pressure set to 1.3"wc, temperature rise 41⁰ No water leaks present at this time Furnace is operating perfectly within factory specifications at this time

Fault codes erase themselves after 72 hours, no stored fault codes upon arrival
Found inducer and condensate trap gaskets leaking water inside the furnace
Removed inducer and condensate trap
Flushed trap with water
Replaced trap gasket
Resealed inducer seals with RTV
Blower is clean
20x25x1 Filter is in good shape 
Pulled flame sensor and cleaned 
Run tested furnace
High fire gas pressure set to 3.2"wc, Temperature rise 46⁰
Low fire gas pressure set to 1.3"wc, temperature rise 41⁰
No water leaks present at this time
Furnace is operating perfectly within factory specifications at this time Fault codes erase themselves after 72 hours, no stored fault codes upon arrival
Found inducer and condensate trap gaskets leaking water inside the furnace
Removed inducer and condensate trap
Flushed trap with water
Replaced trap gasket
Resealed inducer seals with RTV
Blower is clean
20x25x1 Filter is in good shape 
Pulled flame sensor and cleaned 
Run tested furnace
High fire gas pressure set to 3.2"wc, Temperature rise 46⁰
Low fire gas pressure set to 1.3"wc, temperature rise 41⁰
No water leaks present at this time
Furnace is operating perfectly within factory specifications at this time

Nate G.

Nate G. Job Checkin

Replace HEPA filters and UV bulbs on all systems Left a full set of additional HEPA maintenence kits Install intake condensate drain coupling on the in-law suite furnace

Replace HEPA filters and UV bulbs on all systems
Left a full set of additional HEPA maintenence kits

Install intake condensate drain coupling on the in-law suite furnace Replace HEPA filters and UV bulbs on all systems
Left a full set of additional HEPA maintenence kits

Install intake condensate drain coupling on the in-law suite furnace

Brandon P.

Brandon P. Job Checkin

Install Totaline whole home humidifier onto hvac system. Install humidifier controller and wire into EAC terminal. Humidifier can run whenever the blower is operating. Recommend turning thermostat fan option to ON for first week or two to increase humidifier operating time to get to set humidity of 40%. Hook up water line and tie into ac coil drain line. Adjusted furnace blower speed for humidifier application. System is operating properly.

Install Totaline whole home humidifier onto hvac system. Install humidifier controller and wire into EAC terminal. Humidifier can run whenever the blower is operating. Recommend turning thermostat fan option to ON for first week or two to increase humidifier operating time to get to set humidity of 40%. Hook up water line and tie into ac coil drain line. Adjusted furnace blower speed for humidifier application. System is operating properly. Install Totaline whole home humidifier onto hvac system. Install humidifier controller and wire into EAC terminal. Humidifier can run whenever the blower is operating. Recommend turning thermostat fan option to ON for first week or two to increase humidifier operating time to get to set humidity of 40%. Hook up water line and tie into ac coil drain line. Adjusted furnace blower speed for humidifier application. System is operating properly.

Graham M.

Graham M. Job Checkin

Replace high limit and verify operation. Unit was cycling on limit flashing in and out while messing with wiring. Unit stopped showing problems but homeowner wanted to be proactive so limit was replaced.


Brandon P.

Brandon P. Job Checkin

Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary.

Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary. Upon arrival, system has a tripped rollout switch. Reset switch and performed test run of system. During system test, performed a combustion analysis to test integrity of the heat exchanger. Upon insertion of the combustion analyzer, the system read approximately 300ppm COAF, before immediately shutting off on CO threshold exceeded safety measure. System is not safe to operate and has been disabled to prevent operation. Due to the age of the system, 2009, replacement of the furnace is necessary.

Brandon P.

Brandon P. Job Checkin

Outdoor fan motor bearings are in initial stages of failure. Recommend replacement of fan motor before total failure. Motor has been ordered and Westin will call back to schedule once part is in hand.

Outdoor fan motor bearings are in initial stages of failure. Recommend replacement of fan motor before total failure. Motor has been ordered and Westin will call back to schedule once part is in hand.

Nate G.

Nate G. Job Checkin

Replaced inducer assembly Signed up for gold maintenance Parts are NOT under warranty

Replaced inducer assembly 

Signed up for gold maintenance

Parts are NOT under warranty

Graham M.

Graham M. Job Checkin

Replace blower wheel and motor under manufacturers parts warranty to help dampen the noise heard near return air in hall way. If noise is still over comfort levels I would advise having us slow down stage 2 blower speeds only if noise is still problematic.


Nate G.

Nate G. Job Checkin

Bypass humidifier


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed basement Check filter - 20x25x4 due soon Clean flame sensor Inspect burners - no concerns Ohm test igniter: 56.2 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: new today Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 2.72 Check amp draw on inducer motor:0.62 Check delta T - 66° Furnace is in optimal running conditions Gas heating preventative maintenance performed 2nd floor Check filter - 20x25x4 due soon Clean flame sensor Inspect burners - no concerns Ohm test igniter: 58.2 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: new today Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 2.32 Check amp draw on inducer motor:0.51 Check delta T - 68° Furnace is in optimal running conditions


Graham M.

Graham M. Job Checkin

Found leak in same spot from previous repair. Need to return and perform repair again.

Found leak in same spot from previous repair. Need to return and perform repair again. Found leak in same spot from previous repair. Need to return and perform repair again.

Brandon P.

Brandon P. Job Checkin

Upon arrival, inspected overlook system found no major concerns with unit. Inspected boilers per Ralph request and boiler #2 was faulted and needed restarted. After restarting boiler 2 temp went from 109 to 160. Once boiler was back up and running changed out all filters for house and car barn. Opened overlook doors to allow master bed air into overlook. Master bed system sounds to have a bad blower motor/blower wheel humming loudly at system and spreading through nearby registers. Warranty motor should be quoted to reduce noise. Pool house is not accessible today due to the snow. It is 2ft+ deep in most places.

Upon arrival, inspected overlook system found no major concerns with unit. Inspected boilers per Ralph request and boiler #2 was faulted and needed restarted. After restarting boiler 2 temp went from 109 to 160. Once boiler was back up and running changed out all filters for house and car barn. Opened overlook doors to allow master bed air into overlook. Master bed system sounds to have a bad blower motor/blower wheel humming loudly at system and spreading through nearby registers. Warranty motor should be quoted to reduce noise. Pool house is not accessible today due to the snow. It is 2ft+ deep in most places. Upon arrival, inspected overlook system found no major concerns with unit. Inspected boilers per Ralph request and boiler #2 was faulted and needed restarted. After restarting boiler 2 temp went from 109 to 160. Once boiler was back up and running changed out all filters for house and car barn. Opened overlook doors to allow master bed air into overlook. Master bed system sounds to have a bad blower motor/blower wheel humming loudly at system and spreading through nearby registers. Warranty motor should be quoted to reduce noise. Pool house is not accessible today due to the snow. It is 2ft+ deep in most places.

Graham M.

Graham M. Job Checkin

Upon arrival, inspected system and found no current problems. Homeowner informed me that furnace was flashing a code 3. Trudge through 2foot deep snow to check vent pipe. Pipe is buried on roof with snow. Chop intake stuff towel into fresh air side and allow furnace room to intake air. -homeowner wants a 90 installed and the pipe capped off with 2” cap to prevent future problems. Informed him to have a handyman cut an intake into furnace room using return grills before installing cap and 90. May change it to having drain added and pipe extended on roof not sure of direction to go.