Upon arrival, spoke with employees and they stressed concerns over the two RTU‘s outback one of them is overheating and the other one is not igniting. Both unit units need belts and filters. Belt is bx68 and filters are x2-20x20x2 x4-20x25x2 need two orders for the left and the right systems. The igniter on the left one is bad at 168 ohms. Right tested at 72. May as well order two igniters So that the right one doesn’t have the same problem in a few weeks. Will build quote for repairs on Monday when parts stores open