Rated 4.9 out of 5 stars based on 17 customer reviews

Wonderful service

Great service, clean, and courteous. Very friendly. This was an annual check and a piece was broken. They had it on the truck and repaired it that day. Highly recommend.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Very knowledgeable technician

Seth did a great job. He was very knowledgeable and quickly diagnosed our issue.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great, quick service

Great quick service, and did more than I even expected

  • Overall Experience
  • Quality
  • Price
  • Convenience

Repeat Customer for a reason

This is my second house that I am using Westin air for servicing, and not just annual HVAC inspections and cleaning. My first house only had one air vent in a large furnished basement. It caused problems. They added more circulation without touching the cosmetics. My 2nd house needs more circulation in the basement due to moisture in the summer. There air no water leaks in the walls to fix. Just stale, moist air forcing me to run the dehumidifier. Their pricing is reasonable for the work and the cost savings from the electric bill is worth it.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

All went well and to our satisfaction

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

The technicians quickly diagnosed the problem and fix our unit

  • Overall Experience
  • Quality
  • Price
  • Convenience

Always helpful

  • Overall Experience
  • Quality
  • Price
  • Convenience

Pleasant and thorough.

Westin still has a 5 star rating with me, though the fact that Westin canceled out original appointment and was late on the rescheduled appointment puts that opinion in jepordy.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great price and installation

I'm very satisfied with Weston air. I complement their sales person who came to out home and the office person for her attention. The installation crew was excellent.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Thanks for sending Seth.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Timely service, good inspection and advise

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service! Seth is extremely friendly and easy to work with!

I am very pleased with our service from Westin Air. They are very accommodating to crazy schedules as well.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Westin Air is one of the most easy to deal with service company I have dealt with in a long time. From the front office staff to the service team everyone is friendly and professional and are very responsive to any question or concern I have had. They stand behind the products they represent and are very easy to deal with. I had a new HVAC system installed about a year ago and have had multiple issues within this time period. Seth my service tech came out and spent numerous hours diagnosing and eventually fixing the problem so I can defiantly say they stand behind the products.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Satisfied!

Seth arrived within the window and performed annual maintenance on two furnace units. He was courteous while in the home, performed his work timely and made sure to point out items that needed my attention. I have used Westin a number of times over the past year for various properties and have always felt they provided a good service that is reliable and honest. I would recommend Westin to anyone looking for service on their heating/air systems.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for powell, oh

Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on two gas furnaces. Both air filters in good condition. Basement humidifier pad needs changed due to calcium buildup up. Keith is getting it himself. Cleaned flame sensors and checked ignitors. Visual inspection of burners. Flush condensation trap on basement system. Test ran each in gas heating mode. Both systems are operating properly and within specifications for temperature rise, blower and inducer motor amp draw, and gas pressure. Exhaust vents are all in good condition and no sign of leaks. 0PPM CO detected during testing. Performed non invasive test on geothermal heating. Refrigerant temperatures are within spec. No unusual codes in the geothermal systems. Systems are operating properly, efficiently and ready for Winter.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on standard efficiency American Standard furnace running in good condition. Trane Clean Effects pre-filter cleaning. #35 humidifier pad in good condition. Clean flame sensor and check ignitor. Visual inspection of burners. Test ran in heating mode. Temperature rise is within specs. Blower and inducer motors tested good. Flue vent is solid. 0PPM CO detected during testing. System is operating properly, efficiently and ready for Winter.


Nate G.

Nate G. Job Checkin

Install new indoor air coil as part of Geothermal split systems. New coil to be R-410a with txv to match geothermal system.


Graham M.

Graham M. Job Checkin

upon arrival inspected system and found no concerns heat pump heating at 22° independent and 67° with strips. humidifier #35 panel due ASAP to prevent leaking. adjust thermostat programming to revert -2° offset to 0°. tabletop thermostat reading 68° at 72°


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on Carrier propane furnace and Waterfurnace geothermal units. Gas furnace inspection includes filter check, flame sensor cleaning and ignitor test, condensate trap cleaning, operation test to test gas pressure, air temperature rise, and check for carbon monoxide. All gas furnace test came back good with no issues found or suspected. Waterfurnace inspection included operation test to test refrigerant temperatures, air temperature rise, and ground loop pressure/temperature. Only issue found with geothermal operation was low ground loop pressure. Over time, the ground loops pipes with expand and cause pressure drop, and this does not mean there is a leak. Repressurized ground loop from 10psi to 80psi. Low ground loop pressure will lead to inefficient operation due to reduced heat transfer. Inefficient operation causes longer run times. Question about ground loop position should be able to be answered by Jackson Well Services as they were the ins

Preventative maintenence inspection on Carrier propane furnace and Waterfurnace geothermal units. Gas furnace inspection includes filter check, flame sensor cleaning and ignitor test, condensate trap cleaning, operation test to test gas pressure, air temperature rise, and check for carbon monoxide. All gas furnace test came back good with no issues found or suspected. 

Waterfurnace inspection included operation test to test refrigerant temperatures, air temperature rise, and ground loop pressure/temperature. 

Only issue found with geothermal operation was low ground loop pressure. Over time, the ground loops pipes with expand and cause pressure drop, and this does not mean there is a leak. Repressurized ground loop from 10psi to 80psi. 

Low ground loop pressure will lead to inefficient operation due to reduced heat transfer. Inefficient operation causes longer run times. 

Question about ground loop position should be able to be answered by Jackson Well Services as they were the ins Preventative maintenence inspection on Carrier propane furnace and Waterfurnace geothermal units. Gas furnace inspection includes filter check, flame sensor cleaning and ignitor test, condensate trap cleaning, operation test to test gas pressure, air temperature rise, and check for carbon monoxide. All gas furnace test came back good with no issues found or suspected. 

Waterfurnace inspection included operation test to test refrigerant temperatures, air temperature rise, and ground loop pressure/temperature. 

Only issue found with geothermal operation was low ground loop pressure. Over time, the ground loops pipes with expand and cause pressure drop, and this does not mean there is a leak. Repressurized ground loop from 10psi to 80psi. 

Low ground loop pressure will lead to inefficient operation due to reduced heat transfer. Inefficient operation causes longer run times. 

Question about ground loop position should be able to be answered by Jackson Well Services as they were the ins

Nate G.

Nate G. Job Checkin

Replace transformer and add a low voltage fuse to protect new transformer Cannot fully diagnose unit without a working transformer Additional issues may be found after this repair Replace inducer motor assembly for Elliot's The three systems pertaining to this quoted work are now heating normally at this time.


Jason D.

Jason D. Job Checkin

Humidifier not wired correctly


Nate G.

Nate G. Job Checkin

Dual fuel geo split 5 series 4 ton water furnace Lennox natural gas 2 stage 96% Installing contractor used Lennox evaporator coil as the air coil Geo is low on refrigerant and already has leak sealant in the system Gas furnace was throwing a slew of pressure switch codes Found furnace burner intake pipe full of foliage Cut pipe and cleared blockage. Put intake back together with an unglued coupling for future cleanout Gas furnace operating properly now Removed cover for Lennox coil. No obvious signs of a leak. From experience, the likelihood of the Lennox coil leaking refrigerant is very high. Recommend replacing coil with a water furnace coil 21" wide coil. If taller than 29", reme halo will need removed and humidifier bypass relocated to the side of the plenum.

Dual fuel geo split 
5 series 4 ton water furnace
Lennox natural gas 2 stage 96%
Installing contractor used Lennox evaporator coil as the air coil
Geo is low on refrigerant and already has leak sealant in the system
Gas furnace was throwing a slew of pressure switch codes

Found furnace burner intake pipe full of foliage
Cut pipe and cleared blockage.  
Put intake back together with an unglued coupling for future cleanout
Gas furnace operating properly now 

Removed cover for Lennox coil.  No obvious signs of a leak.  From experience, the likelihood of the Lennox coil leaking refrigerant is very high.  
Recommend replacing coil with a water furnace coil
21" wide coil.  If taller than 29", reme halo will need removed and humidifier bypass relocated to the side of the plenum.

Brandon P.

Brandon P. Job Checkin

Install new Geo-Link 2-Pump Non-pressurized flow center. Connect to existing lop lines and electric supply. Test run operation and fill to appropriate level. Check again weekly for the first month to top off if any air bubbles are pushed out of the system.


Install new Geo-Link 2-Pump Non-pressurized flow center. Connect to existing lop lines and electric supply. Test run operation and fill to appropriate level. Check again weekly for the first month to top off if any air bubbles are pushed out of the system. 
Install new Geo-Link 2-Pump Non-pressurized flow center. Connect to existing lop lines and electric supply. Test run operation and fill to appropriate level. Check again weekly for the first month to top off if any air bubbles are pushed out of the system.

Nate G.

Nate G. Job Checkin

Dip switch setting for freeze protection was incorrect Wiring for humidifier incorrect Verified correct humidifier operation with the thermostat settings Signed up for maintenance plan


Nate G.

Nate G. Job Checkin

Performed heating maintenance on first floor furnace Pulled burgers, they're in good shape Pulled condensate trap and flushed with hot water Pulled flame sensor and cleaned Filter OK Replaced humidifier pad Run tested furnace and performed combustion analysis Combustion numbers are very healthy Low fire 2.2" 38⁰ temp rise Med fire 5.8" 42⁰ temp rise High fire 11" 39⁰ temp rise Furnace is operating within factory specs at this time Heat pump operation is also perfectly within healthy operating numbers at this time: 31,000btu output 150⁰ Vapor line tempature 30⁰ temperature rise 46⁰ outdoor temperature Invoice payable online Also sent maintenance plan as a separate email

Performed heating maintenance on first floor furnace
Pulled burgers,  they're in good shape 
Pulled condensate trap and flushed with hot water 
Pulled flame sensor and cleaned 
Filter OK
Replaced humidifier pad
Run tested furnace and performed combustion analysis
Combustion numbers are very healthy
Low fire 2.2" 38⁰ temp rise 
Med fire 5.8" 42⁰ temp rise
High fire 11" 39⁰ temp rise
Furnace is operating within factory specs at this time

Heat pump operation is also perfectly within healthy operating numbers at this time:
31,000btu output
150⁰ Vapor line tempature
30⁰ temperature rise 
46⁰ outdoor temperature 

Invoice payable online
Also sent maintenance plan as a separate email Performed heating maintenance on first floor furnace
Pulled burgers,  they're in good shape 
Pulled condensate trap and flushed with hot water 
Pulled flame sensor and cleaned 
Filter OK
Replaced humidifier pad
Run tested furnace and performed combustion analysis
Combustion numbers are very healthy
Low fire 2.2" 38⁰ temp rise 
Med fire 5.8" 42⁰ temp rise
High fire 11" 39⁰ temp rise
Furnace is operating within factory specs at this time

Heat pump operation is also perfectly within healthy operating numbers at this time:
31,000btu output
150⁰ Vapor line tempature
30⁰ temperature rise 
46⁰ outdoor temperature 

Invoice payable online
Also sent maintenance plan as a separate email

Brandon P.

Brandon P. Job Checkin

Upon arrival, system is showing a code E2.1 "Retries exceeded (Flame failed to establish)." Attempted to fire off furnace to test operation. Inducer motor comes on as it should. Ignitor glows as it should. Gas valve opens as it should but then only stays on for approximately three seconds. Inspected flame sensor and it is not terribly dirty. Removed one burner to inspect for rust. Burner is extremely rusty causing the flame sense feature to not work. When ignition happens, the furnace does not get any signal for flame established. Replaced oem Trane steel burner with oem Trane stainless steel burners to prevent rusting. Test ran operation of system with no other issues found or suspected.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on Trane high efficiency furnace running in great condition. 20x25x4 air filter in new condition. #35 humidifier pad should be changed due to calcium buildup. This buildup can cause efficiency loss and possibly a water leak. Shravan is getting a new pad. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Run test unit in heating mode from thermostat. Temperature rise is within specs. Blower and inducer motors tested good. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. Humidifier tested during heating mode test. System is operating properly, efficiently and ready for Winter.


Brandon P.

Brandon P. Job Checkin

50a fuse failure on 240v circuit. Heat strips are not getting proper power. Replaced fuses with non-fused connections since main breaker is rated properly. Test run two remaining heat strips. Both are pulling approximately 20A and within range. System is operwtingnin both geothermal and auxiliary at this time.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on Carrier high efficiency furnace running in great condition. AA21y air filter in dirty condition. Filter will need replaced soon. #35 humidifier pad in good condition, damper opened and water valve turned on for minimal amount. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Run test unit in heating mode. Temperature rise is within specs. Blower and inducer motors tested good. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. Humidifier tested during heating mode test. Dehumidifier is off for Winter. All systems are operating properly, efficiently and ready for Winter.