Perform gold cooling PMI Filter ok Delta T 21° Refrigerant pressures sc/SH within spec Coil is clean Amps are within spec unit is operating properly at this time
Water furnace 5 series Thermostat locked out on e10 compressor monitor with 31 lockout cycles recorded in AID diagnostics. Control circuit is active with power provided by EAH supply voltage Compressor circuit has no power. 45 amp two-pole breaker in the main panel is in the tripped off center position. Also at the same time One of the two five amp resettable circuit breaker at the control board is also tripped.. Both circuit breakers reset and all systems ran normal. E10 on the communicating thermostat was activated by no compressor power or operation. The primary cause of both circuit breaker trips could not be determined while on site today. 30uf compressor capacitor is within specs Hot water generator circuit is functioning and running normal. Two pump flow center is also functioning with both motors operational registering 15.5 GPM on the AIS tool System is registering high heat of rejection at 54K on aid compared to book specs however all other systems, water temperatures,
14-year-old water furnace premiere locked out on high pressure and water flow LED. Comfort alert compressor monitor active on short cycle alarm #2 Pressurized ground loops at 22 PSI, static off refrigerant pressure 178 Initial testing found no power to flow center caused by blown 10 amp L2 relay supply voltage fuse. Flow center has one of two pumps locked up. Due to the age and condition of the flow center individual pumps cannot be replaced. Confirmed alcohol-based antifreeze at 0.975 Repressurize ground loops to 60 psi Replaced blown high voltage 10 amp fuse for temporary operation with three amp fuse for flow center Disabled left side flow center pump Run test equipment in cooling mode. Current refrigerant pressures with 50% water flow potential are at 107 & 247. Refrigerant pressures will need retested and probably adjusted after full water flow and pressure are reestablished. The compressor discharge line service port currently has a very minor refrigerant oil leak nearly
Break room AC frozen up Diagnosed failed furnace blower motor. Replaced with universal 3/4HP motor and new capacitor. Left AC power disconnect switched off to allow the system to thaw. Advised not turning it back on until tomorrow morning.
Removed 2 hanging heaters in the warehouse capped off flu, gasline and high voltage. Left one unit there that they said was working for them to reuse at a later time.
Per pre-authorized diagnosis, recharge rooftop package equipment. System is known to have leaks and there is no guarantees or warranties on refrigerant, labor, or additional diagnostics or trip charges Recharge 3.8 lb R422D (full charge) XP brand refrigerant leak stop with dye Pre recharge, The system was locked out on low pressure switch with 6.0 PSI Recharge equipment to running pressures of 70psi with 25° superheat and 399psi discharge pressure Supply temperature after recharge 60.6° f Equipment does not have any drain lines attached to assist in condensate removal Both 20x30x1 air filters had to be removed due to excessive air flow restriction
2023 water furnace 5 series including performance and refrigeration package. Two pump non-pressurized flow center. Alcohol test 0.977 equivalent to 10° f freeze protection Inspect and test run hot water generator circuit. Confirm relay and circulator pump operation, confirm heating temperature rise from 66.7 Entering to 73.2 leaving. During 45 minute run test for cooling season maintenance the tank temperature increased from 63.8 to 71.4 Test run vision pro 8000 thermostat in multi-stage cooling mode and confirm 45.3 supply air temperature. Test run non-pressurized two pump flow center at 13.9 GPMs 30x32x2 pleated air filter is like new and on schedule with homeowners All equipment is clean safe and ready for summer Homeowner will consult water heater plumber regarding any further concerns
2024 Trane Xzr AC running in new condition. 20x25x1 air filter is new today. Visual inspection of indoor coil. Check cooling blower speed and confirm for the proper 1000cfm for 2.5 ton AC. Run test unit in cooling mode from thermostat. Delta t of 20F with supply temp of 54F. Refrigerant pressures are within spec. High 300psi with 11F SC, low 130psi with 12F SH. Outdoor coils are in clean condition. Dual ran capacitor is within spec. Outdoor fan motor and compressor are operating within Amp draw specifications. System is operating properly, efficiently and ready for Summer.
Performed cooling PMI Replaced filter Closed humidifier damper Drain clear Blower clean Capacitor 63/12 actual measurement under load Charge looks off. Per the charging chart, head pressure was high and suction pressure was low. Tore down and gave the condenser a heavy wash. Got authorization for topping off refrigerant and adding sealant/UV dye Added 1lb r410a and a sealant with dye. System now running 20⁰ superheat at a 35⁰ vapor saturation which is within tolerances on the charging chart.
Bryant Preferred 96 2-Stage Gas Furnace Model #: 926TC60100V21 Serial #:11525A46436 100,000 BTU's 96% AFUE - VCT ECM Propane Conversion Kit Bryant Single-Stage Air Conditioner Model #: GA5SAN56000W Serial #: 1325G06983 5 Ton - 14.3 SEER2 Puron Advance Refrigerant, R-454B Matching Cased Coil: CVAVA6024XMC Serial #: 5024J25438 Installation: * Reconnect to existing gas line and high voltage electric * Transition to existing supply and return ductwork * Install propane conversion kit * Start up and commission new system * Honeywell thermostat Warranty: 20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed) 10 Year Bryant manufacturers Parts & Compressor Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed)
Diagnosed obvious refrigerant leaks at compressor and Condenser coil. We cannot guarantee there are not more leaks that are not visible. System is from 2001. Working up repair and replacement quotes.
Preventative maintenence inspection on three Lennox AC s0lit systems. Replaced all air filters, and shut humidifier dampers. Tested blower motor capacitors. Visually inspect indoor air coils, and flush out drain pans. Check thernostats for any warnings or battery level indicators with none found. Run test each unit in cooling mode from respective thermostat. All systems are operating within specs for refrigerant pressures/temperatures and supply air delta t specifications. Tested dual run capacitors on each AC. All are within spec. All condenser fan motors and refrigerant compressors are operating properly within Amp draw specifications. No issues found or suspected while performing inspections. Systems are operating properly, efficiently and ready for Summer.
2014 Trane EnviroWise geothermal split system with TAM5 air handler Air filter replaced by homeowners on schedule, inspect indoor air coil and flush drain system, inspect all electronics and perform minor maintenance cleaning. Test run Honeywell vision pro 8000 thermostat in multi-stage cooling geothermal heat pump mode Test run outdoor unit and cooling mode, repressurize alcohol ground loops from 20 to 45 PSI for summer time Clean and inspector outdoor electronics compartment and flow center motor Relevel outdoor unit permapad and wash down outdoor system
10-year-old water furnace premier branded in Trane Multiple issues unable to be repaired by comfort Express Initial test run failed to start the compressor and locked out on service code 6 on comforter alert indicating open start windings 440 volt compressor power supply set to 45 UF capacitor reading 10.9 Installed new turbo 200 compressor capacitor At the same time it was discovered that all three switch banks of the replacement control board were set to the factory standard Set all three Banks of dip switches designed for two stage with hot water generator and ECM 1\2hp motor Run test all equipment including refrigerant pressures and test antifreeze. 0.992 indicates a week or degraded mixture of alcohol antifreeze and freeze protection to roughly +25° Refrigerant pressures temperatures temperature drops and pressure drops all exactly within book specs with no questions Reattach existing low pressure switch that was bypassed by the previous company Recommend alcohol rejuvenat
Gas meter locked out for leakage beyond the stop cock of the furnace During inspection today no gas pressure is available for micro gel leak detection or electronic detection. Based on test results and photos provided to me by third party all indications are that the gas valve is leaking through and not closing tightly. 100% positive identification of the leak with no gas pressure will require a gas line plumber performing a pressure test. Option two replace gas valve and notify gas supplier that the repair has been completed. After gas pressure is reestablished an additional visit will be required to set the manifold pressures of the two-stage intermittent pilot gas valve The December 2004 TempStar high efficiency LP propane gas multi-stage equipment is in very poor neglected condition with extensive wear and tear and water damage that needs immediate attention. Such items include plastic heat exchanger collector box with micro cracks leaking water, The burners are rusted and c