725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews
for sunbury, oh

Rated 5.0 out of 5 stars based on 15 customer reviews

Chris was great

Showed up in a timely manner and explained everything very well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service!

Always there when I need them. And always ready to help out when I am in a pinch. Great guys to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service Exceeds Expectations

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Very professional Strive for excellence

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome

5 star plus

  • Overall Experience
  • Quality
  • Price
  • Convenience

5 Stars all the Way!

Excellent customer service and a tremendous knowledge of anything HVAC.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service!

Great job - thanks so much!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome Service!!

Seth and the guy with him were awesome!! They were super friendly and were very thorough in their explanation of what they were gonna do and when they were done, explained how to use the new humidifier with great detail!! The price was great too!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Preventive maintenance inspection

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

Seth was professional. Did excellent propane to gas conversions on three furnaces.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Alway pleasant and efficient

  • Overall Experience
  • Quality
  • Price
  • Convenience

Took lots of time to explain things, thank you!

I really appreciate Seth taking the time to explain things to me in a way I could understand. Very friendly and knowledgeable!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Replacement System-Furnace & Heat Pump

  • Overall Experience
  • Quality
  • Price
  • Convenience

New roof top furnace

They did a great job! Helpful and professional. Neat work and on time.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome Geothermal service

Quick, efficient and friendly service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for sunbury, oh

Nate G.

Nate G. Job Checkin

Performed heating maintenance on a Trane 2 stage 96% efficient propane-fired furnace Pulled and cleaned flame sensor Checked Condensate lines Adjusted burner Manifold pressure also had to increase house regulator pressure to get burner pressure correct 10"wc high fire 6"wc low fire Temperature rise 35⁰ for both fire rates 16x25x1 filter is in OK condition Signed up for silver maintenance plan


Nate G.

Nate G. Job Checkin

Performed two system heating maintenance Attic system: 2023 Lennox dual fuel system Two stage 96% efficient LP-fired furnace 3 ton heat pump 16x25x1 filter is good Left a new one with the furnace Corrected drain safety switch wiring to shut the furnace and AC down in the event ofman drain backup Run tested heat pump Getting 110⁰ Vapor line temperature and 17⁰ temperature rise Pulled and cleaned furnace flame sensor Cleared condensate ports internal to the furnace Run tested furnace High fire Manifold pressure set to 10"wc with reference to the sealed burner box Temperature rise 40⁰ Low fire pressure set to 4.5" Temperature rise 30⁰ Main system: 2023 Lennox dual fuel system 18 SEER inverter heat pump 2 stage 96% propane furnace Ductwork massively undersized 5 ton heat pump requires 2000CFM of air Return drop is 10x24" with one side utilizing a 16x25x1 filter Return trunk is 8x24 Ductwork needs to be at least 30x12 with a 20x25x4 filter, preferably a 24x25x4 Discussed issue of airflo

Performed two system heating maintenance

Attic system:
2023 Lennox dual fuel system
Two stage 96% efficient LP-fired furnace
3 ton heat pump
16x25x1 filter is good 
Left a new one with the furnace 
Corrected drain safety switch wiring to shut the furnace and AC down in the event ofman drain backup
Run tested heat pump
Getting 110⁰ Vapor line temperature and 17⁰ temperature rise
Pulled and cleaned furnace flame sensor
Cleared condensate ports internal to the furnace
Run tested furnace
High fire Manifold pressure set to 10"wc with reference to the sealed burner box
Temperature rise 40⁰
Low fire pressure set to 4.5"
Temperature rise 30⁰

Main system:
2023 Lennox dual fuel system
18 SEER inverter heat pump
2 stage 96% propane furnace
Ductwork massively undersized
5 ton heat pump requires 2000CFM of air
Return drop is 10x24" with one side utilizing a 16x25x1 filter
Return trunk is 8x24
Ductwork needs to be at least 30x12 with a 20x25x4 filter, preferably a 24x25x4
Discussed issue of airflo Performed two system heating maintenance

Attic system:
2023 Lennox dual fuel system
Two stage 96% efficient LP-fired furnace
3 ton heat pump
16x25x1 filter is good 
Left a new one with the furnace 
Corrected drain safety switch wiring to shut the furnace and AC down in the event ofman drain backup
Run tested heat pump
Getting 110⁰ Vapor line temperature and 17⁰ temperature rise
Pulled and cleaned furnace flame sensor
Cleared condensate ports internal to the furnace
Run tested furnace
High fire Manifold pressure set to 10"wc with reference to the sealed burner box
Temperature rise 40⁰
Low fire pressure set to 4.5"
Temperature rise 30⁰

Main system:
2023 Lennox dual fuel system
18 SEER inverter heat pump
2 stage 96% propane furnace
Ductwork massively undersized
5 ton heat pump requires 2000CFM of air
Return drop is 10x24" with one side utilizing a 16x25x1 filter
Return trunk is 8x24
Ductwork needs to be at least 30x12 with a 20x25x4 filter, preferably a 24x25x4
Discussed issue of airflo

Nate G.

Nate G. Job Checkin

Performed leak search on mini split of all flare fittings Found vapor line flare fitting on indoor head for the lobby Tightened flare. All other flare connections are good Next step will be recover refrigerant and reflare the line if tightening does not stop the leak

Performed leak search on mini split of all flare fittings
Found vapor line flare fitting on indoor head for the lobby
Tightened flare.  
All other flare connections are good
Next step will be recover refrigerant and reflare the line if tightening does not stop the leak

Jason D.

Jason D. Job Checkin

SOLD: 11/12/2025 9:47:28 PM - Option 1 Install New Bryant Two Stage Gas Furnace Model #: 927TA48080V17 Serial #: 4425A59611 80,000 BTU’s - 97% AFUE Installation: * Reconnect to existing gas line and high voltage electric * Transition to existing supply and return ductwork * Start up and commission new system * Air Filtration - AprilAire 1210 (20X25) Media Air Cleaner Warranty: 20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed) 10 Year Bryant manufacturers Parts Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed)


SOLD: 11/12/2025 9:47:28 PM - Option 1

Install New Bryant Two Stage Gas Furnace
Model #: 927TA48080V17
Serial #: 4425A59611
80,000 BTU’s - 97% AFUE
 
Installation:
* Reconnect to existing gas line and high voltage electric
* Transition to existing supply and return ductwork
* Start up and commission new system
* Air Filtration - AprilAire 1210 (20X25) Media Air Cleaner
 
Warranty:
20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed)
10 Year Bryant manufacturers Parts Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)

SOLD: 11/12/2025 9:47:28 PM - Option 1

Install New Bryant Two Stage Gas Furnace
Model #: 927TA48080V17
Serial #: 4425A59611
80,000 BTU’s - 97% AFUE
 
Installation:
* Reconnect to existing gas line and high voltage electric
* Transition to existing supply and return ductwork
* Start up and commission new system
* Air Filtration - AprilAire 1210 (20X25) Media Air Cleaner
 
Warranty:
20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed)
10 Year Bryant manufacturers Parts Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)

Nate G.

Nate G. Job Checkin

Zone 1 dampers whistling when closed during zone 2 call for heat Discussed options Decided to lock zone 1 dampers open


Jason D.

Jason D. Job Checkin

Install WaterFurnace 5 Series Geothermal split system. 2 Stage compressor - Geothermal Model # W5SZ048BD1B1FCFFFB10 4 Ton 5 Series Split Geo Serial# 251000494 -Geothermal Coil Model # A5DC048BNFA0FFFFFF1F Serial# 251000495 - Furnace #Bryant 927TA60080V21 Preferred 97, Up to 97% AFUE, Two-Stage, Variable 25-Speed, Non-Communicating, 4-Way Multipoise, Condensing Gas Furnace with InteliSense Technology, 80K, 5T, 21" width Serial# 2025A45614 Features Included: *Aurora Advanced Controls *April Aire 1210 High Efficiency Media Air Cleaner *2 Pump GeoLink non-pressurized loop flow center *Vision Pro 8000 WiFi thermostat Installation: *Install 4 Ton vertical closed loop field (Installed by Jackson Geothermal) *Reconnect to existing high voltage electrical circuit *Add electrical circuit for Geo split portion *Transition to existing supply and return duct Warranty: (Annual maintenance must be performed) WaterFurnace 10 Year Parts WaterFurnace 5 Year Labor Bryant Manufacturers Parts Warranty


Nate G.

Nate G. Job Checkin

Service recall Furnace board showing e01 fault (pressure switch failure to close) Inducer never runs Measured 0V to the inducer Noted board making a funny sound, too Swapped with a new board Inducer now runs Found igniter broken off New board kit includes an igniter Replaced the igniter Furnace operating normally at this time


Graham M.

Graham M. Job Checkin

Upon arrival, inspected system and found inducer motor is non-operable. Control board throwing code 3 inducer motor error. Inducer motor has zero resistance, spins freely, but will not turn on. Called train and motor is available but extremely expensive being an ECM inducer. Recommend replacement over repair due to repair repair costs, quote for repair and quote number are in estimates in case replacement is not the route taken.


Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2001 Trane 78% efficient single stage natural gas furnace 16x25x1 filter is OK, **will need changed in another month or so** Pulled and clesned flame sensor Blower wheel is not the cleanest, but considering age, do not feel it is worth pursuing cleaning it Cleared pressure switch port Run tested furnace Gas pressure is 3.5"wc Combustion test numbers are in a healthy range 0ppm carbon monoxide in the ductwork Temperature rise 56⁰ Despite age, furnace is running OK and safe at this time.

Performed heating maintenance on a 2001 Trane 78% efficient single stage natural gas furnace
16x25x1 filter is OK, **will need changed in another month or so**
Pulled and clesned flame sensor
Blower wheel is not the cleanest, but considering age, do not feel it is worth pursuing cleaning it
Cleared pressure switch port
Run tested furnace
Gas pressure is 3.5"wc
Combustion test numbers are in a healthy range
0ppm carbon monoxide in the ductwork
Temperature rise 56⁰
Despite age, furnace is running OK and safe at this time.

Graham M.

Graham M. Job Checkin

Upon arrival inspected unit and found mouse nest in intake and burner compartment. Unit not running due to pressure switch error. Vacuum nest and remains from pipe and burner compartment and test run heating on propane and heat pump, verify proper operation for both functions. Unit is heating great at this time


Brandon P.

Brandon P. Job Checkin

Install replacement OEM Trane variable speed blower motor. Test run operation in fan only and geothermal heating stage 2 for multiple speed test.


Nate G.

Nate G. Job Checkin

Discussed issue over the phone. Everything he's describing is a setting issue with the thermostat. He will play with the settings and call us back Monday if needed.


Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2022 Lennox 2 stage 96% efficient propane furnace Replaced 20x25x1 Filter Pulled and cleaned the flame sensor Checked Condensate lines and ports for blockage Run tested furnace Low fire gas pressure set to 4.5"wc (spec 4.5) Temperature rise 38⁰ (spec 30-60) High fire gas pressure 10"wc (spec 10") Temperature rise 50⁰ (spec 40-70) No signs of water leaks inside the furnace No water leaks from the intake and exhaust vent piping Blower wheel is clean Inducer and blower motors amp draw in spec Furnace is in perfect running order and condition

Performed heating maintenance on a 2022 Lennox 2 stage 96% efficient propane furnace
Replaced 20x25x1 Filter
Pulled and cleaned the flame sensor
Checked Condensate lines and ports for blockage
Run tested furnace
Low fire gas pressure set to 4.5"wc (spec 4.5) 
Temperature rise 38⁰ (spec 30-60)
High fire gas pressure 10"wc (spec 10")
Temperature rise 50⁰ (spec 40-70)
No signs of water leaks inside the furnace
No water leaks from the intake and exhaust vent piping
Blower wheel is clean
Inducer and blower motors amp draw in spec
Furnace is in perfect running order and condition

Nate G.

Nate G. Job Checkin

Performed two system heating maintenance Second floor system: 2018 Goodman 2 stage 96% efficient natural gas furnace 16x25x4 filter is OK Installed intake drain to stop further water damage to the gas valve Corrected water leak issue at the inducer outlet hose clamp Pulled and cleaned flame sensor Condensate trap is clear Run tested furnace High fire was set to 4"wc, adjusted down to specification 3.5" Temperature rise 40⁰ Low fire gas pressure was 2.5"wc, adjusted down to specification 1.7" Temperature rise 35⁰ First floor system 2018 Goodman 2 stage 96% efficient natural gas furnace Installed intake drain coupling, condensation damage to gas valve Pulled and cleaned flame sensor Drain trap clear 16x25x4 filter OK Replaced humidifier water panel High fire set to 3.5" 50⁰ temp rise Low fire set to 1.9"

Performed two system heating maintenance

Second floor system:
2018 Goodman 2 stage 96% efficient natural gas furnace 
16x25x4 filter is OK
Installed intake drain to stop further water damage to the gas valve
Corrected water leak issue at the inducer outlet hose clamp
Pulled and cleaned flame sensor 
Condensate trap is clear
Run tested furnace
High fire was set to 4"wc, adjusted down to specification 3.5"
Temperature rise 40⁰
Low fire gas pressure was 2.5"wc, adjusted down to specification 1.7"
Temperature rise 35⁰

First floor system 
2018 Goodman 2 stage 96% efficient natural gas furnace
Installed intake drain coupling, condensation damage to gas valve
Pulled and cleaned flame sensor
Drain trap clear 
16x25x4 filter OK
Replaced humidifier water panel
High fire set to 3.5" 50⁰ temp rise
Low fire set to 1.9" 
Performed two system heating maintenance

Second floor system:
2018 Goodman 2 stage 96% efficient natural gas furnace 
16x25x4 filter is OK
Installed intake drain to stop further water damage to the gas valve
Corrected water leak issue at the inducer outlet hose clamp
Pulled and cleaned flame sensor 
Condensate trap is clear
Run tested furnace
High fire was set to 4"wc, adjusted down to specification 3.5"
Temperature rise 40⁰
Low fire gas pressure was 2.5"wc, adjusted down to specification 1.7"
Temperature rise 35⁰

First floor system 
2018 Goodman 2 stage 96% efficient natural gas furnace
Installed intake drain coupling, condensation damage to gas valve
Pulled and cleaned flame sensor
Drain trap clear 
16x25x4 filter OK
Replaced humidifier water panel
High fire set to 3.5" 50⁰ temp rise
Low fire set to 1.9"

Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2024 Trane S9X2 two stage 96% efficient natural gas furnace 20x25x1 Filter is new Pulled and cleaned flame sensor Blew out Condensate trap Pulled and cleaned burners High fire gas pressure set to 3.5"wc Temperature rise 61⁰ Low fire gas pressure set to 1.7"wc Temperature rise 53⁰ No water leaks present Furnace is operating perfectly within factory specs at this time

Performed heating maintenance on a 2024 Trane S9X2 two stage 96% efficient natural gas furnace
20x25x1 Filter is new
Pulled and cleaned flame sensor
Blew out Condensate trap
Pulled and cleaned burners
High fire gas pressure set to 3.5"wc Temperature rise 61⁰
Low fire gas pressure set to 1.7"wc Temperature rise 53⁰
No water leaks present
Furnace is operating perfectly within factory specs at this time