725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews
for sunbury, oh

Rated 5.0 out of 5 stars based on 15 customer reviews

Chris was great

Showed up in a timely manner and explained everything very well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service!

Always there when I need them. And always ready to help out when I am in a pinch. Great guys to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service Exceeds Expectations

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Very professional Strive for excellence

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome

5 star plus

  • Overall Experience
  • Quality
  • Price
  • Convenience

5 Stars all the Way!

Excellent customer service and a tremendous knowledge of anything HVAC.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service!

Great job - thanks so much!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome Service!!

Seth and the guy with him were awesome!! They were super friendly and were very thorough in their explanation of what they were gonna do and when they were done, explained how to use the new humidifier with great detail!! The price was great too!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Preventive maintenance inspection

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

Seth was professional. Did excellent propane to gas conversions on three furnaces.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Alway pleasant and efficient

  • Overall Experience
  • Quality
  • Price
  • Convenience

Took lots of time to explain things, thank you!

I really appreciate Seth taking the time to explain things to me in a way I could understand. Very friendly and knowledgeable!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Replacement System-Furnace & Heat Pump

  • Overall Experience
  • Quality
  • Price
  • Convenience

New roof top furnace

They did a great job! Helpful and professional. Neat work and on time.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome Geothermal service

Quick, efficient and friendly service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for sunbury, oh

Brandon P.

Brandon P. Job Checkin

Install replacement OEM Trane variable speed blower motor. Test run operation in fan only and geothermal heating stage 2 for multiple speed test.


Nate G.

Nate G. Job Checkin

Discussed issue over the phone. Everything he's describing is a setting issue with the thermostat. He will play with the settings and call us back Monday if needed.


Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2022 Lennox 2 stage 96% efficient propane furnace Replaced 20x25x1 Filter Pulled and cleaned the flame sensor Checked Condensate lines and ports for blockage Run tested furnace Low fire gas pressure set to 4.5"wc (spec 4.5) Temperature rise 38⁰ (spec 30-60) High fire gas pressure 10"wc (spec 10") Temperature rise 50⁰ (spec 40-70) No signs of water leaks inside the furnace No water leaks from the intake and exhaust vent piping Blower wheel is clean Inducer and blower motors amp draw in spec Furnace is in perfect running order and condition

Performed heating maintenance on a 2022 Lennox 2 stage 96% efficient propane furnace
Replaced 20x25x1 Filter
Pulled and cleaned the flame sensor
Checked Condensate lines and ports for blockage
Run tested furnace
Low fire gas pressure set to 4.5"wc (spec 4.5) 
Temperature rise 38⁰ (spec 30-60)
High fire gas pressure 10"wc (spec 10")
Temperature rise 50⁰ (spec 40-70)
No signs of water leaks inside the furnace
No water leaks from the intake and exhaust vent piping
Blower wheel is clean
Inducer and blower motors amp draw in spec
Furnace is in perfect running order and condition

Nate G.

Nate G. Job Checkin

Performed two system heating maintenance Second floor system: 2018 Goodman 2 stage 96% efficient natural gas furnace 16x25x4 filter is OK Installed intake drain to stop further water damage to the gas valve Corrected water leak issue at the inducer outlet hose clamp Pulled and cleaned flame sensor Condensate trap is clear Run tested furnace High fire was set to 4"wc, adjusted down to specification 3.5" Temperature rise 40⁰ Low fire gas pressure was 2.5"wc, adjusted down to specification 1.7" Temperature rise 35⁰ First floor system 2018 Goodman 2 stage 96% efficient natural gas furnace Installed intake drain coupling, condensation damage to gas valve Pulled and cleaned flame sensor Drain trap clear 16x25x4 filter OK Replaced humidifier water panel High fire set to 3.5" 50⁰ temp rise Low fire set to 1.9"

Performed two system heating maintenance

Second floor system:
2018 Goodman 2 stage 96% efficient natural gas furnace 
16x25x4 filter is OK
Installed intake drain to stop further water damage to the gas valve
Corrected water leak issue at the inducer outlet hose clamp
Pulled and cleaned flame sensor 
Condensate trap is clear
Run tested furnace
High fire was set to 4"wc, adjusted down to specification 3.5"
Temperature rise 40⁰
Low fire gas pressure was 2.5"wc, adjusted down to specification 1.7"
Temperature rise 35⁰

First floor system 
2018 Goodman 2 stage 96% efficient natural gas furnace
Installed intake drain coupling, condensation damage to gas valve
Pulled and cleaned flame sensor
Drain trap clear 
16x25x4 filter OK
Replaced humidifier water panel
High fire set to 3.5" 50⁰ temp rise
Low fire set to 1.9" 
Performed two system heating maintenance

Second floor system:
2018 Goodman 2 stage 96% efficient natural gas furnace 
16x25x4 filter is OK
Installed intake drain to stop further water damage to the gas valve
Corrected water leak issue at the inducer outlet hose clamp
Pulled and cleaned flame sensor 
Condensate trap is clear
Run tested furnace
High fire was set to 4"wc, adjusted down to specification 3.5"
Temperature rise 40⁰
Low fire gas pressure was 2.5"wc, adjusted down to specification 1.7"
Temperature rise 35⁰

First floor system 
2018 Goodman 2 stage 96% efficient natural gas furnace
Installed intake drain coupling, condensation damage to gas valve
Pulled and cleaned flame sensor
Drain trap clear 
16x25x4 filter OK
Replaced humidifier water panel
High fire set to 3.5" 50⁰ temp rise
Low fire set to 1.9"

Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2024 Trane S9X2 two stage 96% efficient natural gas furnace 20x25x1 Filter is new Pulled and cleaned flame sensor Blew out Condensate trap Pulled and cleaned burners High fire gas pressure set to 3.5"wc Temperature rise 61⁰ Low fire gas pressure set to 1.7"wc Temperature rise 53⁰ No water leaks present Furnace is operating perfectly within factory specs at this time

Performed heating maintenance on a 2024 Trane S9X2 two stage 96% efficient natural gas furnace
20x25x1 Filter is new
Pulled and cleaned flame sensor
Blew out Condensate trap
Pulled and cleaned burners
High fire gas pressure set to 3.5"wc Temperature rise 61⁰
Low fire gas pressure set to 1.7"wc Temperature rise 53⁰
No water leaks present
Furnace is operating perfectly within factory specs at this time

Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2024 Daikin 97% efficient modulating natural gas furnace Replaced aprilaire 210 filter with one from truck stock Pulled and cleaned flame sensor Condensate trap is clean Blower is clean Run tested furnace Low fire Temperature rise 30⁰ (spec 20-50) High fire Temperature rise 46⁰ (spec 25-55) No stored faults other than thermostat reboots (software updates and power resets cause these) Furnace is operating perfectly within manufacturer's specifications at this time No concerns found on today's visit


Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2017 Goodman single stage 96% efficient natural gas furnace Corrected some drain tubing issues from new construction install inside the furnace (tubing cut incorrect length and kinked) Corrected hose clamps issues on the inducer outlet elbow that had signs of water leakage 20x25x1 Filter is still good, left the one we provide with the gold maintenance plan on top of the filter rack Blower wheel is clean Blower capacitor measured 19.8mfd Pulled condensate trap and flushed with water (had lots of debris buildup) Pulled flame sensor and cleaned with steel wool Run tested furnace Burner gas Manifold pressure set to 3.5"wc Temperature rise is a steady 50⁰ Furnace is in good shape and operating within manufacturer's specifications at this time

Performed heating maintenance on a 2017 Goodman single stage 96% efficient natural gas furnace
Corrected some drain tubing issues from new construction install inside the furnace (tubing cut incorrect length and kinked)
Corrected hose clamps issues on the inducer outlet elbow that had signs of water leakage
20x25x1 Filter is still good, left the one we provide with the gold maintenance plan on top of the filter rack
Blower wheel is clean
Blower capacitor measured 19.8mfd
Pulled condensate trap and flushed with water (had lots of debris buildup)
Pulled flame sensor and cleaned with steel wool 
Run tested furnace
Burner gas Manifold pressure set to 3.5"wc
Temperature rise is a steady 50⁰
Furnace is in good shape and operating within manufacturer's specifications at this time

Brandon P.

Brandon P. Job Checkin

Initial test run of furnace shows that when there is a call for heat, the inducer motor kicks on, after a few seconds, the igniter glows, but only for a second before the control board "resets." Igniter turns off and inducer motor shuts off for a few seconds before coming on again. Initialy thought it was a bad igniter, so tested a new igniter with no change in sequence of operation. During initial testing also noticed that the gas valve did not seem to come on. Tested for 24v at gas valve during start up. During test with gas valve unplugged, there was 24v present when gas valve should be opened. Noticed that with gas valve unplugged, the control board did not "reset," but showed a code for no flame present. Tested wiring with new gas valve in hand. During fire off, the new gas valve received the 24v call and opened as it should. This confirms the gas valve has an internal electrical malfunction and must be replaced. Replaced faulty gas valve with new gas valve. Sealed all joints that

Initial test run of furnace shows that when there is a call for heat, the inducer motor kicks on, after a few seconds, the igniter glows, but only for a second before the control board "resets." Igniter turns off and inducer motor shuts off for a few seconds before coming on again. Initialy thought it was a bad igniter, so tested a new igniter with no change in sequence of operation. During initial testing also noticed that the gas valve did not seem to come on. Tested for 24v at gas valve during start up. During test with gas valve unplugged, there was 24v present when gas valve should be opened. Noticed that with gas valve unplugged, the control board did not "reset," but showed a code for no flame present. Tested wiring with new gas valve in hand. During fire off, the new gas valve received the 24v call and opened as it should. This confirms the gas valve has an internal electrical malfunction and must be replaced. Replaced faulty gas valve with new gas valve. Sealed all joints that

Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2021 Bryant single stage 95% efficient natural gas furnace Replaced 16x25x4 filter Pulled flame sensor and cleaned with steel wool Condensate trap is clear Adjusted blower speed up one speed tap Set gas pressure to 3.5"wc Temperature rise is a steady 56⁰ Blower is in OK condition Amp draw of blower and inducer motors in spec No concerns found with intake and exhaust pipes Condensate lines show no signs of water leakage Furnace is in good shape and operating within factory specs at this time


Brandon P.

Brandon P. Job Checkin

Depressurize loop. Replace leaking 1-1/4in elbow in basement and new P/T ports on geo elbows Add undiluted glycol to system and flush/blend existing fluid to 15 deg freeze point and repressurize loop. Disclaimer Westin Air will repair the identified leak in the geothermal loop field. This service is limited to this specified repair, and we are not responsible for undetected leaks, pre-existing issues, or the overall condition of the system.


Nate G.

Nate G. Job Checkin

Performed heating maintenance on a Bryant single stage 80% efficient natural gas furnace 16x25x1 filter is in good shape, left the one we provide with the gold plan with the furnace Pulled and cleaned the flame sensor rod Blower wheel is clean Burners are clean Exhaust flue pipe in good shape Run tested furnace Gas pressure set to 3.2"wc Increased heating blower speed up one speed tap Temperature rise is 64⁰ No concerns found on today's visit


Nate G.

Nate G. Job Checkin

Replaced inducer under factory parts warranty


Graham M.

Graham M. Job Checkin

Remove and replace capacitor and test run system. Verify proper operation. Clean dusty burner compartment and flame sensor. No concerns as of now


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 16x25x1 clean Clean flame sensor Ohm test igniter: 62.6 Inspect wiring for loose connections and/or hot spots - none found Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 3.21 Check amp draw on inducer motor:1.32 Check delta T - 53° Furnace is in optimal running conditions


Jason D.

Jason D. Job Checkin

SOLD: 10/09/2025 9:42:50 PM - Option 2 Install New Daikin FIT HVAC System *Two Stage - Variable Speed Furnace: Model #: DR97MC0603BNA Serial #: 2505249733 60,000 BTU's - 97% AFUE *Variable Speed Air Conditioner: Model #: DC6VSS3010A Serial #: 2506339162 2.5 Ton - 17.2 SEER2 *Matching Indoor Coil: Model #: CAPEA3022B3A Serial #: 2412413782 *Daikin One+ Thermostat: DTST-TOU-A Serial #: EA2504609882 Installation: * Additional Services - New PVC furnace vents. Level 2 * Reconnect to existing gas line and electric * Transition to existing supply and return ductwork * Start up and commission new system * Aprilaire 1210 (20x25) Media Air Cleaner Warranty: 12 Year Daikin manufacturers Parts Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed) Daikin manufacturers Lifetime Heat Exchanger Warranty (Annual maintenance must be performed)


SOLD: 10/09/2025 9:42:50 PM - Option 2

Install New Daikin FIT HVAC System
*Two Stage - Variable Speed Furnace:
Model #: DR97MC0603BNA
Serial #: 2505249733
60,000 BTU's - 97% AFUE
*Variable Speed Air Conditioner:
Model #: DC6VSS3010A
Serial #: 2506339162
2.5 Ton - 17.2 SEER2
*Matching Indoor Coil:
Model #: CAPEA3022B3A
Serial #: 2412413782
*Daikin One+ Thermostat: DTST-TOU-A
Serial #: EA2504609882
 
Installation:
* Additional Services - New PVC furnace vents. Level 2
* Reconnect to existing gas line and electric
* Transition to existing supply and return ductwork
* Start up and commission new system
* Aprilaire 1210 (20x25) Media Air Cleaner
 
Warranty:
12 Year Daikin manufacturers Parts Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)
Daikin manufacturers Lifetime Heat Exchanger Warranty (Annual maintenance must be performed)

SOLD: 10/09/2025 9:42:50 PM - Option 2

Install New Daikin FIT HVAC System
*Two Stage - Variable Speed Furnace:
Model #: DR97MC0603BNA
Serial #: 2505249733
60,000 BTU's - 97% AFUE
*Variable Speed Air Conditioner:
Model #: DC6VSS3010A
Serial #: 2506339162
2.5 Ton - 17.2 SEER2
*Matching Indoor Coil:
Model #: CAPEA3022B3A
Serial #: 2412413782
*Daikin One+ Thermostat: DTST-TOU-A
Serial #: EA2504609882
 
Installation:
* Additional Services - New PVC furnace vents. Level 2
* Reconnect to existing gas line and electric
* Transition to existing supply and return ductwork
* Start up and commission new system
* Aprilaire 1210 (20x25) Media Air Cleaner
 
Warranty:
12 Year Daikin manufacturers Parts Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)
Daikin manufacturers Lifetime Heat Exchanger Warranty (Annual maintenance must be performed)