725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews
for sunbury, oh

Rated 5.0 out of 5 stars based on 15 customer reviews

Chris was great

Showed up in a timely manner and explained everything very well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service!

Always there when I need them. And always ready to help out when I am in a pinch. Great guys to work with.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service Exceeds Expectations

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

Very professional Strive for excellence

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome

5 star plus

  • Overall Experience
  • Quality
  • Price
  • Convenience

5 Stars all the Way!

Excellent customer service and a tremendous knowledge of anything HVAC.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service!

Great job - thanks so much!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome Service!!

Seth and the guy with him were awesome!! They were super friendly and were very thorough in their explanation of what they were gonna do and when they were done, explained how to use the new humidifier with great detail!! The price was great too!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Preventive maintenance inspection

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

Seth was professional. Did excellent propane to gas conversions on three furnaces.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Alway pleasant and efficient

  • Overall Experience
  • Quality
  • Price
  • Convenience

Took lots of time to explain things, thank you!

I really appreciate Seth taking the time to explain things to me in a way I could understand. Very friendly and knowledgeable!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Replacement System-Furnace & Heat Pump

  • Overall Experience
  • Quality
  • Price
  • Convenience

New roof top furnace

They did a great job! Helpful and professional. Neat work and on time.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Awesome Geothermal service

Quick, efficient and friendly service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for sunbury, oh

Brandon P.

Brandon P. Job Checkin

Newer filter installed backwards has flattened out and is causing a major air flow blockage. Intialctest run in heating stage 2 showed discharge pressures at 500psi. Installed new air filter and test ran in second stage. Current operation discharge pressures at 350psi and is within spec. Test run operation of humidifier with no issues found.


Brandon P.

Brandon P. Job Checkin

Service warranty Missed recirculation issue during last two diagnostics. Replace current flue termination with new goose neck to prevent recirculation and ice buildup in the intake pipe. No diagnostic charge, bill today is only for parts and labor used for repairs.

Service warranty
Missed recirculation issue during last two diagnostics. Replace current flue termination with new goose neck to prevent recirculation and ice buildup in the intake pipe. No diagnostic charge, bill today is only for parts and labor used for repairs. Service warranty
Missed recirculation issue during last two diagnostics. Replace current flue termination with new goose neck to prevent recirculation and ice buildup in the intake pipe. No diagnostic charge, bill today is only for parts and labor used for repairs.

Nate G.

Nate G. Job Checkin

Outdoor temperature thermistor 'may' be reading too low, but this will bring the system into propane only at a warmer outdoor temp than the 30⁰ setting The fact the house got cold indicates the propane furnace stopped working The stored faults were all a 2 code "# of retries exceeded" Cleaned flame sensor Found burner ignition not fully reliable crossover Pulled and cleaned burners Intake and exhaust might have been covered with snow on the roof, too Furnace is operating normally at this time Invoice is payable online


Nate G.

Nate G. Job Checkin

Resettable fuse failed Jumped past it to test operation Combustion fan (inducer motor) failed Inspected heat exchanger, giant hole in it Due to condition of the system, we recommend unit replacement

Resettable fuse failed
Jumped past it to test operation
Combustion fan (inducer motor) failed 
Inspected heat exchanger, giant hole in it
Due to condition of the system, we recommend unit replacement Resettable fuse failed
Jumped past it to test operation
Combustion fan (inducer motor) failed 
Inspected heat exchanger, giant hole in it
Due to condition of the system, we recommend unit replacement

Nate G.

Nate G. Job Checkin

Service recall: no diagnostic charge Pressure switch not closing again Tubing plugged with ice Replaced tubing with a thicker tube and wrapped it in insulation Sealed exhaust outlet of leakage inside the burner cabinet Added a smoke stack exhaust pipe to get the moist exhaust gasses over the top of the unit Feared exhaust was hitting the wall in front of the exhaust outlet and recirculating back into the burner compartment Cost for today is additional material used

Service recall: no diagnostic charge 
Pressure switch not closing again 
Tubing plugged with ice
Replaced tubing with a thicker tube and wrapped it in insulation
Sealed exhaust outlet of leakage inside the burner cabinet
Added a smoke stack exhaust pipe to get the moist exhaust gasses over the top of the unit
Feared exhaust was hitting the wall in front of the exhaust outlet and recirculating back into the burner compartment 
Cost for today is additional material used Service recall: no diagnostic charge 
Pressure switch not closing again 
Tubing plugged with ice
Replaced tubing with a thicker tube and wrapped it in insulation
Sealed exhaust outlet of leakage inside the burner cabinet
Added a smoke stack exhaust pipe to get the moist exhaust gasses over the top of the unit
Feared exhaust was hitting the wall in front of the exhaust outlet and recirculating back into the burner compartment 
Cost for today is additional material used

Nate G.

Nate G. Job Checkin

Replacement labor warranty House was ar 68⁰ with a 72⁰ set point Droop settings were 0.5⁰ apart from each other, so auxiliary should be 1.5⁰ from Setpoint Found auxiliary heat wiring not going through the energy monitoring CT Put those through After that, energy monitoring only showed 20A when all 3 strips were pulling 20A each Shut power down Swapped L1 and L2 for the 10kw heat bank Energy monitoring now showing all 60A After all of this, system is acting normally


Brandon P.

Brandon P. Job Checkin

Service warranty During control board replacement, wire for gas furnace heating call was not installed properly and making very poor connection leading to intermitten heating. Fixed wiring and test ran operstion from thermostat.


Brandon P.

Brandon P. Job Checkin

Current controller settings were causing left vanes to point more downwards than right vanes. Test3d several operstion settings and confirmed proper vanes control. Controller is now setup for complete infrared eye control and vanes may look different while system is operating. No issues found or suspected


Nate G.

Nate G. Job Checkin

Furnace had stored ignition failure codes Flame sensor signal was 6.0 micro amps before cleaning Signal rose to 6.7 after cleaning Checked gas pressure, standing inlet was 10.8" Homeowner adjusted regulator to 13" with the furnace operating Manifold pressure 11" Suspect low gas pressure from potentially frozen regulator No issues found with the furnace itself Exhaust pipe is clear


Nate G.

Nate G. Job Checkin

Pressure switch stuck open Replaced pressure switch System heating normally at this time.


Nate G.

Nate G. Job Checkin

Replace water fitting on humidifier water supply - water line cpvc 3/4. Reconfigure furnace wiring for humidifier to be controlled with heat. Install 2” drain trap on and install T fitting for drain on 3/4 pvc drain.

Replace water fitting on humidifier water supply - water line cpvc 3/4. Reconfigure furnace wiring for humidifier to be controlled with heat. Install 2” drain trap on and install T fitting for drain on 3/4 pvc drain. Replace water fitting on humidifier water supply - water line cpvc 3/4. Reconfigure furnace wiring for humidifier to be controlled with heat. Install 2” drain trap on and install T fitting for drain on 3/4 pvc drain.

Graham M.

Graham M. Job Checkin

Replace pump that was grinding for hot water generator on geo Ordered through Waterfurnace PO# SM4693Blue


Nate G.

Nate G. Job Checkin

Furnace blower door switch failing. Bypassed door switch Performed heating maintenance Cleaned flame sensor Low fire gas pressure 1.5" High fire gas pressure 3.2" Furnace tripping high limit in high fire Increased airflow to maximum It still trips the high limit Recommend low MERV rating filters, the flat panel fiberglass filters will mitigate this overheating issue Wired thermostat for two stage heating control, so hopefully it won't utilize high fire very much at all.


Brandon P.

Brandon P. Job Checkin

System has a failed 45uf capacitor for compressor operation. Replace failed capacitor and test run in heating mode. No other issues found or suspected during testing. Geothermal maintenence plan includes two visits for maintenence. Once in the spring for checking geothermal operation, and once in the fall for checking electric heat strips operation.

System has a failed 45uf capacitor for compressor operation. Replace failed capacitor and test run in heating mode. No other issues found or suspected during testing. 
Geothermal maintenence plan includes two visits for maintenence. Once in the spring for checking geothermal operation, and once in the fall for checking electric heat strips operation.

Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 20x25x4 new today Clean flame sensor Inspect burners - clean Ohm test igniter: 54.2 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: panel ok - water supply very concerning (CPVC should not have a saddle valve on it) photo submitted. Wiring also improper allowing humidifier operation without gas heat or fan. Turned off currently. Inspect exhaust flu - no concerns with exhaust. No drain on intake allowing excess moisture into burner compartment. Set thermostat for heat Check amp draw on blower motor: 3.26 Check amp draw on inducer motor:0.62 Check delta T - 53° Furnace is in optimal running conditions

Gas heating preventative maintenance performed
Check filter - 20x25x4 new today 
Clean flame sensor
Inspect burners - clean
Ohm test igniter: 54.2
Inspect wiring for loose connections and/or hot spots - none found
Check humidifier pad: panel ok - water supply very concerning (CPVC should not have a saddle valve on it) photo submitted. Wiring also improper allowing humidifier operation without gas heat or fan. Turned off currently. 
Inspect exhaust flu - no concerns with exhaust. No drain on intake allowing excess moisture into burner compartment. 
Set thermostat for heat
Check amp draw on blower motor: 3.26
Check amp draw on inducer motor:0.62
Check delta T -  53°
Furnace is in optimal running conditions Gas heating preventative maintenance performed
Check filter - 20x25x4 new today 
Clean flame sensor
Inspect burners - clean
Ohm test igniter: 54.2
Inspect wiring for loose connections and/or hot spots - none found
Check humidifier pad: panel ok - water supply very concerning (CPVC should not have a saddle valve on it) photo submitted. Wiring also improper allowing humidifier operation without gas heat or fan. Turned off currently. 
Inspect exhaust flu - no concerns with exhaust. No drain on intake allowing excess moisture into burner compartment. 
Set thermostat for heat
Check amp draw on blower motor: 3.26
Check amp draw on inducer motor:0.62
Check delta T -  53°
Furnace is in optimal running conditions