The generator needs a new oil pressure switch. Found generator in low oil pressure fault, the second time it faulted out in two months. IF APPROVED - THE TECH WILL NEED A MECHANICAL OIL PRESSURE GAUGE. The tech needs to install their mechanical gauge and make sure the oil pump is working correctly then they can take their gauge out and install the new oil pressure switch.