#1 service. Generator is working properly.
Annual service. Generator is working properly. Replaced battery during service.
LOAD SHED ON MAIN HVAC UNIT FAILED AND WAS REPLACED. AFTER HOURS CALL OUT.
#1 service. Generator is working properly.
#1 service. Generator is working properly.
#1 service. Generator is working properly. Replace oil again on next service due to high moisture content in engine.
#1/4 Service. Recommend battery replacement due to age. No further issues.
Upon arrival generator was faulted for High Engine Temp. Tried to bypass the sensor but generator still faulted. While diagnosing the High Engine Temp alarm I noticed the generator controller displayed Low Battery. Battery was tested and even though the date is 2017, battery tested good. Customer declined new battery. It was determined the controller was faulty causing the Temp Alarm and the charging issue. Once controller was replaced we simulated an outage. Generator is now operating properly.
JB49806214 Annual service. Fuel level 87%-457 gallons. July 2022 dated batteries. Fuel sample taken
JB48919820 Q1 service. Fuel level 90%(473 gallon). 272.0 hrs. 6/22 dated batteries.
#2 service. Generator is working properly.
#2 service. Generator is working properly.