AUXILIARY SHUTDOWN ALARM WOULD NOT CLEAR. REPLACED SWITCH AND WAS ABLE TO CLEAR ALARM. WARRANTY WAS FILED.
Fault 1505, 12.9 hours. #3004745587. Updated firmware. Generator starter not engaging. Replaced battery. Generator still wouldnt crank. 12 volts to solenoid during cranking cycle. Replaced starter and tested. Generator is now working properly.
#1 service. Replaced battery and air filter during service. Received a check for PMA and parts for $641.37. Check #2569.
#2 service. Replaced battery and battery charger due to a faulty charger. Generator is now working properly.
#2 service. Generator is working properly.
#1 service. Generator is working properly. Replaced air filter during service.
#1 Service. Adjusted valves. Replaced battery and air filter. Updated firmware from 1.12 to 1.21. No issues.
Replaced avr and tested. Generator is now working properly.
Startup complete. Fuel pressures under load, 11”. Exerciser set of Monday at noon. See attached pictures.
JB49803673 Annual Service. Fuel level 86%-215 Gallons. July 2022 dated batteries. Fuel sample taken.
JB49777284 Wired portable spot cooler into electrical panel.
This is supposed to be a startup, not a #1. We are not starting the unit up due to gas bottle being strapped to the electrical pole.