W119843 Called out for site without power. FOund tree had taken down utility line to building. Utility company showed up and they repaired it
Start up complete. Gas pressure 12” static, 11.5” under load. Exerciser set for 11:00 Monday.
#2 service. Oil pressure switch was leaking. Replaced oil pressure switch and tested. Generator is now working properly.
Replaced motor and tested. Generator is working properly.
#1 service. Generator is working properly. Generator needs to be moved away from A/C. Our install. 30' of whip, 2 3/4X3" nipples. One 3/4 ninety.
#1 service. Generator is working properly.
#1 service. Generator is working properly.
Generator will not start and stay running. Propane tank is empty. Tank gauge reading inaccurate. Informed customer to have propane company fill tank and let us know if it starts and runs properly.
No rotation warning. 1505. Replaced starter and tested. Generator is working properly. Generac covered labor travel and part. Control #304721662
#1 service. Generator is working properly.
Replaced starter due to multiple RPM Sense Loss alarms. Generator is out of parts and labor warranty as of 6/9/2022. Customer will be responsible for parts and labor.