#2 service. generator is working properly
Found two fuses blown in the master switch and what seems to have been water getting into the switch. Sealed the top of both switches and tested. Generator is working properly. Installation error, loose flex and pipe connections. Not our install.
#1 service. Replaced battery and air filter during. Generator is working properly.
Wiring harness had shorted out at the plug where it connects to the smart a/c module. Had to replace both. Tested unit. Everything is working properly. 3004715117 transfer switch. 21.8 hours. Harness 10000005872, Smart a/c module 10000004183.
Generator had a few codes in history. Main code being low fuel pressure. Natural gas regulator atmospheric vent was completely clogged. I removed the brass vent and cleaned debris and bb out of vent path. Once vent was cleared I inspected fuel pressure, 14” static, 12” running. Gas work is not correct per Generac installation guidelines. See attached pictures. Could not perform a test transfer due to site being critical infrastructure. Generator seems to be starting and running as it should. To guarantee no further issues gas work should be redone to Generac’s guidelines.
#1 service. Generator is working properly.
Startup complete. See attached pictures. Fuel pressure under load 11”. Exerciser set for Wednesday at noon.
#1 service. Generator is working properly. Replaced load shed module during service. SMM only.
JB49828522 Annual Service. January 2022 battery. Fuel level 85%-170 gallons.
JB49031807 TOPPED OFF FUEL LEVEL TO 90% (180 GALLONS)
JB49031807 - W102051 Q1 SERVICE. 544.6 HRS. 1/22 DATED GROUP 24 BATTERY. FUEL LEVEL 90% (180 GALLONS)
#2 Service. Updated firmware from 1.12 to 1.15. No issues.
#1 service. Generator is working properly.