Rich A.

Rich A. Job Checkin

serial#3004715117 claim#305050314


Rodney N.

Rodney N. Job Checkin

#2 service. generator is working properly


Rodney N.

Rodney N. Job Checkin

Found two fuses blown in the master switch and what seems to have been water getting into the switch. Sealed the top of both switches and tested. Generator is working properly. Installation error, loose flex and pipe connections. Not our install.


Rodney N.

Rodney N. Job Checkin

#1 service. Replaced battery and air filter during. Generator is working properly.


Rodney N.

Rodney N. Job Checkin

Wiring harness had shorted out at the plug where it connects to the smart a/c module. Had to replace both. Tested unit. Everything is working properly. 3004715117 transfer switch. 21.8 hours. Harness 10000005872, Smart a/c module 10000004183.


Tyler L.

Tyler L. Job Checkin

JB50949435-W100645 ATS MAJOR COMPLETE


Tyler L.

Tyler L. Job Checkin

Generator had a few codes in history. Main code being low fuel pressure. Natural gas regulator atmospheric vent was completely clogged. I removed the brass vent and cleaned debris and bb out of vent path. Once vent was cleared I inspected fuel pressure, 14” static, 12” running. Gas work is not correct per Generac installation guidelines. See attached pictures. Could not perform a test transfer due to site being critical infrastructure. Generator seems to be starting and running as it should. To guarantee no further issues gas work should be redone to Generac’s guidelines.


Rodney N.

Rodney N. Job Checkin

#1 service. Generator is working properly.


Tyler L.

Tyler L. Job Checkin

Startup complete. See attached pictures. Fuel pressure under load 11”. Exerciser set for Wednesday at noon.


Rodney N.

Rodney N. Job Checkin

#1 service. Generator is working properly. Replaced load shed module during service. SMM only.


Tyler L.

Tyler L. Job Checkin

JB49828522 Annual Service. January 2022 battery. Fuel level 85%-170 gallons.


Tyler L.

Tyler L. Job Checkin

JB49031807 TOPPED OFF FUEL LEVEL TO 90% (180 GALLONS)


Tyler L.

Tyler L. Job Checkin

JB49031807 - W102051 Q1 SERVICE. 544.6 HRS. 1/22 DATED GROUP 24 BATTERY. FUEL LEVEL 90% (180 GALLONS)


Tyler L.

Tyler L. Job Checkin

#2 Service. Updated firmware from 1.12 to 1.15. No issues.


Rodney N.

Rodney N. Job Checkin

#1 service. Generator is working properly.