Rodney N.

Rodney N. Job Checkin

#2 service. Generator is working properly.


Tyler L.

Tyler L. Job Checkin

JB51642423 - W12115 DELIVERED COMBO HVAC TRAILER TO SPRINGFIELD FROM THE SAVANNAH HE. WAITED ON SITE FOR A 5 TON PORTABLE HVAC TO BE DELIVERED. WIRED 5 TON TO OUTSIDE DISCONNECT. LEFT COMBO TRAILER ON SITE AS A BACKUP.


Tyler L.

Tyler L. Job Checkin

JB51608105 - W120876 DELIVERED COMBO TRAILER TO SPRINGFIELD. JOHNSON CONTROLS DETERMINED THEY COULD NOT USE IT. WAITED ON SITE FOR A SPOT COOLER TO BE DELIVERED. ONCE DELIVERED I WIRED IT INTO AN INTERIOR ELECTRICAL PANEL. WHEN LEAVING SITE I DELIVERED THE COMBO TRAILER BACK TO THE SAVANNAH HE.


Rodney N.

Rodney N. Job Checkin

#1 service with a two hour load test.


Tyler L.

Tyler L. Job Checkin

AC Major demand completed


Tyler L.

Tyler L. Job Checkin

JB50374570-W100601 ATS-W102213 AC SM002022242 Ats and AC Demand complete


Tyler L.

Tyler L. Job Checkin

JB50044510 Installed new generator fuel gauge and networking equipment. Quoted job per Chad.


Tyler L.

Tyler L. Job Checkin

JB49813661 Annual service. September 2022 dated battery. Fuel level 90% - 180 gallons.


Tyler L.

Tyler L. Job Checkin

JB49813661 Inspected fuel level. Level was 3.5 inches from tank. Echo gauge was reporting 60%. Kohler controller was reporting 84%. I added 22 gallons to bring fuel level up to 2 inches from top of tank. Echo gauge reporting improperly. Fuel level on controlled is now reporting 90%.


Tyler L.

Tyler L. Job Checkin

JB49432685 - W106168 Installed 60 amp breaker in electrical panel an hooked up spot cooler. Had to cut hole in exterior sheet metal panel to bring exhaust duct through.


Tyler L.

Tyler L. Job Checkin

# 1 SERVICE. REPLACED BATTERY DUE TO AGE. DURING SERVICE IT WAS NOTICED THE ENGINE IS STARTING TO SMOKE. COULD BE DUE TO RINGS OR VALVE STEM SEALS. NEED TO MONITOR OIL LEVEL AND GENERATOR FOR ISSUES RELATED TO BURNING OIL.


Tyler L.

Tyler L. Job Checkin

#1 service. Replaced battery due to age. No issues.


Tyler L.

Tyler L. Job Checkin

JB48942254 Q1 service. 417.9 hrs. Fuel level 90% (180 gallons). 8/22 battery.


Tyler L.

Tyler L. Job Checkin

JB # 47384202 ASSET AUDIT. THIS IS NOT A QUARTERLY INSPECTION. AUDIT COMPLETE.


Tyler L.

Tyler L. Job Checkin

#2 SERVICE. NO ISSUES.