Rodney N.

Rodney N. Job Checkin

#1 service. Generator is blowing 15 amp fuse when power outage start up only. Tightened all grounds. Then a storm came.


Rodney N.

Rodney N. Job Checkin

#1 service. Generator is working properly.


Rodney N.

Rodney N. Job Checkin

#2 service> Generator is working properly.


Rodney N.

Rodney N. Job Checkin

#1 service. Replaced battery and air filter. Generator is working properly.


Rodney N.

Rodney N. Job Checkin

Generator breaker was tripped due to odd voltage from utilities. Turned breaker back on and tested. Generator is now working properly.


Tyler L.

Tyler L. Job Checkin

#2 Service. Installed new battery due to age. No issues.


Tyler L.

Tyler L. Job Checkin

#2 Service. Updated firmware from 1.38 to 1.51. No issues.


Tyler L.

Tyler L. Job Checkin

#1 Service. Generator was faulted for 2602 Ignition Fault. Same as last repair/visit. See attached pictures of actual diagnostics. Inspected the magpickup. Output voltage way below spec. Removed, cleaned, reinstalled and adjusted output voltage to spec. Inspected cam sensor. Resistance is high but within spec. Fault likely due to low output voltage from magpickup. Updated firmware from 1.48 to 1.51. No further issues.


Tyler L.

Tyler L. Job Checkin

#2 Service. No issues.


Tyler L.

Tyler L. Job Checkin

#1 Service. Adjusted valves. Updated firmware from 1.15 to 1.17. No issues.


Tyler L.

Tyler L. Job Checkin

#2 Service. Need to replace battery due to age. No other issues.


Tyler L.

Tyler L. Job Checkin

Filed warranty for oil pressure sensor to cover trip charge for overcrank. Regulator has been changed and customer should not have any further issues.


Tyler L.

Tyler L. Job Checkin

#1 Service. Updated firmware from 1.15 to 1.16. Red light on for Overcrank. Explained to customer that the regulator used is going to cause Overcrank issues. See attached pictures. Customer will reach out to gas company to remedy faulty regulator. No further issues.


Rodney N.

Rodney N. Job Checkin

#2 service. Generator is working properly. Garage window on the left hand side of the generator is a closed window.


Rodney N.

Rodney N. Job Checkin

#2 service. Generator is working properly.