JB50163573 We were asked to start the generators using the system controller and make sure they sink up properly without faulting. Gen 2 will not sync and close to the buss. Frequency is low at 59.3hz. Keith is going to make adjustments and necessary repairs.
JB49924235 Annual Service-Gen 2. 78.7 hrs. February 2022 battery. Fuel level 87%-462 gallons. Fuel sample taken.
JB49924235 Annual Service-Gen 1. 78.7 hrs. February 2022 battery. Fuel level 85%-452 gallons. Fuel sample taken.
JB49702697 - W107660 GENERATOR 1 HAD RUPTURE BASIN ALARM. BASED ON TESTING SENSOR WAS FOUND TO BE FAULTY. WILL NEED TO ORDER SENSOR AND REUTRN TO MAKE REPAIRS.
JB48975269 TOPPED OF FUEL LEVEL TO 90%(478 GALONS)
JB48975269 TOPPED OFF FUEL LEVEL TO 90%(478 GALLONS)
JB48975269 Q1 SERVICE. 2/22 BATTERY. 73.4 HRS. FUEL LEVEL 90% (478 GALLONS).
JB48975269 Q1 SERVICE. 2/22 BATTERY. 51.1 HRS. 90% FUEL LEVEL (478 GALLONS).
on 09/27/2022 technician found oil pressure switch bad. Return on 09/28/2022 to repair 9/28/22 JB # 46412110 Replaced sensor. Generator is now displaying oil pressure.
JB # 46058548 Eaton Power Meter had a blown fuse on A Phase. Replaced fuse, meter is reporting correctly.