GENERATOR NOT EXERCISING PROPERLY - FOUND CONTROLLER WOULD NOT STOP TRYING TO CONNECT TO WIFI, CAUSING NOT TO HAVE CORRECT DAY OR TIME - TRIED HARD RESET - RESET EXERCISE TIME & DAY - FAILED TO EXERCISE - REPLACED CONTROLLER - SET UP PROPER DAY/TIME FOR EXERCISE - TESTED FOR PROPER OPERTION - WORKING NORMALLY AT THIS TIME
REPLACED STARTER - WARRANTY CLAIM # 304757572
Inspection on 22kw a/c. Have to replace rotor and stater. Warranty
PR19826727 $100 PR19826794 $65 WO001961161 $50
W76278 - 10/15/2022 Checked all fluids, cracked injectors and spun over to eliminate any air, pulled check valve and cleaned; emptied fuel filters incase of water contamination; spun unit over started unit. Shutdown and restarted 10 times and let run 45 minutes. 10/16/2022 returned to verify that unit would run after repairs. Let run 45 more minutes to confirm. Repair Complete