403 Headquarters Dr. Unit 5
Millersville, MD 21108
(443) 396-3797

Job Locations
for berwyn heights, md


Map of Berwyn Heights MD
Alex W.

Alex W.


Job Checkin

Customer has a 125 amp max panel in basement This collusion includes removing 100 amp seu cable and installing a 200 amp seu cable from overhead line down to a new meter can. Customer has pepco and they do not supply meter cans so we will provide one and install it on side of home. We will also install 2 new ground rods outside of home and run a number 4 ground wire to both of them then into the new panel. We will remove existing electrical panel and install a new moister barrier board for new panel. We will install a 200 amp 42 space main breaker electrical panel We will install all new ARC fault and ARC fault gfci combo breakers to replace the ones that were already in existing electrical panel and label panel We will install a whole home surge protector to protect homes electronics and homes utilities from potential power surges Customers cold water ground is already done correctly and the home can not be bonded at the water heater due to pvc pipes Permits and inspections. Pg coun